TA200
www.baumer.com
23
Line 28
Update time (display repetition)
0 * 0,5 s
1
1 s
2
2 s
3
3 s
4
5 s
5
10 s
6
20 s
7
30 s
8
60 s
Line 29
Time out F1
On stillstand, after expiry of this period a reset to zero occurs
0 * 1 s
1
2 s
2
3 s
3
5 s
4
10 s
5
20 s
6
30 s
7
60 s
8
Time out not operational
9
Time out not operational, with storage of F1 in the event of a
power failure.
Line 30
Time unit F1
0 * 1/min
1
1/s
2
1/h
Line 36
Decimal point for F1
0 * No decimal point
1
0.0
2
0.00
3
0.000
Line 40
Code setting
0 * No code
1 - 9999
After completion of these programming lines, a dotted line appears
in the display. The dotted line represents the end of the third pro-
gramming field.
Switching back
➜
Hold down the key
and press the key
again.
through the program lines
Switching off the
➜
Press the key
.
programming mode
●
The controller is now on the operating level again.
Reprogramming
➜
Press and hold the
and
keys and switching the
with the dafault settings
instrument on.
●
All values which have already been programmed are returned to
the default settings. Display shows for a short time
.