Programming manual SCU-series
HB-37500-820-10-12F-EN SCU Programming manual
Page 154 of 252
Status: 19.03.2021
4.13.2.2. Listing of the startup types via the
“
Enable
” button
The input of the start element to be monitored must be connected with the output of the input
element by the description
“Start
element”.
Various elements can be monitored.
Figure 141 Start block / reset block connected with monitored start
Information
: When the corresponding input element is edited, the connection to the start element
is deleted, and cannot be restored any more. After the connection has been deleted, it must be
manually completed.
•
Input: signal n
o
: 1
Like with the input elements, this selection list is used to determine the input in the SCU
module, with which the button for the start element shall be connected. Internally, this input
is restricted to the assignation to a basic module (I0.1 to I0.14).
•
Use
as “alarm reset (normally open contact) “
If this option is set, the corresponding button can be used to reset (to quit) a device alarm
that can occur during operation. Thus, the user is not forced to reset an occurring error with
the
“Function“ button
at the SCU module. A special programme code is created, but in case
of an alarm reset this input is directly processed by the SCU module.
Information
: If a reset element is used, no monitoring of the cross-connection can be
processed for this input. In this case, the test of the cross-
connection is set to “AUS”
[“OFF”]
.