9252000990 Rev N
BE1-50/51M Controls and Indicators
2-3
Table 2-1. BE1-50/51M Controls and Indicators (Refer to Figures 2-1 and 2-2)
Locator
Control or Indicator
Function
A
INST MANUAL TRIP
Test Points
When shorted, the test points (jacks) provide a secure means to
manually trip the controlled breaker. Jacks accept a standard 0.08
inch diameter phone tip plug.
B INST
PICKUP
Selectors
Two switches (TENS and UNITS on five ampere models,
COARSE and FINE on one ampere models) to select pickup
current in amperes. Changing switch selectors while the relay is in
service may cause tripping.
C Targets
Red target indicators latch when the trip circuit current is greater
than 0.2 amperes. One target each for TIME and INST.
D TIME
PICKUP
Selectors
Two switches (TENS and UNITS on five ampere models,
COARSE and FINE on one ampere models) to select pickup
current in amperes. Changing switch selectors while the relay is in
service may cause tripping.
E
CURVE
Selector
Ten position selector switch to select one of nine inverse functions
or one fixed time function.
F
TIME DIAL
Selectors
Two selector switches (UNITS and TENTHS) to select the desired
characteristic curve. A setting of 0.0 results in instantaneous
operation without any intentional delay. A setting of 9.9
corresponds to the typical time provided by an electromechanical
relay at its maximum dial setting.
G
TIME MANUAL TRIP
Test Points
When shorted, the test points provide a secure means to manually
trip the controlled breaker. Jacks accept a standard 0.08 inch
diameter phone tip plug.
H
ACTIVE/PICKUP
LED
Red LED indicates sensed current has exceeded the TIME
PICKUP setting. LED turns from red to green when sensed current
falls below 95% of pickup setting. When the LED is green, the
relay is active but has not picked up.
I
Target
RESET
Button
Linkage extends through back of front cover to reset both gravity
latched target indicators.
SW3-1
SW3-1 selects the system operating frequency. Opening SW3-1
(OFF) selects 60 hertz operation. Closing SW3-1 (ON) selects 50
hertz operation.
SW3-2
SW3-2 selects additional delay for the instantaneous element.
Closing SW3-2 (ON) provides an additional instantaneous delay of
0.1 seconds.
SW3-3
100 Series Relays
Closing SW3-3 (ON) provides an additional instantaneous delay of
0.2 seconds. Closing both SW3-2 (ON) and SW3-3 (ON) provides
an additional instantaneous delay of 0.3 seconds.
200 Series Relays
Opening SW3-3 (OFF) selects ABB type curves (refer to Table 1-
3.) Closing SW3-3 (ON) selects GE IAC type curves (refer to
Table 1-4).
J
SW3-4
SW3-4 provides selection of either instantaneous or integrating
reset characteristics. Closing SW3-4 (ON) selects integrating reset
characteristics. Opening SW3-4 (OFF) selects instantaneous reset
characteristics. See Section 1,
General Information,
Specifications,
for details on time reset.
Содержание BE1-50M
Страница 1: ...INSTRUCTION MANUAL FOR OVERCURRENT RELAY BE1 50 51M Publication 9252000990 Revision N 03 08 ...
Страница 2: ......
Страница 8: ...vi BE1 50 51M Introduction 9252000990 Rev N This page intentionally left blank ...
Страница 10: ...ii BE1 50 51M General Information 9252000990 Rev N This page intentionally left blank ...
Страница 22: ...ii BE1 50 51M Controls and Indicators 9252000990 Rev N This page intentionally left blank ...
Страница 28: ...ii BE1 50 51M Functional Description 9252000990 Rev N This page intentionally left blank ...
Страница 32: ...ii BE1 50 51M Installation 9252000990 Rev N This page intentionally left blank ...
Страница 37: ...9252000990 Rev N BE1 50 51M Installation 4 5 Figure 4 5 DC Control Connections ...
Страница 38: ...4 6 BE1 50 51M Installation 9252000990 Rev N Figure 4 6 BE1 50 51M Terminal Connections Rear View ...
Страница 40: ...4 8 BE1 50 51M Installation 9252000990 Rev N This page intentionally left blank ...
Страница 42: ...ii BE1 50 51M Testing 9252000990 Rev N This page intentionally left blank ...
Страница 50: ...5 8 BE1 50 51M Testing 9252000990 Rev N This page intentionally left blank ...
Страница 52: ...ii BE1 50 51M Relay Differences 9252000990 Rev N This page intentionally left blank ...
Страница 56: ...6 4 BE1 50 51M Relay Differences 9252000990 Rev N This page intentionally left blank ...
Страница 58: ...ii BE1 50 51M Time Characteristic Curves 9252000990 Rev N This page intentionally left blank ...