Operational Instruction
(Original)
Distribution box
Type 07-5103-…./…., 07-5105-
…./…., 07-5106-…./…. and 07-5107-…./….
BARTEC
Varnost d.o.o.
Cesta 9.avgusta 59
1410 Zagorje ob Savi
Slovenia
Tel.: +386 59 221 471
Fax: +386 59 221 470
[email protected]
www.bartecvarnost.si
Reservation
Technical data subject to change without notice. Changes, errors and
misprints may not be used as a basis for any claim for damages.
EN 2/3
V
S
–
1
1
01
3
01
(
is
su
e
N
o
I
/
2.
11
.2
01
6)
Safety instructions
The distribution box may be used within the
specified temperature class and the tempera-
ture range indicated for it (see type label).
The distribution box may be operated only if it
is clean and not damaged in any way. Dust
deposits > 5 mm (> 0.2 in) must be removed.
As for distribution boxes used in flammable
dust, the ignition temperature of the dust/air
mixture and the glowing temperature of the
dust concerned must be greater than the
maximum surface temperature of the distribu-
tion box taking into account of the given safety
factor specified in EN 60079-0.
Utilization in areas other than those specified or
the modification of the product by anyone other
than the manufacturer is not permitted and will
exempt BARTEC Varnost from liability for
defects and any further liability.
The generally applicable statutory rules and
other binding directives relating to workplace
safety, accident prevention and environmental
protection must be observed.
Observe the applicable laws and directives
when commissioning or restarting operation.
Always follow the safety instructions on the
operating equipment.
Marking
Particularly important points in these instruc-
tions are marked with a symbol:
DANGER indicates a hazardous situation
which, if not avoided, will result in death or
serious injury.
WARNING indicates a hazardous situation
which, if not avoided, could result in death or
serious injury.
CAUTION indicates a hazardous situation
which, if not avoided, could result in minor or
moderate injury.
NOTICE is used to address practices not
related to personal injury.
Note
Important instructions and information on
effective, economical and environmentally
compatible handling.
Standards conformed to
2014/34/EU
as well as
EN 60079-0:2012/IEC 60079-0:2011
EN 60079-7:2007/IEC 60079-7:2006-07
EN 60079-11:2007/IEC 60079-11:2006
EN 60079-31:2009/IEC 60079-31:2008
as well as
EN 62208:2011/IEC 62208:2011
EN 60445:2010/IEC 60445:2010
EN 60529:1991 + A1:2000
Transport, storage
Risk of injury due to heavy loads.
Use an appropriate carrying aid or an
appropriate means of transport (e.g. a fork-
lift) with an adequate load-carrying ability.
Ensure that the lifted load will not tip over
or slip off.
Damage through incorrect transport or
incorrect storage.
Transport the distribution box in original
packaging, handle with care, and do not
drop.
Store the distribution box dry in original
packaging.
Assembly, installation, and
commissioning
Risk of serious injury due to incorrect
proceedings.
Only
qualified
personnel
who
are
authorized and trained to assemble electri-
cal components in hazardous (potentially
explosive) areas may do any of the as-
sembly, disassembly, installation and
commissioning work.
For assembly and operation of explosion
protected electrical equipment, relevant in-
stallation and operating regulations are to
adhere (e.g. Betr.SichV, IEC/EN 60079-14
and series DIN VDE 0100).
The data on the label and the EEC design
test data are to be observed. Further tech-
nical information is provided in the Bartec
catalog and on the product itself.
User may not drill holes in the distribution
boxes and add terminals
Do not open the distribution box when
energized.
Assembly / disassembly
Death or serious injury because of a miss-
ing protective earth connection.
Metallic conductor entries must be con-
nected to the ground. With plastic enclo-
sures, BARTEC Earth loc or appropriate
ground plates serve the similar purpose.
Risk of serious injury due to incorrect pro-
ceedings.
The assembly with connecting and/or rail-
mounted terminals must be implemented
under the consideration of the EEC design
inspection certificate.
Check when assembling:
•
Use suitable tools.
•
Pay attention to the type of mounting
required
(for
fitting
into
enclo-
sure/attachment with distribution box).
•
For distribution boxes placed in outdoors,
steps must be taken to ensure smooth
operation, for example rain protected
roofs, and if necessary, sufficient enclo-
sure protection.
Installation
Risk of injury due to incorrect proceedings.
Extensions or modifications to the distribu-
tion box are only permissible if the manu-
facturer’s approval is obtained first.
The IEC/EN60079-14 must be observed.
Installations for the highly combustible range
must exhibit an EEC design inspection certifi-
cate. Installation of these components must
take place in such way, so that at least the
enclosure remains IP54.
Connection of cables and conductors to equip-
ment in hazardous areas require Ex certified
entries, which are suitable for respective cable
and conductor types. They must possess the
protection type e” and contain a suitable sealing
gasket, so that the protection class of the
enclosure remains at least IP54.
Unused holes for cable entries have to be
sealed with Ex-certified plugs. Connection of
cables and conductors of zone 21 and 22
equipment require at least the protection class
IP 66.