INSTRUCTIONS FOR THE INSTALLER
0402_2507
Figure 11
A 90° bend reduces the total duct length by 0.5 metre.
A 45° bend reduces the total duct length by 0.25 metre.
IMPORTANT
: Ensure a minimum downward slope of
1 cm
toward the boiler per
each metre
of duct length.
Make sure that the exhaust and intake ducts are securely fixed to the walls.
(L1 + L2) max = 80 m
L max = 15 m
0207_0907
010828_0600
The maximum length of the suction
duct must be 15 metres.
SEPARATED HORIZONTAL FLUE TERMINALS INSTALLATION OPTIONS