4.3
Fault messages
Code Meaning/effect
Cause/remedy
FE 206
Monitoring of the auger conveyor
is defective
The boiler is in operation.
Press the Reset button. If the fault reoccurs after a reset, inform Windhager
Customer Service or a heating technician.
FE 238
Feed is not sucking any pellets in
Check pellet supply in storage room
and feed hose. Press Reset.
No pellet feed is possible. The boiler does not operate.
a) No pellets at the suction probe – Set „probe switching“ to „automatic“ or
select another probe (see section 2.8.1.5). Press the Reset button.
b) Feed hose blocked at the intake or entry to the changeover unit – clear it.
Press the Reset button.
c) Inform Windhager Customer Service or a heating technician.
Emergency operation:
Switch off the feed unit (see section 2.8.1.3). Fill the reser-
ve supply container with pellets by hand, boiler may continue operating without
feed.
FE 239
Probe switching defective
Check the changeover unit.
Press Reset.
No pellet feed is possible. The boiler does not operate.
Press the Reset button. If the fault reoccurs after a reset, inform Windhager Custo-
mer Service or a heating technician.
Emergency operation:
Switch off the feed unit (see section 2.8.1.3). Fill the reser-
ve supply container with pellets by hand, boiler may continue operating without
feed.
FE 356
Combustion chamber pressure
not stable
The boiler is in operation.
a) Heating surface cover leaking, check whether this is firmly closed (see sec-
tion 3.8), press the Reset button.
b) Combustion chamber and ash door are leaking – check the seal, replace
the seal if necessary, press the reset button.
c) Pressure measuring nipple of combustion chamber pressure switch is blok-
ked – clear it (see section 3.9.1), press the reset button.
d) Intake air line or induction opening at rear is blocked – clear it and press
the reset button.
e) Exhaust pipe or flue is blocked, clear it and press the reset button.
f) Combustion chamber pressure switch is defective, inform Windhager
Customer Service or a heating technician.
FE 381
Reserve supply container empty
Time programme blocking feed.
Change enable time in menu/operator
level.
Enable time for the feed has been set too short, which means the pellets in
the reserve supply container are used up and the feed is blocked.
Extend the enable time for the feed in the „Feed operating mode“ menu item
(see section 2.8.1.4) or operate „with start time“ or „without time control“ (see
section 2.8.1.3).
Troubleshooting