50
7113868.01 - en
INSTRUCTIONS FOR FITTERS
Description of parameter
Factory settings
140 Fi
240 Fi
240 i
280 i
280 Fi
F01
Type of boiler
10
= sealed chamber -
20
= atmospheric chamber
10
10
20
20
10
F02
Gas used
00
= METHANE -
01
= LPG
00 or 01
F03
Hydraulic system
06
F04
Programmable relay 1 setting
(See SERVICE Instructions)
02
F05
Setting programmable relays 2
(06 = DHW pump - See SERVICE Instructions)
06
F06
Ext sensor configuration
(See SERVICE Instructions)
00
F07…F12
manufacture information
00
F13
CH max. output
(0-100%)
100
F14
DHW max. output
(0-100%)
100
F15
Min. heating output
(0-100%)
00
F16
Maximum CH setpoint (°C)
00
= 85°C -
01
= 45°C
00
F17
Pump overrun time in heating mode
(01-240 minutes)
03
F18
Burner ignition delay in CH mode
(00-10 minutes) - 00=10 seconds
03
F19
manufacture information
07
F20
manufacture information
00
F21
Anti-legionella function
00
= Disabled -
01
= Enabled
00
F22
manufacture information
00
F23
Maximum DHW setpoint
60
F24
manufacture information
35
F25
No water safety device
00
F26…F29
manufacture information
(read-only parameters)
--
F30
manufacture information
03
F31
manufacture information
00
F32…F41
Diagnostics (See SERVICE Instructions)
--
Final
parameter
Calibration function activation
(See SERVICE Instructions)
0
20. PARAMETER SETTINGS
To set the boiler parameters, press
R
and
-
(
) together and hold down for at least 6 seconds.
When the function is activated, the display shows “
F01
” alternated with the value of the parameter.
Edit parameters
r 1SFTT
+/-
CVUUPOTGPSTDSPMMJOHQBSBNFUFST
r 1SFTT
+/-
CVUUPOTUPDIBOHFUIFTJOHMFQBSBNFUFSWBMVF
r 1SFTT UIF
P
button to save changes, the display shows
“
MEM
u
r 1SFTTUIF
,
button to leave the function without saving,
the display shows “
ESC
”.
0704_1902
WARNING:
do not modify the values of the “Manufacturer information” parameters.