Syscompact 2000 M pro
Faults and corrective measures
822-175-2
87 / 98
16.1 Safety instructions for repair work
WARNING
Easily accessible live parts
Danger to life, risk of injury due to electric shock.
Once the system has been opened, live parts will be accessible. The
surge voltage generator integrated within the system has a capacitor
comprising two separate sub-capacitors. These sub-capacitors can still
hold a residual charge, even when switched off.
Never take the system apart. Inside the device there are no
components that could be serviced or repaired by the user.
Maintenance and repair work must only be carried out by personnel
trained and authorised by BAUR.
16.2 Error display on the system control panel
16.2.1 Fault indication with status LEDs
The status of the operational earth monitoring and state of the surge protective device is
displayed on the system control panel by LEDs. If one of these status LEDs lights up red, the
system cannot be operated.
Display
Possible cause
Corrective measure
Status LED of the operational
earth monitoring ( ) turns red.
The
EMERGENCY OFF ACTIV
INTERNAL
error message is
displayed.
The resistance between
operational and protective
earthing is too high (> 4 ohm).
Ensure that the operational earthing
is connected correctly.
If the connection points are dirty,
clean them.
Status LED of the surge protective
device ( ) turns red. The
EMERGENCY OFF ACTIV
INTERNAL
error message is
displayed.
The surge protective device is
damaged.
The surge protective device has to be
replaced. It is not possible to continue
using the system.
Contact BAUR After Sales Service.
16 F
AULTS AND CORRECTIVE MEASURES