COMPLIANCE

 

STANDARD

 

 
 
 
 
 
 
 
 
 
 
 
 

CONNECTION

 

DESCRIPTION

 

 
 
 

 

 
 
 

EIA-232 Serial Connection  

 
 
 
 
 
 
 
 
 

 

 
 
 
 
 

ATS CPU 

 
 
 
 
 
 
 
 
 

 

BayTech units are in accordance with the general requirements of 

Standard for Information 

Technology Equipment

 (ETL listed, conforms to ANSI/UL 60950-1 2

nd

 Edition and CAN/CSA C22.2 

No. 60950-00. CE conforms to IEC 60950.) 

Equipment installations are to be in accordance with the 

Canadian Electrical Code, Part I, CSA C22.1-02; General Requirements – Canadian Electrical, Part 
II, CSA C22.2 No 0-M91; the National Electrical Code, NFPA 70-2005; and the National Electrical 
Safety Code, NFPA, IEEE C2-2002. 

We welcome any comments you may have about our products, and we hope that you will continue to 
look to BayTech for your remote management needs.

 

BayTech's Modular Series unit provides a Serial EIA232 interface that controls user access and outlet 
controls to the power strip.  

CAUTION:

 All power should be removed from the BayTech unit prior to removing or installing 

cables and /or adapters. 

ATTENTION: 

Tout pouvoir doit être retiré de l'unité BayTech avant de retirer ou d'installer des 

câbles et / ou des adaptateurs

 

The Module has an RJ-45 port which uses an 8-pin crossed modular cable to connect to a local EIA-
232 device such as a computer terminal or external modem. Most serial computers do not have RJ-45 
connections; therefore an adapter is provided with this unit to convert from a DE-9 connector to an RJ-
45 connector (Bay Tech Part No. 9FRJ45PC-4). An adapter to convert from a DB-25 connector to an 
RJ-45 connector is also available from Bay Tech, upon request (Bay Tech Part No. 25FRJ45PC-4). 
The 8-pin crossed modular cable is configured to operate with these adapters.  

NOTE: 

Custom cables are available to connect a device to this unit’s serial port. These custom 

cables are one-way cables labeled with Baytech on one end and a device name on the other end.  

REMARQUE: 

les câbles sur mesure sont disponibles pour connecter un périphérique au port 

série de cet appareil. Ces câbles sont des câbles de commande à sens unique marqué par 
Baytech à une extrémité et un nom de périphérique à l'autre extrémité.

 

Units built after 2010, have Atmel Flash CPUs installed. The internal processer can be upgraded via 
the EIA232 Serial port. The user will need to download the AVRProg.exe program from 

www.avrfreaks.net

 or use internet search engine. Contact Baytech Support for the latest ATS firmware 

file and upload instructions. 

Содержание ATS Series

Страница 1: ...Page 1 2019 COPYRIGHT 2019 Bay Technical Associates Inc 1 1 2019 Transfer Switch ATS ...

Страница 2: ...d 15 Change ATS Voltage Switching Points 15 Change ATS Switch Back Mode Time 15 Change ATS Delay Switch to Secondary 16 Change Buzzer Audible Alarms 17 Display Current Electrical Characteristics 18 Logging Out 18 Current User Password 18 Identify Current User 19 Unit Identification 19 Setting Source Input Primary 19 SETUP OPTIONS 19 ATSSET 19 Default Set Points 19 Frequency Set 19 Voltage Set 20 L...

Страница 3: ... dommages à l équipement IMPORTANT This term is used to denote conditions that could result in the loss of communications or to highlight the proper functioning of equipment IMPORTANT Ce terme est employé pour dénoter les conditions qui pourraient avoir comme conséquence la perte de communications ou accentuer le fonctionnement approprié de l équipement NOTE This term is used to denote items of in...

Страница 4: ...odule has an RJ 45 port which uses an 8 pin crossed modular cable to connect to a local EIA 232 device such as a computer terminal or external modem Most serial computers do not have RJ 45 connections therefore an adapter is provided with this unit to convert from a DE 9 connector to an RJ 45 connector Bay Tech Part No 9FRJ45PC 4 An adapter to convert from a DB 25 connector to an RJ 45 connector i...

Страница 5: ...ptacle L accès à l emplacement d installation devrait être limité au personnel autorisé L installation de ces unités devrait être limitée à ITE et à environnements de serveur de Telco CAUTION This unit is intended for indoor use only Do not install near water or expose this unit to moisture To prevent heat buildup do not coil the power cord when in use Do not use extension cords Do not attempt to ...

Страница 6: ...Pour l ÉQUIPEMENT QUE L ON PEUT BRANCHER la douille sortie sera installée près de l équipement et facilement accessible Les sorties fournissant la puissance à l unité seront protégées contre le courant le court circuit et le défaut de terre finis par les dispositifs protecteurs évalués appropriés 208V 24A 3øY Rated Model 30A Maximum Over current protection Device 208V 16A 3øY Rated Model 20A Maxim...

Страница 7: ... 25 Pin Signal DTR 1 1 4 20 DSR GND 2 2 1 GND RTS 3 3 7 5 CTS TXD 4 4 3 2 RXD RXD 5 5 2 3 TXD DSR 6 N C 6 6 DTR GND 7 7 5 7 GND CTS 8 8 4 RTS DTR 4 DCD DCD 8 1 8 DTR RI 9 22 Depending on if the unit has circuit breakers in the case of power overload the circuit breaker automatically trips Determine the cause of the tripped circuit breaker correct the problem then reset the circuit breaker by depre...

Страница 8: ... RJ45 to RJ45 Figure 2 RJ08X007 Pin Out Figure 3 RJ45 Connector Plug Adapters Figure 4 9FRJ45PC Cisco Adapter Pin Out Figure 5 9FRJ45PC 1 Adaptor Pin Out Use with RJ08X007 Cable And B C switch in C Use with RJ08X007 Cable And B C switch in B ...

Страница 9: ...ow for Cisco s PC cable to operate in most cases but not all Indicators ALM Red LED Over current alarm or an abnormally input voltage PWR Green LED power is connected to the unit through either source 1 or 2 Source 1 Green LED lit indicates unit is using Source 1 as the Input power Source 2 Green LED lit indicates unit is using Source 2 as the Input power Only one of the source LEDs will be lighte...

Страница 10: ... a blinking cursor Type 5 semi colons there is a one second delay before the menu is displayed 5 You should get a Status menu similar to the one seen below ATS Series C 2014 Baytech F1 18 Option s Installed True RMS Voltage True RMS Current Internal Temperature Unit ID ATS Series Primary Source 1 Source 2 121 2 Volts Power True RMS Peak RMS True RMS Average Volt Source Current Current Voltage Powe...

Страница 11: ...list of commands ATS The Status Menu will display after the user logs in if a login is required This menu lists the firmware version installed options primary source secondary source voltage primary source current voltage and power and the internal temperature of the ATS unit If there are users installed on the unit a login will be required This may have a password or not It is recommended that at...

Страница 12: ...isable Status Menu 4 Change Unit ID 5 Change Alarm Threshold 6 Change ATS Switching Voltage Points 7 Change ATS Switch Back mode time 8 Change ATS Delay Switch to secondary 9 Change Buzzer Audible Alarms X Exit Enter Request Select 1 from the configure menu to allow the admin user to add and delete users change passwords and change the outlet list The following menu appears if the unit has been re...

Страница 13: ...er NOTE If you delete the user in the first position the ATS will display the following You are deleting the current admin user The next user will become the admin user do you want to continue Y N IMPORTANT The unit must have had a power cycle or unit reset command performed recently prior to deleting the user in the first position This action will prevent the unit from having No Admin user assign...

Страница 14: ...let number s Select 3 to add all outlets to user access The unit will display Y for all outlets Select 4 to remove all outlets from a user The unit will display Y for all outlets Select 2 from the Configure Menu allows the admin user to change the names of the outlets Select this option and the unit displays all of the outlet names Default name is Outlet 1 Outlet number of outlets on unit Enter Re...

Страница 15: ...t voltage switching points The processor uses a 6 cycle window to determine if the voltage is greater than zero but less than the trip threshold This should only be set after the ATSSET command has been performed This value can be tweaked according to loading It is recommended that the default values be maintained Enter Request 7 Disable switch back to primary Y N n Current delay switch back to pr...

Страница 16: ...econdary source time is 3 Seconds Change delay switch to secondary time Y N Y Enter seconds 1 255 Enter Request 8 Disable delay switch to secondary Y N Y Enter Request Type N and press Enter The unit will display the current switch time and ask if you want to change the time Type N and press Enter and you will be sent back to the config menu Type Y and press Enter You will be asked to enter a time...

Страница 17: ...r The unit will display Y N option Type Y and press Enter to disable the Over Current Buzzer Type N and press Enter to maintain current alarm state 1 Power loss buzzer alarm Off Default off 2 Over current buzzer alarm On Default On Enter Request 2 Press Enter The unit will display Y N option Type Y and press Enter to disable the Over Current Buzzer Type N and press Enter to enable the buzzer If th...

Страница 18: ...C3 202 4 Volts Circuit C4 202 1 Volts Circuit C5 204 5 Volts Circuit C6 205 8 Volts Total kW h 0 Circuit Average Volt Group Power Amps Circuit M1 0 Watts 4 VA Circuit M2 0 Watts 4 VA Circuit M3 0 Watts 4 VA Circuit M4 0 Watts 4 VA Circuit M5 0 Watts 4 VA Circuit M6 0 Watts 4 VA Int Temp 95 9 F Ext 1 72 1 F 31 5 RH Ext 2 70 9 F Note Units with probes connected to external sensor ports will be displ...

Страница 19: ...he new user name Type Unitid at the prompt to determine the Unit ID the unit will display the following To change the unit ID Go to the Outlet Configuration menu and select Change Unit ID option The maximum field length is 32 or 16 for older unit Unit ID ATS18 Type ATSSET at the prompt sets the pre defined switch over points for power loss and brownout The preset values are listed below The menu d...

Страница 20: ...o secondary power and back The processor uses cycle window to determine if the power is at Zero These values are preset when an ATSSET routine is run Changing the values is allowed but could cause the unit to operate in ways not previously determined It is recommended that the default values be used ATS losspsp Primary to secondary trip primary voltage value 138 5 Volts Modify Y N y Enter Secondar...

Страница 21: ...nless approved by BayTech management Replacements for defective products may be cross shipped to the customer at no cost if requested within 30 days of date of purchase At BayTech s discretion this period may be extended to 90 days For additional information or more specific warranty issues contact BayTech s Technical Support Department at 800 523 2702 or 228 563 7334 This warranty does not cover ...

Страница 22: ...tech net Return policy refers to BayTech products purchased and returned for credit or repair A Return Authorization RA number must be obtained in all cases before returning the BayTech product Have the serial number and reason for the return or description of the problem handy Customers in the Continental U S can call 1 800 523 2702 or international customers can call 228 563 7334 to obtain an RA...

Страница 23: ...close a letter with name address RA number daytime phone number and description of the problem 3 Surround your unit with a minimum of two inches of insulation 4 Be sure to seal the box securely with strapping or packing tape We do not recommend masking tape or cellophane tape 5 Mark the RA number clearly on the outside of the package 6 Ship the unit by insured prepaid carrier to the following addr...

Страница 24: ...hat was requested has been added to the unit concerning when the alarm lights and buzzer sounds There is NO Silence the Alarm 1 If the Alarm LED is light solid and the buzzer sounds without pauses you have an Over Current condition a Solution clear the over current condition 2 If the Alarm LED is light intermittent and the buzzer sound intermittent on a cyclic rate of long beep long pause than bee...

Страница 25: ...e wrap bag 1U Bracket part number M140R115 Attach brackets to the each of the unit s side panel with two screws Verify both brackets are facing the same direction on the unit once attached 2U Bracket part number M140R114 Attach brackets to the each of the unit s side panel with two screws Verify both brackets are facing the same direction on the unit once attached Attach brackets and unit to rack ...

Отзывы: