EMD-RMTR.. User’s Manual
10
4. Specifica ons
Exci ng current can be selected for 125mA
、
187.5mA
;
Velocity range: 0.1 to 15m/s,current speed resolu on: 0.5mm/s;
AC high-frequency switching power, range of voltage: 85VAC to 250VAC
DC 24V switching power, range of voltage: 20VDC to 36VDC
Network func on: MODBUS
、
HART Communication (Op onal)
4.1
Especial Func on
Recording time when power turn-off, to record power broken me of instrument system automatically and
recruit to count the missing flux
Recording function of hour gross, to record the flux gross by hour, fit for timed measure;
4.2 Normal Opera ng Condi ons
Ambient Temperature Ranges: –10
~
+60°C
Relative Humidity: 5%
~
90%;
Power Supply: 85...250V, 45
~
63Hz ( single-phase AC) or 20...36VDC
Dissipation Power: < 20W
4.3 Measure Precision
Range (m/s)
Accuracy
0,1....0,3
±0,25 % FS
0,3...1
±0,5 % R
1...15
±0,5 % R