46
1.1
INTRODUCTION
The
“Slim HPS”
are hot water generators
designed for medium-sized heating plants.
Are designed and built in accordance with
the european directives 2009/142/CEE,
2004/108/CEE, 2006/95/CEE and
92/42/CEE.
These appliances can be fired by natural
gas (methane) and butane gas (G30) or
propane gas (G31).
The instructions given in this manual are
provided to ensure proper installation and
perfect operation of the appliance.
1
DESCRIPTION OF THE BOILER
1.2
DIMENSIONS
Fig. 1
R C.H. return
1
1
/
2
”
M C.H.
flow
1
1
/
2
”
G Gas
connection
1”
S Boiler/filling
drain
3/4”
L
D
P
A
mm
ø mm
mm mm
1.80
940
180
645 415
1.99
1140
225
645 415
1.110
1240
250
670 400
1.3
TECHNICAL FEATURES
Slim HPS
1.80
1.99
1.110
Heat output
kW
56.0-78.7
69.9-98.6
74.7-107.9
Heat input
kW
62.2-87.4
77.7-109.5
85.5-120.5
Sections
n°
9
11
12
Power consumption
W
16
16
69
Maximum water head
bar
4
4
4
Test pressure
bar
6
6
6
Water content
l
28
34
37
Category
II
2H3+
II
2H3+
II
2H3+
Type
B
11BS
B
11BS
B
11
Smokes temperature
°C
160
144
140
Smokes flow
kg/h
180
287
330
Maximum temperature
°C
95
95
95
C.H. setting range
°C
40÷85
40÷85
40÷85
Main burner nozzles
Quantity
n°
8
10
11
Natural gas
ø mm
2.95
2.95
2.95
G30 - G31
ø mm
1.70
1.70
1.70
Gas consumption *
Natural gas
m
3
st/h
9.2
11.6
12.7
Butane (G30)
kg/h
6.8
8.5
9.3
Propane (G31)
kg/h
6.7
8.3
9.1
Burner gas pressure
Natural gas
mbar
4.6 - 9.1
4.7 - 9.3
4.6 - 9.3
Butane (G30)
mbar
12.3 - 25.4
12.5 - 25.1
12.6 - 25.6
Propane (G31)
mbar
16.1 - 30.2
16.6 - 32.7
16.6 - 34.3
Gas supply pressure
Natural gas
mbar
20
20
20
Butane (G30)
mbar
30
30
30
Propane (G31)
mbar
37
37
37
Weight
kg
266
322
350
* The gas consumptions refer to the calorific value at standard conditions at 15°C - 1013 mbar.