Manual_GNAMG_CANopen_EN.doc
27/41
Baumer IVO GmbH & Co. KG
21.11.12
Villingen-Schwenningen, Germany
Object 2110
Manufacturer_Options
SubIndex
0
Data type
Unsigned 32
Access
ReadWrite
Default
8h
EEPROM
Yes
Meaning
Parameters to guarantee compatibility to former sensors respectively to
proceed customer-specific configurations
Object is not supported by EDS file.
Any parameterization should be by the manufacturer only. Any customer-
specific parameterization should be strictly conform to the table below.
Parameters
Bit3 = 0 no reset if BusOFF
1 bus reset if BusOFF
Bit5 = 0 Heartbeat protocol active
1 Nodeguarding protocol active
Object 2201
Statistics
SubIndex
0
Data type
Unsigned 8
Access
ReadOnly
Default
3h
EEPROM
No
Meaning
Maximum supported subindex
Parameters
3
SubIndex
1
Data type
Unsigned 32
Access
ReadOnly
Default
0h
EEPROM
Yes
Meaning
Presently not assigned
Parameters
-
SubIndex
2
Data type
Unsigned 32
Access
ReadOnly
Default
0h
EEPROM
Yes
Meaning
Operating time in seconds total (object 6508h time elapsed since last reset)
Parameters
0... 4294967295
SubIndex
3
Data type
Unsigned 32
Access
ReadOnly
Default
0h
EEPROM
Yes
Meaning
WatchDog TimerReset counter
Parameters
0... 4294967295