- 36 -
5.1.1 Installation
Dimensions required for positioning
Installation instructions
CAUTION!
In order to avoid the concentration of the harmful combustion products in
the installation room the device must be installed only in properly ventilated
rooms according to the regulations.
•
The installation room must consist as much air as required for appropriate
combustion of gas. For appropriate combustion the intake air flux must not be
lower than 2 m
3
/h per kW of the rated device power (see rating plate on the
device). Moreover follow the safety regulations.
•
Air must be taken directly from outside environment through the permanently
opened gaps or intake ducts connected with fresh air area.