background image

9279400990 Rev B 

BE1-59NC General Information 

1-1 

SECTION 1 

 GENERAL INFORMATION 

DESCRIPTION 

BE1-59NC Neutral Overvoltage Relays provide sensitive protection for capacitor banks. There are three 
common types of capacitor bank failures that BE1-59NC Neutral Overvoltage Relays recognize. They are: 

  Unit dielectric failure 

  Capacitor bank insulator failure 

 Blown 

fuses 

BE1-59NC Neutral Overvoltage relays protect for overvoltage due to internal voltage shifts that occur as a 
result of these types of failures. 

APPLICATION 

Capacitor banks are widely used by utilities to maintain specified system voltage. Addition of capacitive 
loads at appropriate points on the system compensate for heavy inductive loading that normally tends to 
reduce voltage. This adding of leading megavars to compensate for the lagging megavar component of 
electric loads is frequently referred to as power factor correction. Capacitor banks must be switched in 
response to actual load conditions in order to obtain maximum power factor correction benefits. 

Capacitor Bank Switching 

One of the common methods of maximizing capacitor bank benefits is by evaluating the bus voltage. A 
bandwidth surrounding the desired bus voltage level is established. When the bus voltage falls below the 
bandwidth level, the capacitor bank is switched into the circuit. When the bus voltage rises above the 
bandwidth level, the capacitor bank is switched out. 

Protection 

Protection of capacitor banks has always been difficult. It is especially difficult to sense failures inside the 
capacitor banks because of the configuration. Experience indicates that most capacitor bank faults 
involve one or more insulator failures with arcing across groups and/or phase-to-phase inside the bank. In 
most cases, these types of faults are not seen by the bus differential or other protection unless the arcing 
spills over to the area between the fuses and the circuit switcher. A fault across an insulator usually 
means that one or more groups of parallel units are shorted. This will cause a neutral shift and 
unbalanced phase currents. Unbalanced phase current magnitudes are determined by the number of 
series connected groups. For full phase-to-neutral flashover, the maximum phase current is three times 
normal capacitor bank load in the faulted phase. 

One main protection concern is overvoltage cascading. A capacitor bank is unique in that cascading of 
units may take place after a predetermined number of unit fuses have operated. Normally after a fuse has 
blown in any other type of equipment, the faulted apparatus is disconnected and usually does not affect 
any remaining equipment that is in service. That is not so with a capacitor bank. Each fuse that blows to 
isolate the faulted unit sets up an increased voltage stress on the remaining units (Figure 1-1). Sometime 
later, the next weakest unit in that group fails. As each successive fuse blows, the voltage increases 
another step and rapidly causes the next unit to fail. Cascading takes place and results in serious 
damage to the capacitor bank and possible hazards to personnel. While the capacitor bank is failing, the 
station in minimally affected. The voltage is nearly normal, the current flow is almost unaffected, and 
station relay protection is not taking any action until the failure has developed into a phase-to-phase or 
phase-to-ground fault. 

A solution was to develop a protective scheme for the capacitor bank with the main emphasis on 
preventing overvoltage cascading. To do this, a ground fault relay or neutral shift device had to be 
developed that was sensitive enough to detect blown fuses for both alarming and tripping purposes. The 
best place to obtain the sensing information is between the neutral of the capacitor bank and ground. 
Voltage differentials between the normal capacitor bank status and that of one blown fuse are very small. 
However, BE1-59NC Neutral Overvoltage relays are sensitive enough to differentiate between these 
conditions and act decisively. 

 

 

Содержание BE1-59NC

Страница 1: ...INSTRUCTION MANUAL FOR NEUTRAL OVERVOLTAGE RELAY BE1 59NC P0046 15 Serial No H01234567891 NEUTRAL OVERVOLTAGE RELAY BE1 59NC Style No A1ED1JC0S1F Publication 9279400990 Revision B 09 07...

Страница 2: ......

Страница 3: ...ols and Indicators Functional Description Installation Testing WARNING To avoid personal injury or equipment damage only qualified personnel should perform the procedures in this manual NOTE Be sure t...

Страница 4: ...peration The availability and design of all features and options are subject to modification without notice Should further information be required contact Basler Electric BASLER ELECTRIC ROUTE 143 BOX...

Страница 5: ...Section 7 Manual Change Information to manual introduction Added manual part number and revision to all footers Updated cover drawings Updated power supply burden data in Section 1 Updated Target Ind...

Страница 6: ...iv BE1 59NC Introduction 9279400990 Rev B This page intentionally left blank...

Страница 7: ...cy Recognition Certification 1 6 SECTION 2 CONTROLS AND INDICATORS 2 1 INTRODUCTION 2 1 SECTION 3 FUNCTIONAL DESCRIPTION 3 1 INTRODUCTION 3 1 FUNCTIONAL DESCRIPTION 3 1 Inputs 3 1 Filters 3 1 Overvolt...

Страница 8: ...vi BE1 59NC Introduction 9279400990 Rev B This page intentionally left blank...

Страница 9: ...and the circuit switcher A fault across an insulator usually means that one or more groups of parallel units are shorted This will cause a neutral shift and unbalanced phase currents Unbalanced phase...

Страница 10: ...neutral relay senses this voltage unbalance and reacts to give the appropriate signal usually an alarm or trip depending on the voltage level Further loss of more capacitors increases the neutral vol...

Страница 11: ...inside the case assembly The style number identification chart for the BE1 59NC relay is illustrated in Figure 1 2 Figure 1 2 Style Number Identification Chart Style Number Example If a BE1 59NC relay...

Страница 12: ...ristics Inverse Response time decreases as the difference between the monitored voltage and the setpoint increases The inverse time characteristics switch is adjustable from 01 to 99 in 01 increments...

Страница 13: ...circuit Continuous Rating 3 A 1 Second Rating 30 A 2 Minute Rating 7 A Type Tests Shock Withstands 15 G in each of three mutually perpendicular planes without structural damage or performance degrada...

Страница 14: ...certified No POCC US ME05 B03391 complies with the relevant standards of Gosstandart of Russia Issued by accredited certification body POCC RU 0001 11ME05 CHARACTERISTIC CURVES BE1 59NC overvoltage in...

Страница 15: ...9279400990 Rev B BE1 59NC General Information 1 7 Figure 1 4 Overvoltage Inverse Time Curves High Ranges...

Страница 16: ...1 8 BE1 59NC General Information 9279400990 Rev B This page intentionally left blank...

Страница 17: ...the controls and indicators shown and described here P0046 16 Serial No H01234567891 NEUTRAL OVERVOLTAGE RELAY BE1 59NC Style No A1ED1JC0S1F A B C D E F G H I J Figure 2 1 Location of Controls and In...

Страница 18: ...oltage output delay definite timing characteristic adjustable from 00 1 to 99 9 seconds in 0 1 second increments A setting of 00 is instantaneous G POWER LED LED illuminates when proper operating powe...

Страница 19: ...ltage 2 circuits are functionally the same except for timing characteristics Filters Bandpass filters provide peak sensitivity at 50 or 60 hertz for the overvoltage 1 and overvoltage 2 inputs Third ha...

Страница 20: ...us relay de energizes and opens the power supply status output contacts Power Supply Operating power for the relay circuitry is supplied by a wide range electrically isolated low burden power supply P...

Страница 21: ...minimum current of 200 milliamperes must flow through the output trip circuit If a wiring insulation test is required remove the connection plugs and withdraw the relay from its case MOUNTING Because...

Страница 22: ...4 2 BE1 59NC Installation 9279400990 Rev B Figure 4 1 Panel Cutting Drilling Semi Flush Case...

Страница 23: ...9279400990 Rev B BE1 59NC Installation 4 3 Figure 4 2 Panel Cutting Drilling Double Ended Projection Mount Case...

Страница 24: ...4 4 BE1 59NC Installation 9279400990 Rev B D1427 27 12 04 01 Figure 4 3 Case Dimensions Side View Double Ended Semi Flush Case...

Страница 25: ...9279400990 Rev B BE1 59NC Installation 4 5 Figure 4 4 Case Dimensions Side View Double Ended Projection Mount Case...

Страница 26: ...4 6 BE1 59NC Installation 9279400990 Rev B Figure 4 5 Case Dimensions Rear View Semi Flush Case...

Страница 27: ...9279400990 Rev B BE1 59NC Installation 4 7 Figure 4 6 Case Dimensions Rear View Projection Mount Case...

Страница 28: ...4 8 BE1 59NC Installation 9279400990 Rev B P0002 12 01 31 01 Figure 4 7 Case Cover Dimensions Front View...

Страница 29: ...relay Incorrect wiring may result in damage to the relay Except where noted connections should be made with wire no smaller than 14 AWG Typical control circuit connections are shown in Figure 4 8 Typi...

Страница 30: ...4 10 BE1 59NC Installation 9279400990 Rev B Figure 4 9 Typical Protection Methods...

Страница 31: ...9279400990 Rev B BE1 59NC Installation 4 11 Figure 4 10 Typical Internal Connections...

Страница 32: ...Basler Electric to coordinate repairs STORAGE This protective relay contains aluminum electrolytic capacitors which generally have a life expectancy in excess of 10 years at storage temperatures less...

Страница 33: ...lowly turn OVERVOLTAGE 1 PICKUP adjust potentiometer R63 CCW until OVERVOLTAGE 1 PICKUP LED just illuminates Step 3 Set OVERVOLTAGE 1 TIME DIAL to 001 and apply to case terminals 6 and 7 a voltage tha...

Страница 34: ...rvoltage at case terminals 6 and 7 Observe the time registered by the counter Time must equal the setting 100 milliseconds or 2 whichever is greater Step 13 Set OVERVOLTAGE 2 TIME DIAL to 100 Monitor...

Страница 35: ...OVERVOLTAGE 1 TIME DIAL to 11 Step 5 Reset the timer Turn on PS1 While monitoring the output terminals indicated in Figure 5 1 for OVERVOLTAGE 1 initiate PS2 and record the time delay Verify that the...

Страница 36: ...d in Figure 5 1 for OVERVOLTAGE 2 Remove and then reapply the overvoltage at case terminals 6 and 7 Observe the time registered by the counter Time must equal the setting 100 milliseconds or 2 whichev...

Страница 37: ...conds whichever is greater of the time shown in Table 5 1 Step 12 Remove PS1 and PS2 voltage Step 13 With reference to Figure 5 2 set PS1 for the value shown in Table 5 1 and for the specific input op...

Страница 38: ...5 6 BE1 59NC Testing 9279400990 Rev B This page intentionally left blank...

Страница 39: ...ROUTE 143 BOX 269 HIGHLAND IL 62249 USA http www basler com info basler com PHONE 1 618 654 2341 FAX 1 618 654 2351...

Отзывы: