Battery Charger MVD
User's Manual
PROGRAM CURVE : I1 + I2 +I3 + I4 + I5 +I6
Using this Program for the follow battery:
reading battery voltage 0.0 V
Press the buttons UP and DOWN simultaneously.
In the first step A
(8.A)
, the charger workes in current costant way
(I=K)
for the maximum time
of
(60 minutes)
with a current of
(15%Ah --> [600 Ah] 6*15 = 90 Amp).
In the first step B
(8.B)
, the charger workes in current costant way
(I=K)
for the maximum time
of
(120 minutes)
with a current of
(20%Ah --> [600 Ah] 6*20 = 120 Amp).
In the first step C
(8.C)
, the charger workes in current costant way
(I=K)
for the maximum time
of
(180 minutes)
with a current of
(25%Ah --> [600 Ah] 6*25 = 150 Amp),
and if the battery
voltage reache
(2.40 V/Cell)
before the end of the time, the charger will go to next step.
In the first step D
(8.D)
, the charger workes in current costant way
(I=K)
for the maximum time
MVD-BASSI
Page 18 of 34
8.A I=K T= 60m
I=15%Ah
V=DIS
8.B I=K T= 120m
I=20%Ah
V=DIS
8.C I=K T= 180m
I=25%Ah
V=2.40
8.D I=K T= 240m
I=15%Ah
V=2.60 V
8.E I=K T= 120m
I=10%Ah
V=DIS
8.F I=K T= 120m
I=5%Ah
V=DIS
0.0 V
600 Ah
EL= 24
PROG.08