3-2
BE1-87G Functional Description
9170800990 Rev M
Figure 3-2. Stabilizing Reactor Impedance Characteristic, Sensing Input Range 1
Figure 3-3. Stabilizing Reactor Impedance Characteristic, Sensing Input Range 2
Band-Pass Filters
The outputs of the relay’s internal transformers are filtered to eliminate the third harmonic and minimize
the effect of dc offset caused by CT saturation (as may occur during synchronization or asymmetrical
faults). Two band-pass filters are used: difference and sum.
The output of the difference band-pass filter is applied to a full-wave rectifier. The rectifier scales the
differential and applies the output to the comparator as the operating current (I
OP
) signal.
The output of the sum band-pass filter is also applied to a full-wave rectifier. The scaled sum of the two
inputs represents the restraint current (I
R
). The restraint current is scaled for a 50% slope above nominal
input current (5 Aac for sensing input range 1 or 1 Aac for sensing input range 2).
Содержание BE1-87G
Страница 2: ......
Страница 8: ...vi BE1 87G Introduction 9170800990 Rev M This page intentionally left blank...
Страница 10: ...ii BE1 87G General Information 9170800990 Rev M This page intentionally left blank...
Страница 18: ...1 8 BE1 87G General Information 9170800990 Rev M This page intentionally left blank...
Страница 20: ...ii BE1 87G Controls and Indicators 9170800990 Rev M This page intentionally left blank...
Страница 22: ...2 2 BE1 87G Controls and Indicators 9170800990 Rev M This page intentionally left blank...
Страница 24: ...ii BE1 87G Functional Description 9170800990 Rev M This page intentionally left blank...
Страница 30: ...ii BE1 87G Installation 9170800990 Rev M This page intentionally left blank...
Страница 39: ...9170800990 Rev M BE1 87G Installation 4 9 Figure 4 8 Outline Dimensions Rear View Double Ended Mounting Case...
Страница 40: ...4 10 BE1 87G Installation 9170800990 Rev M Figure 4 9 Outline Dimensions Rear View Single Ended Mounting Case...
Страница 41: ...9170800990 Rev M BE1 87G Installation 4 11 Figure 4 10 Outline Dimensions Front View Case Cover...
Страница 46: ...4 16 BE1 87G Installation 9170800990 Rev M Figure 4 15 Typical DC Control Connections...
Страница 47: ...9170800990 Rev M BE1 87G Installation 4 17 Figure 4 16 Single Phase Sensing Connections...
Страница 48: ...4 18 BE1 87G Installation 9170800990 Rev M Figure 4 17 Three Phase Sensing Connections Wye Connected Generator...
Страница 52: ...ii BE1 87G Testing and Setting 9170800990 Rev M This page intentionally left blank...
Страница 56: ...5 4 BE1 87G Testing and Setting 9170800990 Rev M Figure 5 3 Operating Characteristics Relay Style x1x xxx xxxxx...
Страница 57: ...9170800990 Rev M BE1 87G Testing and Setting 5 5 Figure 5 4 Operating Characteristics Relay Style x2x xxx xxxxx...
Страница 62: ...5 10 BE1 87G Testing and Setting 9170800990 Rev M Figure 5 8 Generator Differential Application...
Страница 63: ......