background image

1.0 Introduction

4

1.1

Description

1. The Baxi Brazilia F is a range of room sealed
gas convector appliances designed to be used
with gas type G20 (Natural Gas) at supply
pressure 20 mbar. When converted using the
below kits the non thermostatic range is also
suitable for use with gas type G31 (Propane) at
supply  pressure 37 mbar.

LPG Kits

F 5 & F 5S   5110284
F8S  

5110285

The procedure for installation, servicing etc. is the
same for both Natural Gas and Propane models.

2. The appliance provides warm air by natural
convection and flueing is by means of a
concentric balanced flue arrangement.

3. Except for Comfort Stat, the appliance is
controlled by a control knob which operates the
ignition and alters the heat output. The control
knob has five positions giving a choice of three
output rates:

4. (Comfort Stat only)
The appliance is controlled by a control knob
which operates the ignition and alters the
temperature setting, the knob has four positions.

1.2

Installation

1. The appliance is suitable for installation only in
G.B. and I.E. and should be installed in
accordance with the rules in force. For Ireland
install in accordance with I.S.813 “Domestic gas
installations”. The installation must be carried out
by a CORGI Registered Installer or other
competent person and be in accordance with the
relevant requirements of 

G

AS

S

AFETY

(Installation

and Use) 

R

EGULATIONS

latest edition, the 

B

UILDING

R

EGULATIONS

issued by the Department of the

Environment, 

B

UILDING

S

TANDARDS

(Scotland)

(Consolidation) 

R

EGULATIONS

issued by the

Scottish Development Department and the 

L

OCAL

B

UILDING

R

EGULATIONS

.

Where no specific instructions

are given, reference should be made to the relevant

BRITISH STANDARD CODES OF PRACTICE.

2.

This appliance must be installed in accordance

with the manufacturers instructions and the rules
in force.

3.

Read the instructions before installing or using

this appliance.

NOTE:

All illustrations show F 5S, unless

otherwise indicated. The procedure for
installation, commissioning, servicing etc. is the
same for all Brazilia F models.

Notice

Discolouration of wall surfaces

Most heating appliances generate warm air convection currents and

transfer heat to any wall surface against which they are situated.

Some soft furnishings (such as blown vinyl wallpapers) may not be

suitable for use where they are subject to temperatures above normal

room levels and the manufacturer's advice should be sought before

using this type of wall covering adjacent to any heating appliance.

The likelihood of wall staining from convected air currents will be

increased in environments where high levels of tobacco smoke or other

contaminants exist.

Position

Position

Position

Position

Position

OFF

LOW

IGNITION

MEDIUM

HIGH

l

ll

lll

Baxi Brazilia F 5

Baxi Brazilia F 5S

Baxi Brazilia F 8S & F 8ST

Fig. 1

Fig. 2

Fig. 3

IMPORTANT:

The appliance must only be

used on its designated gas type. This is

indicated on the data label.

Position

Position

OFF

IGNITION PRESET

HIGH

LOW

*

1.3

Important Information

This product contains Refractory Ceramic Fibres (RCF), which are man-made vitreous silicate fibres. Excessive exposure to these materials may cause
irritation to eyes, skin and respiratory tract. Consequently, it is important not to touch or disturb the burner surface to ensure that the release of dust is kept
to a minimum.
To ensure that the release of fibres from these RCF articles is kept to a minimum, during installation and servicing it is recommended that you use a HEPA
filtered vacuum to remove any dust and soot accumulated in and around the fire before and after working on the fire.
When replacing the the burner surface we recommend that the replaced items are not broken up, but are sealed within a heavy duty polythene bag, clearly
labelled as RCF waste. RCF waste is classed as a stable, non-reactive hazardous waste and may be disposed at a landfill licenced to accept such waste.
Protective clothing is not required when handling these articles, but we recommend the use of suitable gloves to prevent irritation. We also recommend you
follow the normal hygiene rules of not smoking, eating or drinking in the work area and always wash your hands before eating or drinking.
This appliance does not contain any component manufactured from asbestos or asbestos related products.

© Baxi Heating U.K. Limited 2007.

Содержание Brazilia Comfort Stat F 8ST Oak

Страница 1: ...ak Balanced Flue Gas Wall Heaters Installation and Servicing Instructions Please leave these instructions with the user 3003035 03 Baxi Brazilia F 5 Baxi Brazilia F 5S Baxi Brazilia F 8ST Comfort Stat Baxi Brazilia F 8S Baxi Heating U K Limited 2007 ...

Страница 2: ...075 03A Baxi Brazilia F 8S Mahogany G C No 35 075 03A Baxi Brazilia F 8S Oak G C No 35 075 03A Baxi Brazilia Comfortstat F8ST Oak G C No 35 075 09 Propane Baxi Brazilia F 5 Propane G C No 35 075 04A Baxi Brazilia F 5S Grey Propane G C No 35 075 05A Baxi Brazilia F 8S Grey Propane G C No 35 075 06A Baxi is a BS EN ISO 9001 Accredited Company For GB IE only Baxi Heating U K Limited 2007 Baxi Heating...

Страница 3: ...9 1 F 8S F 8ST 24 4 One person should be sufficient to lift the fire If for any reason this weight is considered too heavy then obtain assistance When lifting always keep your back straight Bend your legs and not your back Avoid twisting at the waist It is better to reposition your feet Avoid upper body top heavy bending Do not lean forward or sideways whilst handling the fire Always grip with the...

Страница 4: ...colouration of wall surfaces Most heating appliances generate warm air convection currents and transfer heat to any wall surface against which they are situated Some soft furnishings such as blown vinyl wallpapers may not be suitable for use where they are subject to temperatures above normal room levels and the manufacturer s advice should be sought before using this type of wall covering adjacen...

Страница 5: ...tween low and high temperature settings Flame failure device Thermocouple Output 8 13mv Heat Exchanger Cast Iron 2 0 Technical Data 5 F 5 F 5S Natural Gas Category of Appliance II2H3P The appliance is set for Gas Type G20 at 20mbar Heat Input gross High Med Low kW 2 05 1 41 0 86 Btu h 7 000 4 800 3 000 Heat Output gross High Med Low kW 1 5 0 98 0 57 Btu h 5 100 3 350 1 950 Setting Pressure Cold mb...

Страница 6: ...ata F 5 F 5S Propane When converted using kit No 5110284 Category of Appliance II2H3P The appliance is set for Gas Type G31 at 37mbar Heat Input gross High Med Low kW 2 05 1 41 0 86 Btu h 7 000 4 800 3 000 Heat Output gross High Med Low kW 1 5 0 98 0 57 Btu h 5 100 3 350 1 950 Setting Pressure Cold mbar 36 5 1 in wg 14 6 0 4 Injector Size 74 Nox Class 3 Gas Rate on HIGH 0 077 m3 h 0 146 kg h Gas C...

Страница 7: ... Gas Installations in Timber Framed Dwellings IMPORTANT LPG Models This appliance must not be installed below ground in basements cellars etc unless these are open to ground level on one side For further guidance see BS 5871 Pt 1 3 2 Clearances 1 The appliance must be fitted on a vertical flat non combustible wall Any combustible wall coverings should be removed from within the area of the outer c...

Страница 8: ...dow capable of being opened or any ventilation inlet or similar opening no part of the terminal shall be within 300mm 1 ft measured vertically from the bottom of the opening b Where the flue terminal of the appliance is less than 2m 6 ft above the level of any ground balcony flat roof or place to which any person has access and which adjoins the wall in which the flue terminal is situated the term...

Страница 9: ...sses from 248mm 93 4 in to 349mm 133 4 in 2 Three further flue terminals are available as optional extras to suit the wall thicknesses indicated in the table opposite 3 5 Ventilation 1 The appliance is room sealed and therefore requires no purpose built ventilation 2 It is intended for use in habitable rooms and must not be fitted in cupboards or confined compartments 3 6 Gas Supply 1 The inlet co...

Страница 10: ...mm 3 4in Adjust the distance from the back of the airbox and the joint between the terminal and air duct to this dimension Using the length of flue tape provided fix this dimension by taping up the joint between the flue duct assembly and the flue outlet 3 Offer the appliance up to the wall pushing the terminal and flue ducting through the wall 4 Ensuring that the appliance is level secure it to t...

Страница 11: ...e OFF position 2 Remove the knob from the appliance by gently pulling the knob forward Fig 11 3 Fit the outer case by locating the slots in the outer case rear strip onto the four mounting lugs on the wall brackets Fig 13 4 Replace the control knob Fig 13 5 3 Instructing the User 1 Explain how to ignite the appliance and alter the heat settings 2 Show the position of the external gas service cock ...

Страница 12: ...h away any dirt from the heat exchanger casting If necessary clean the viewing window 13 With a light brush carefully remove deposits from the spark electrode burner flame ports and the burner gauze Fig 16 14 Replace the rope seal in the heat exchanger casting if it is damaged in any way Fig 15 Also examine the thermocouple and replace if necessary 15 Re assemble the injector washer and burner ass...

Страница 13: ...e airbox and undo the thermocouple nut from the gas tap Fig 22 24 3 Ease the thermocouple and electrode leads from the rubber grommet Fig 23 4 Disengage the burner from the injector and pull the electrode lead off the spark electrode Fig 22 5 Pull off the spark electrode lead at the rear of the igniter Fig 24 6 Remove the supply pipe from the gas tap 7 Undo the nut holding the gas tap to its retai...

Страница 14: ... burner inlet ensuring that it covers the primary aeration hole Fig 26 8 Reassemble in reverse order of dismantling 7 5 Injector 1 Remove the burner as described in sections 7 4 1 to 7 4 4 2 Undo the injector and sealing washer retaining the washer for use with the new injector If the washer is damaged it must be replaced Fig 28 3 Reassemble in reverse order of dismantling 7 6 Thermocouple 1 Remov...

Страница 15: ...8 0 Fault Finding 15 3 5 0 5mm 7 1 5mm Fig 29 Ensure all installation criteria have been satisfied before performing Fault Finding e g flue terminal position Baxi Heating U K Limited 2007 ...

Страница 16: ...iezo Igniter Generator 042941 I 381941 Injector F 5 F 5S 224047 J 381942 Injector F 8S F 8ST 224104 K 205791 Washer For injector 082365 L 205844 Insulation F 5 F 5S 224048 M E01359 Insulation F 8S F 8ST 223971 N 155654 Lead Electrode 043043 O E01360 Thermocouple 243215 P 384248 Tap Mag Unit Not F 8ST 082462 Q Thermostat Gas Control E94622 Bracket Assy 3002927 For LPG models only R Igniter Gas Tap ...

Страница 17: ...10 0 Notes 17 Baxi Heating U K Limited 2007 ...

Страница 18: ...10 0 Notes 18 Baxi Heating U K Limited 2007 ...

Страница 19: ...heating market Gas Central Heating Boilers Wall Floor and Fireside models Independent Gas Fires Renewal Firefronts Gas Wall Heaters Solid Fuel Fires If you require information on any of these products please write telephone or fax to the Sales Department Baxi Heating U K Limited 2007 ...

Страница 20: ...ne Erdington Birmingham B24 9QP www firesandstoves co uk The Baxi Helplines For General Enquiries 44 0 8706 061 064 For After Sales Service 44 0 8706 090 081 For Technical Enquiries 44 0 8706 061 065 Baxi Heating U K Limited 2007 ...