DECS-100 BESTCOMS for Windows
®
OS
5-5
Figure 5-9. Setting Adjustments Screen, Setpoint Tab
Setting Adjustments
The Setting Adjustments screen consists of two tabs: Setpoint and Startup.
Setpoint Tab
The Setpoint tab settings of the Setting Adjustments screen are shown in Figure 5-9. Each setting of the
Setpoint tab is described in the following paragraphs.
Automatic Voltage Regulator (AVR) - AVR Setpoint (V). This setting field is used to enter the desired
generator output terminal voltage. The AVR setpoint value range depends on the regulator sensing voltage
and band setting.
Fine Voltage Adjustment - Band Setting (%). The Band Setting determines the minimum and maximum
adjustment allowed to the AVR Setpoint (as a percentage of the Regulator Sensing Voltage setting (see
Figure 5-8)). Band Setting values are entered as a percentage of the regulator sensing voltage setting over
a range of 0 to 15 percent in 0.1 percent increments.
Droop - Setpoint (%). This setting controls the reactive droop compensation feature of the DECS-100. The
setpoint value determines the amount of change permitted in the generator voltage setpoint when the
DECS-100 responds to a reactive load. The setpoint value is adjustable from 0 to 10 percent in increments
of 0.01 percent. The setpoint is based on a 0.8 power factor load.
Field Current Regulator (FCR) - FCR Setpoint (A). This setting defines the field current setpoint when
operating in Manual mode. The FCR Setpoint field accepts a value of 0 to 7 Adc in increments of 0.01 Adc
Reactive Power Control (VAR) - VAR Setpoint (% of nom.). The VAR Setpoint determines the level of
generator vars maintained by the DECS-100 when operating in Var Control mode. Values from -100 to +100
percent in 1.0 percent increments may be entered in the VAR Setpoint field.
Power Factor Control (PF) - PF Setpoint. The PF Setpoint determines the level of generator power factor
maintained by the DECS-100 when operating in Power Factor Control mode. PF Setpoint values are
adjustable from -0.6 to -1 (1) or 0.6 to +1 in 0.001 increments.
Startup Tab
The Startup-tab settings of the Setting Adjustment screen are shown in Figure 5-10. Each setting of the
Startup tab is described in the following paragraphs.
Содержание DECS-100
Страница 5: ...DECS 100 Introduction iv...
Страница 24: ...DECS 100 Installation 4 2 Figure 4 1 DECS 100 Dimensions...
Страница 25: ...DECS 100 Installation 4 3 Figure 4 2 Cutout and Drilling Dimensions...
Страница 60: ...DECS 100 BESTCOMS for Windows OS 5 24 Figure 5 30 DECS 100 Information After Upload...