Baxi Luna HT Troubleshooting Guide 

E119 

Low Water Cut-off Pressure 

Switch Activating 

1-

Ensure all air is purged from the system and all shutoff valves are open

2-

Check boiler and system for leaks

3-

Ensure the pressure in the expansion tank is 11.6 psi

4-

Fill the system between 1 and 1.5 bar on the pressure gauge.

5-

If an E119 error code persists jump the leads on the low water cutoff. If the boiler
fires up change the low water cutoff switch.

NOTES: 

E130 

Flue Gas Temperature 

Sensor/ Air Pressure Switch 

If unit 

can

 be reset (Pressure Switch Activated) 

1-

Check for obstructions in the venting and termination

2-

Ensure the venting is within the maximum venting length requirements

3-

Make sure there is water in the condensate trap

4-

Check that the proper QAA73 parameter values have been adjusted with respect to
gas type, venting length and altitude. Refer to installation manual for values

5-

Check the silicone tubes coming from the air pressure switch for kinks, melting and
holes, make sure that the low pressure opening at the back of the unit is not
blocked.

6-

Ensure that there are no loose wires and that the pressure switch is opening and
closing properly

7-

Reset boiler and analyze the combustion gas to ensure the correct CO2 and CO
values. Refer to the installation guide for combustion specifications.

Note:

 When CO levels are significantly higher than the numbers above the boiler’s 

specifications it is recycling products of combustion. Check all gasket seals between the flue 
and air intake venting connections. 

If unit 

cannot

 be reset (Flue High Limit has Activated) 

1-

The flue high limit has a red manual reset button in the center of the sensor.

2-

Check for obstructions in the venting and termination

3-

Ensure the venting is within the maximum venting length requirements

4-

Check that the proper QAA73 parameter values have been adjusted with respect to
gas type, venting length and altitude. Refer to installation manual for values

5-

Reset boiler and analyze the combustion gas to ensure the correct CO2 and CO
values. Refer to the installation guide for combustion specifications.

Note:

 When CO levels are significantly higher than the numbers above the boiler’s 

specifications it is recycling products of combustion. Check all gasket seals between the flue 
and air intake venting connections. 

NOTES: 

E133 

Burner Lockout 

No Spark: 

1-

Check ground and polarity back to the circuit breaker

2-

Ensure the boiler is on a dedicated circuit

3-

Check for 30 V DC going to the spark generator

If there is voltage to the spark generator change the spark generator. If there is no voltage to 
the spark generator change the main control board. 

Содержание Luna HT Residential series

Страница 1: ...Energy Efficient Environmentally Friendly Heating Solutions Baxi Luna HT Residential Troubleshooting Guide ...

Страница 2: ...O HAVE SUCCESSFULLY COMPLETED THE BAXI INSTALLATION PROGRAM USE OF THE INFORMATION HEREIN FOR THE PURPOSES OF ONSITE APPLIANCE CORRECTION BY UNTRAINED PERSONNEL MAY CAUSE EXTREMELY DANGEROUS CONDITIONS AND MAY VOID THE MANUFACTURER S WARRANTY BAXI N A ASSUMES ABSOLUTELY NO LIABILITY IN THE EXECUTION OF THE TRAINING SUGGESTIONS IN THIS DOCUMENT SHOULD YOU EXPERIENCE PROBLEMS OR COMPLICATIONS BEYOND...

Страница 3: ...TWO DIGITS E1 FOLLOWED BY THE LAST TWO DIGITS 33 IF AN ERROR CODE APPEARS YOU WILL NEED TO RESET THE BOILER USING THE TOGGLE SWITCH ON THE LEFT HAND SIDE OF THE CONTROL PANEL TURN THE TOGGLE SWITCH TO THE R POSITION RESET FOR THREE SECONDS FIG 2 3 AND THEN LET GO THE TOGGLE SWITCH SHOULD GO TO THE WINTER MODE POSITION FIG 2 1 AND ATTEMPT IT S SEQUENCE OF OPERATION PROVIDING THERE IS A CALL FOR HEA...

Страница 4: ... paste NOTES E50 DHW NTC Sensor Fault 1 Take an ohm reading of the DHW NTC sensor If the NTC sensor is out of calibration replace the faulty sensor 2 Check for a resistance in terminals 9 and 10 on the M2 connector Only for heating boilers 3 If utilizing an indirect tank sensor take an ohm reading using chart C If the sensor is faulty replace it If the sensor is working check parameter 651 on the ...

Страница 5: ...e the correct CO2 and CO values Refer to the installation guide for combustion specifications Note When CO levels are significantly higher than the numbers above the boiler s specifications it is recycling products of combustion Check all gasket seals between the flue and air intake venting connections If unit cannot be reset Flue High Limit has Activated 1 The flue high limit has a red manual res...

Страница 6: ...s try cleaning the flame sensor Note Do not clean the flame sensor using sandpaper as it may damage the protective coating If the sensor is dirty check you re venting to ensure you are not recycling products of combustion Also ensure that your QAA73 parameters are correct for the type of gas you are using NOTES E160 Fan Speed Thresholds not Reached 1 Check QAA73 fan speed parameters values have be...

Страница 7: ...H loop If it is going through the CH loop replace the paddles inside the diverter valve and clean the diverter valve 2 Clean the DHW plate heat exchanger 3 Check the DHW NTC sensor 4 Check the Combustion NOTES No Error code Boiler Short Cycles 1 Make sure the combustion settings are correct for the unit and its application 2 Make sure your heat load is adequate for the boiler NOTES No Error code B...

Страница 8: ...esistance C Ω Part Resistance Gas Valve 380 1 330 1 3 1250Ω 5 1 450 1 650 1 3 1180Ω 5 1 100 EV1 620 Ω 5 EV2 3356Ω 5 Pump 380 1 330 45 Ω 5 3 Way Motor 380 1 330 1480 Ω 5 Fan 380 1 330 9 Ω 5 Spark Generator 380 1 330 370 Ω 5 DHW Flow Sensor 380 2706 Ω 5 ...

Отзывы: