3-7
The BE3-25A jumpers are shown in Figure 3-1 and Figure 3-2 and are described in Table 3-3.
Table 3-3. Jumpers.
JUMPER
FUNCTION
RESET Jumper
Used to enable the internal reset function. Refer to paragraph
1-1.b.3 and 2-1.b.1.a.
0.75 S DELAY Jumper
Used to enable the 0.75 second delay to occur between
synchronization and breaker closure enable.
GOV STABILITY RANGE
Jumper
Used to select the governor stability range (system response
time). Refer to Figure 3-2.
REGULATOR POLARITY
Jumper
Used to select the Synchronizer polarity output for correct
regulator operation.
DEAD BUS Jumper
Used to enable the Dead Bus Option.
3-3. JUMPERS
NOTE
Not all jumpers are required for all styles.
Figure 3-2. Governor Stability Jumper