4.
The smoke match should be placed
horizontally into the hotbox at the right hand
side (See figure 26).
The installation is satisfactory if the smoke is
drawn into the appliance.
If the smoke is not drawn into the appliance
leave the appliance alight at the maximum
setting for a further ten minutes and then repeat
the test. If the smoke is still not drawn into the
appliance inspect the sealing to the fireplace
surround. If the sealing is satisfactory but the
appliance is installed with the flue restrictor (See
section 9 point 14) remove the restrictor, reseal
the appliance and retest. If smoke is still not
drawn into the appliance
disconnect the
appliance and seek expert advice.
5.
If the above test is satisfactory open all
internal connecting doors, hatches, etc. in the room. Keep all doors and windows that
open to the outside of the building closed. Recheck for spillage as above. If an extractor
fan is installed in the same room as the appliance or a connecting room, check that
spillage does not occur with the fan operating and all doors and other openings between
the fan and the appliance open.
If the smoke is drawn into the appliance, continue with the installation. If the test is not
satisfactory
disconnect the appliance and advise the customer of the cause of
failure
.
13.3 Flame supervision and spillage monitoring system.
This pilot unit includes a system that will automatically shut off the gas supply if the
pilot flame goes out or if there is insufficient oxygen due to spillage or poor ventilation.
This monitoring system must not be adjusted, bypassed or put out of operation.
This monitoring system or any of its parts must only be exchanged using Baxi Fires
Division authorised parts.
Page 27
INSTALLER GUIDE
©
Baxi Heating U.K. Limited 2006.
Figure 26. Smoke match tube
position