25
020429_0400
Figure 15
To simplify calibration of the gas valve, the “calibration function” can be set directly on the boiler
control panel by proceeding as follows:
1) Press the keys (2-3) together until the display shows the pointer “ ” alongside the symbol
(about 6 seconds).
2) Press the keys to set the fan speed at the minimum and maximum heat output (%PWM);
N.b - to set the
minimum
and
maximum
heat output quickly, press the keys respectively;
3) press either of the two keys to exit the function.
LUNA HT 1.240
G20 - 2H - 20 mbar
G31 - 3P - 37 mbar
LUNA HT 280
CO
2
max. heat output
8,7%
10%
CO
2
min. heat output
8,4%
9,5%
Gas nozzle
7,5 mm
7,5 mm
Table 1c
Table 1b
LUNA HT 330
G20 - 2H - 20 mbar
G31 - 3P - 37 mbar
LUNA HT 1.280
CO
2
max. heat output
8,7%
10%
CO
2
min. heat output
8,4%
9,8%
Gas nozzle
12,0 mm
12,0 mm
Table 1a
LUNA HT 330
Gas consumption at 15 °C
G20 - 2H - 20 mbar
G31 - 3P - 37 mbar
1013 mbar
PCI
34.02 MJ/m
3
46.3 MJ/kg
Consumption at max. heat output
3.59 m
3
/h
2.64 kg/h
Consumption at min. heat output
1.06 m
3
/h
0.78 kg/h
Table 2a
IMPORTANT:
in the case of conversion from natural gas to propane (LPG), the following operations
must be performed before calibrating the gas valve as illustrated above:
• Turn adjuster screw (V) on the gas valve through the number of complete revolutions specified in
table 3 or 3.1;
• On the control panel display set ignition power parameters H608 and H611. The values to be input
are given in table 3 or 3.1. The programming methods are described in chapter 17;
LUNA HT 1.120
G20 - 2H - 20 mbar
G31 - 3P - 37 mbar
CO
2
max. heat output
8,7%
10%
CO
2
min. heat output
8,4%
9,5%
Gas nozzle
4,0 mm
4,0 mm