![Basler BE1-59NC Скачать руководство пользователя страница 37](http://html1.mh-extra.com/html/basler/be1-59nc/be1-59nc_instruction-manual_2707525037.webp)
9279400990 Rev B
BE1-59NC Testing
5-5
D2 Timing Option
Step 1. With reference to Figure 5-2, set PS1 for the value shown in Table 5-1, input option (column 1)
and for the specific pickup voltage (column 2,
Volts Pickup 50/60 Hz
).
Example:
input option 1,
PS1 set to 10 volts, at 0
°
.
Step 2. Adjust the OVERVOLTAGE 1 PICKUP adjust potentiometer R63 so the OVERVOLTAGE 1
PICKUP LED just illuminates.
Step 3. Adjust PS1 and PS2 for the voltage levels and phase angles based on input options as shown
in Table 5-1 (columns 3 and 4).
Step 4. Set the OVERVOLTAGE 1 TIME DIAL to 11.
Step 5. Reset the timer. Turn on PS1. While monitoring the output terminals indicated in Figure 5-2 for
OVERVOLTAGE 1, initiate PS2 and record the time delay. Verify that the time is within 5.0% or
25 milliseconds (whichever is greater) of the time shown in Table 5-1.
Step 6. Remove PS1 and PS2 voltage.
Step 7. Set the OVERVOLTAGE 1 TIME DIAL to 33.
Step 8. Reset the timer. Turn on PS1. While monitoring the output terminals indicated in Figure 5-2 for
OVERVOLTAGE 1, initiate PS2 and record the time delay. Verify that the time is within 5.0% or
25 milliseconds (whichever is greater) of the time shown in Table 5-1.
Step 9. Remove PS1 and PS2 voltage.
Step 10. Set the OVERVOLTAGE 1 TIME DIAL to 88.
Step 11. Reset the timer. Turn on PS1. While monitoring the output terminals indicated in Figure 5-2 for
OVERVOLTAGE 1, initiate PS2 and record the time delay. Verify that the time is within 5.0% or
25 milliseconds (whichever is greater) of the time shown in Table 5-1.
Step 12. Remove PS1 and PS2 voltage.
Step 13. With reference to Figure 5-2, set PS1 for the value shown in Table 5-1 and for the specific input
option.
Step 14. Adjust the OVERVOLTAGE 2 PICKUP adjust potentiometer R43 so the OVERVOLTAGE 2
PICKUP LED just illuminates.
Step 15 Adjust PS1 and PS2 for the voltage levels and phase angles based on input options as shown
in Table 5-2.
Step 16. Set the OVERVOLTAGE 2 TIME DIAL to 11.
Step 17. Reset the timer. Turn on PS1. While monitoring the output terminals indicated in Figure 5-2 for
OVERVOLTAGE 2, initiate PS2 and record the time delay. Verify that the time is within 5.0% or
25 milliseconds (whichever is greater) of the time shown in Table 5-1.
Step 18. Remove PS1 and PS2 voltage.
Step 19. Set the OVERVOLTAGE 2 TIME DIAL to 33.
Step 20. Reset the timer. Turn on PS1. While monitoring the output terminals indicated in Figure 5-2 for
OVERVOLTAGE 2, initiate PS2 and record the time delay. Verify that the time is within 5.0% or
25 milliseconds (whichever is greater) of the time shown in Table 5-1.
Step 21. Remove PS1 and PS2 voltage.
Step 22. Set the OVERVOLTAGE 2 TIME DIAL to 88.
Step 23. Reset the timer. Turn on PS1. While monitoring the output terminals indicated in Figure 5-2 for
OVERVOLTAGE 2, initiate PS2 and record the time delay. Verify that the time is within 5.0% or
25 milliseconds (whichever is greater) of the time shown in Table 5-1.
Step 24. Remove PS1 and PS2 voltage.
NOTE
In the following inverse time tests, voltage is stepped from one-half of pickup to a
voltage that is higher (by value in column for Volts Over Pickup, Table 5-1) than
the pickup.
Содержание BE1-59NC
Страница 2: ......
Страница 6: ...iv BE1 59NC Introduction 9279400990 Rev B This page intentionally left blank...
Страница 8: ...vi BE1 59NC Introduction 9279400990 Rev B This page intentionally left blank...
Страница 15: ...9279400990 Rev B BE1 59NC General Information 1 7 Figure 1 4 Overvoltage Inverse Time Curves High Ranges...
Страница 16: ...1 8 BE1 59NC General Information 9279400990 Rev B This page intentionally left blank...
Страница 22: ...4 2 BE1 59NC Installation 9279400990 Rev B Figure 4 1 Panel Cutting Drilling Semi Flush Case...
Страница 23: ...9279400990 Rev B BE1 59NC Installation 4 3 Figure 4 2 Panel Cutting Drilling Double Ended Projection Mount Case...
Страница 26: ...4 6 BE1 59NC Installation 9279400990 Rev B Figure 4 5 Case Dimensions Rear View Semi Flush Case...
Страница 27: ...9279400990 Rev B BE1 59NC Installation 4 7 Figure 4 6 Case Dimensions Rear View Projection Mount Case...
Страница 28: ...4 8 BE1 59NC Installation 9279400990 Rev B P0002 12 01 31 01 Figure 4 7 Case Cover Dimensions Front View...
Страница 30: ...4 10 BE1 59NC Installation 9279400990 Rev B Figure 4 9 Typical Protection Methods...
Страница 31: ...9279400990 Rev B BE1 59NC Installation 4 11 Figure 4 10 Typical Internal Connections...
Страница 38: ...5 6 BE1 59NC Testing 9279400990 Rev B This page intentionally left blank...