2
%)
For correct boiler operation, the content of (CO
2
- O
2
) in the combustion fumes must observe the tolerances indicated in the
following table. If the value of (CO
2
- O
2
) is different, check the electrodes and their relative distances. If necessary, replace the
electrodes and position them correctly. If the problem persists, use the following function.
G20
G31
CO
2
%
O
2
%
CO
2
%
O
2
%
Maximum power
Nominal value
8.7
5.4
10.0
6.0
Permitted value
8.2 - 9.3
6.3 - 4.3
9.5 - 10.5
6.8 - 5.2
Ignition power
Nominal value
8.7
5.4
10.8
4.8
Permitted value
8.2 - 9.3
6.3 - 4.3
10.3 - 11.3
5.5 - 4.1
Minimum power
Nominal value
8.8
5.2
10.0
6.0
Permitted value
8.2 - 9.3
6.3 - 4.3
9.5 - 10.5
6.8 - 5.2
The
CO
2
/O
2
values are with the cover closed.
The combustions analisys shall be done using an analyzer regularly calibrated.
During normal operation the boiler performs combustion control cycles. In this phase, CO values higher than 1000 ppm can
occur for brief periods of time.
COMBUSTION ADJUSTMENT FUNCTION (CO
2
%)
This function sets out to partially adjust the value of
CO
2
%
. The following procedure is used.
•
Press buttons
and
together for at least 6 seconds. When the function is enabled, the displays shows “
On
” for a few
seconds followed by programme row “
304
” alternated with the
%
of boiler power.
•
After the burner is lit, the boiler reverts to maximum DHW power (100). When the display shows "
100
" it is possible to partially
adjust the value of
CO
2
%
;
• press
. The display shows "
00
" alternating with the function number "
304
" ( flashes);
• press
to raise or lower the amount of
CO
2
(from -5 to +5).
• press
to save the new value and view the power value "100" on the display again (the boiler continues operating at
maximum DHW power).
This procedure can also be used to adjust the quantity of
CO
2
to the
ignition power
and to the
minimum power
by pressing
after point 5 of the procedure described above.
•
After saving the new value (point 5 of the procedure), press
to take the boiler to its
ignition power
. Wait for the value of
CO
2
to stabilise and then adjust as described in point 4 of the procedure (the power value is a number <> 100 and <> 0) then
save (point 5).
• press
again to take the boiler to
minimum power
. Wait for the value of
CO
2
to stabilise and then adjust as described in
point 4 of the procedure (power value = 00);
•
to exit the function, press the buttons for at least 6 seconds as described in point 1.
13. GAS VALVE
This appliance does not require any mechanical adjustment on the valve. The system ensures electronic auto-adaptation.
Gas valve key
Pi
Gas supply inlet pressure tap
13.1 GAS CONVERSION METHODS
Only an Authorised Technical Assistance Service can convert boiler operation from
NATURAL GAS
to
LPG
or vice-versa. To
perform calibration, set parameter
P02
as described in the PARAMETER SETTINGS section. Lastly, check the combustion
parameters as described in the SPECIAL FUNCTIONS - CHECKING COMBUSTION PARAMETERS section.
When the gas change is completed the boiler data plate must be amended to indicate the new gas data.
Pi
Содержание DUO-TEC COMPACT
Страница 23: ...23 7710400 01 06 18 r u...
Страница 25: ...25 r u 7710400 01 06 18 1 7 1 2 SI US 1 1 C 20 C 11 2 1 1 2 3...
Страница 28: ...7710400 01 06 18 28 r u 0 C 17 60 C 9 SECTION C G3 4 30 9 1 SECTION C A D B E C G1 2 G3 4 F...
Страница 38: ...7710400 01 06 18 38 r u 16 0 5 5 30 24 10 24 3 17 SECTION E Q H 18 SECTION F...
Страница 40: ...7710400 01 06 18 40 r u 19 4 CO2 CO2 6 On 3 303 1 ESC...
Страница 68: ...7710400 01 06 18 68 S E C T I O N C...
Страница 69: ...69 S E C T I O N C 7710400 01 06 18 A B C D E F 65 65 65 65 31 5 70 38 5 105 162 5 153 5 22...
Страница 70: ...7710400 01 06 18 70 S E C T I O N D 25 mm...
Страница 72: ...7710400 01 06 18 72 S E C T I O N E...
Страница 73: ...73 S E C T I O N F 7710400 01 06 18...
Страница 74: ...7710400 01 06 18 74 S E C T I O N G 2 1 D A C G H E F B...
Страница 75: ...75 S E C T I O N G 7710400 01 06 18...