Current Sensing Input
BE1-50/51B-235
Continuous Rating:
14 Aac
∗
1 Second Rating:
400 Aac
∗
Continuous rating is 14 Aac for temperatures up to 45
°
C. See Figure 1-1 for derating curve.
Continuous Current
Current Sensing Input
0
2
4
6
8
10
12
14
16
-40
-20
0
20
40
60
Ambient Temperature (C)
Curren
t (Aac)
Figure 1-1. Current Sensing Input Derating Curve (BE1-50/51B-235)
BE1-50/51B-236
Continuous Rating:
2.8 Aac
∗
1 Second Rating:
80 Aac
∗
Continuous rating is 2.8 Aac for temperatures up to 45
°
C. See Figure 1-2 for derating curve.
Continuous Current
Current Sensing Input
0
0.4
0.8
1.2
1.6
2
2.4
2.8
3.2
-40
-20
0
20
40
60
Ambient Temperature (C)
Curr
ent (A
ac)
Figure 1-2. Current Sensing Input Derating Curve (BE1-50/51B-236)