3.11
The minimum height from the base of the fireplace opening to the underside of
any shelf made from wood or other combustible materials is detailed below.
•
For a shelf up to 150mm deep
: Minimum height = 750mm.
•
For a shelf deeper than 150mm
: 750mm + 12.5mm for every 25mm depth over
150mm (See Graph 1).
3.12
Note that soft wall coverings (e.g.
embossed vinyl, etc.) are easily affected by
heat. They may scorch or become discoloured
when close to a heating appliance. Please
bear this in mind when installing.
3.13
The appliance must not be installed in
any room, which contains a bath, or shower or
where steam is regularly present.
3.14
An extractor fan may only be used in
the same room as this appliance, or in any
area from which ventilation for the appliance
is taken, if it does not affect the safe
performance of the appliance. Note the
spillage test requirements detailed further on
in this manual. If the fan is likely to affect the appliance, the appliance must not be
installed unless the fan is permanently disconnected.
Page 12
INSTALLER GUIDE
©
Baxi Heating U.K. Limited 2006.
Figure 4. Removal of combustible
cladding (Shown with the ‘Chic’
fascia)
Graph 1. Combustible shelf clearances