Object 6120
Slope angle X- axis (Slope lateral)
SubIndex
0
Data type
Integer 32
Access
ReadOnly
Default
EEPROM
No
Meaning
Slope angle
Parameters
Value range
Depending on the device type (measuring range) and parameter in 6000h
(resolution):
(+measuring range)/resolution ... to ... (-measuring range)/resolution
Example:
Measuring range = ±30°
Resolution = 0,001
Value range: +30000...-30000
Object 6121
Operating parameters X-axis (Slope lateral operating parameter)
SubIndex
0
Data type
Unsigned 8
Access
ReadWrite
Default
0h
EEPROM
Yes
Meaning
Inversion:
Inversion enabled means reverse polarity of the X-axis.
Scaling:
Scaling enabled means calculation of slope of the X-axis as follows:
Slope X
–axis
= physically measured slope + d
ifferential offset X- axis
+ o
ffset
X-axis
If scaling is disabled:
Slope X
–axis
= physically measured angle
Parameters
Bit 0 = 1 inversion on
0 inversion off
Bit 1 = 1 scaling on
0 scaling off
Object 6122
Preset value X-axis (Slope lateral preset value)
SubIndex
0
Data type
Integer 32
Access
ReadWrite
Default
0h
EEPROM
Yes
Meaning
Sets the actual slope of the X-axis to the required value
Parameters
Value range depending on parameters in object 6000h