4-4
Figure 4-6. Raise/Lower Contact Interconnection.
1
2
3
4
5
6
7
M
8
9
1 0
1 3
1 2
1 1
1 1
1 2
1 3
CW
I N P U T
V O L T A G E
M O T O R O P E R A T E D
C O N T R O L
B A S L E R
A U X I L I A R Y L I M I T S W I T C H E S
T O V O L T A G E
R E G U L A T O R
O R
G O V E R N O R
C
N C
N O
N C
C
N O
-
+
B E 3 - 2 5 A
R A I S E
L O W E R
F R E Q U E N C Y
M A T C H I N G O P T I O N
"C"
(SEE NOTE 1)
V O L T A G E
M A T C H I N G O P T I O N
"2"
(SEE NOTE 2)
O R
N O T E S :
1 . T E R M I N A L S A R E D E S I G N A T E D W I T H
PREFIX RF OR LF.
2 . T E R M I N A L S A R E D E S I G N A T E D W I T H
P R E F I X R V O R L V .
b. Circuit Breaker (SYNC) Connection. Connect the circuit breaker to the BE3-25A as given in
Table 4-1.
Table 4-1. BE3-25A and Breaker Connections.
Breaker Input
BE3-25A SYNC Output
C
SC
NO
SNO
NC
SNC
c. Voltage Regulator and/or Governor "Raise/Lower" Connections. Connect the "raise/lower"
contact outputs as shown by Figure 4-6.
d. Summing Point Governor Connections. Connect the summing point governor to the BE3-
25A as shown by Figures 4-7 through 4-12.