background image

 

 

   

 

 

Operational Instruction 

(Original)

 

 

Distribution box 

Type 07-5103-…./…., 07-5105-

…./…., 07-5106-…./…. and 07-5107-…./…. 

 

 

BARTEC 
Varnost d.o.o. 

Cesta 9.avgusta 59 
1410 Zagorje ob Savi 
Slovenia 

Tel.:  +386 59 221 471 
Fax:  +386 59 221 470 

info@bartecvarnost.si 
www.bartecvarnost.si 

Reservation

 

Technical data subject to change without notice. Changes, errors and 
misprints may not be used as a basis for any claim for damages. 

EN 1/3

 

 

 

 

 

 

 

 

 

 

Explosion protection 

 

 

Technical data 

 

ATEX 

Ex type of protection 

  II 2G Ex e ia/ib IIA, IIB, IIC T6, T5 Gb 

  II 2G Ex ia/ib IIA, IIB, IIC T6, T5 Gb 

 
For type 07-5103-…./…. and 07-5105-…./…. 
also: 

  II 2D Ex tb IIIC T80 °C,T95 °C Db 

IP65/IP66 

 
For type 07-5105-…./…. also: 

  II 2D Ex ia/ib IIIC T80 °C Db 

Certification 

PTB 08 ATEX 1064 

IECEx 

Ex type of protection 

 

Ex e ia/ib IIA,IIB,IIC T6,T5 Gb 

 

Ex ia/ib IIA,IIB,IIC T6,T5 Gb 

 

For type 07-5103-…./…. and 07-5105-…./…. 
also: 

 

Ex tb IIIC T80°C,T95°C Db IP66 

 

For type 07-5105-…./…. also: 

 

Ex ia/ib IIIC T80°C Db 

Certification 

IECEx PTB 09.0009X 

Working temperature ranges 

With EPDM gasket: 

-20 °C to +95 °C 
(-4 °F to +203 °F) 

With inspection windows: 

-25 °C to +95 °C 
(-13 °F to +203 °F) 

With silicone gasket: 

-55 °C to +100 °C 
(-67 °F to +212 °F) 

Ambient temperature ranges 

Depending on the temperature class: 

 

By T95 °C, T5 and for the Ex ia/ib IIC T6 Gb 
version, silicone gasket: 

-55 °C to +55 °C  
(-67 °F to +131 °F)  

T6 and T80 °C, silicone gasket: 

-55 °C to +40 °C  
(-67 °F to +104 °F)  

T6 EPDM gasket and inspection window(s): 

-20 °C to +40 °C 
(-4 °F to +104 °F) 

Approved for zones 

1 and 2 
21 and 22 

Protection class 

Max. IP66  

Rated voltage (U

e

AC/DC 1000 V 

Mechanical strength 

Impact energy: 7 Joule 

Enclosure material/manufacturing 
process 

Type 07-5103-…./…. and 07-5105-…./…. 

– 

Glass-fiber reinforced polyester 

– 

Surface resistance <10

9

– 

RAL 9005 black 

 
Type 07-5106-…./…. and 07-5107-…./…. 

– 

Glass-fiber reinforced polyester 

– 

Surface resistance >10

12

– 

RAL 9000/RAL 7001 grey 

Lid screws 

Stainless Steel, cross-head (+-) 

Recommended tightening torque 

M4 screw: 

ca. 1.2 Nm 

M6 screw: 

ca. 1.4 Nm 

Terminals 

Certified connecting and/or rail-mounted 
terminals with a maximum rated voltage of 
1100 V AC/DC and a maximum rated cross 
section of 300 mm². 
 
For information about the tightening torque 
of the terminal screw, Tightening torques, 
see manufacturer`s instructions. 

Dimensions in mm (in) 

From 80 x 75 x 55  
(3.1 x 3 x 2.2) 
to 600 x 250 x 120 
(23.6 x 9.8 x 4.7), 
see also Bartec catalogue 

 

V

S

 –

 1

01

 3

01

 (

is

su

N

 I 

/  

2.

11

.2

01

6)

 

Note on instructions 

When working in hazardous areas, the safety of 
personnel  and  equipment  depends  on  compli-
ance  with  the  relevant  safety  regulations.  The 
people  in  charge  of  installation  and  mainte-
nance bear a special responsibility. It is essen-
tial  that  they  have  an  exact  knowledge  of  the 
applicable rules and regulations. 
The instructions provide a summary of the most 
important  safety  measures  and  must  be  read 
by  everyone  working  with  the  product  so  that 
they will be familiar with the correct handling of 
the product. 
The  instructions  have  to  be  kept  for  future 
reference and must be available throughout the 
expected life of the product. 
 

Description 

The  BARTEC  Varnost  distribution  boxes,  type 
07-5103-…./…., 

07-5105-…./…., 

07-5106-

…./….  and  07-5107-…./….,  are  used  for  con-
nections  and  distribution  of  incoming  and 
outgoing  cables  and  wires  with  certified  con-
necting  and/or  rail-mounted  terminals.  The 
distribution  boxes  are  used  for  connecting 
lights, devices and signals. 
The enclosure is made of glass-fibre reinforced 
polyester.  The  lid  and  base  are  fastened  with 
stainless steel captive screws (+/- crosshead). 
A  grooved  spring  system  with  inserted  sealing 
chord in between the lid and the base provides 
for the high protection type IP66.  
The  distribution  boxes  are  mounted  by  means 
of fixing holes outside of the sealed space.  
The  distribution  boxes  are  also  suitable  for 
intrinsically safe electric circuit’s connections. In 
this case, a special marking is required.  
The  distribution  boxes  can  be  used  in  hazard-
ous  areas  of  both  zone  1  and  2  with  certified 
explosion  subgroups  II  and  the  temperature 
class T5/T6 and as well as in zone 21 and 22 
with certified max. surface temperature. 
 

 

Отзывы: