The purpose of this option is to provide Self-testing and Self-diagnostic capabilities to the EXIT sign. At predetermined 

intervals, the EXIT sign will automatically switch into battery mode. Refer to the 

Self-Test Features

 section of this page 

for timing details. The EXIT sign will also perform various Self-diagnostic tests of the unit. Visual signaling will alert 

maintenance personnel to a fault of the EXIT sign electronics, battery and/or battery charger. The circuitry continuously 

monitors the operating condition of the EXIT sign and battery charging circuit/battery supply voltage. Refer to the 

LED 

Indicator 

section below for fault reporting details.

Self-Test Features

• The EXIT sign will automatically switch to battery mode every 30 days for a period of 30 seconds.

• The EXIT sign will automatically switch to battery mode every 180 days for a period of 30 minutes.

• The EXIT sign will automatically switch to battery mode every 365 days for a period of 90 minutes.

LED Indicator

The EXIT sign is equipped with a bi-color LED, which displays green and/or red.

• A steady green LED indicates that normal AC power is being supplied to the EXIT sign and the battery is fully charged.

• A flashing green LED indicates that the EXIT sign is undergoing a test.

• A flashing red and green LED indicates that the battery is being charged.

• A red LED indicates whenever the Self-diagnostics system has detected a fault condition. Refer to the chart below 

  when a red LED is displayed:

Test Switch Feature

MANUAL TEST – Placing the provided magnet near the magnetic test switch and pulling it away 

will switch the EXIT sign into battery mode for 30 seconds.

Use in accordance with local building codes.

Red LED Indication

Steady

Blinking 1 Time

Blinking 2 Times

Blinking 4 Times

Unit Fault

Battery Disconnected

Battery Failure

LED Failure

Battery Charge Failure

Corrective Action

Check Battery Connection

Replace Battery

Check Battery then Consult Factory
Check Battery then Consult Factory

Note:

 For fixtures with 

battery only

NXFX Series

Installation Instructions

10070226 

R

EV 1 - 08/20

6

800-533-3948 www.barronltg.com

Содержание Exitronix NXFX Series

Страница 1: ...d be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel For 2CI operation ensure that both AC power and auxiliary power are not simultaneously live The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Any modification or use of non original components will void the warranty and product liabil...

Страница 2: ...quare gasket from the gasket sheet then route wires out through the canopy followed by the mounting plate and the square gasket Ensure that the mounting plate is in the correct orientation see Fig 1b 8 Make electrical connections see Electrical Connections section 9 Secure the mounting plate to the J box 10 Secure the canopy to the mounting plate ensuring that the canopy has a proper seal with the...

Страница 3: ...plate 4 Route wires out through the center hole of the backplate and the corresponding hole in the back gasket 5 Make electrical connections see Electrical Connections section 6 Secure the unit to the J box ensuring that the gasket aligns properly with the backplate and makes a proper seal with the backplate and the wall 7 Connect the battery if included 8 Remove the chevron s from the EXIT templa...

Страница 4: ...ove additional knockouts to allow for screws to secure the fixture to the J box b If using flexible conduit remove the inner frame by removing the 4 screws and set aside Punch out the desired knockout located in the top or side of the enclosure 5 Using the brackets as a template align the fixture to the mounting location and mark the drill locations on the wall 6 Install wall anchors in the 4 mark...

Страница 5: ...AC Orange 277VAC Note The AC and auxiliary power cannot be simultaneously live consult factory for a solution Fig 4 AC Only Fig 5 With Battery Fig 6 2CI with 120VAC Input Fig 7 2CI with 277VAC Input Red 277VAC Black 120VAC White Com LED Indicator PCB LED Board Transformer Red 277VAC Black 120VAC White Com Transformer LED Indicator Magnetic Test Switch Battery LED Indicator 2CI1 Relay Generator UPS...

Страница 6: ...every 365 days for a period of 90 minutes LED Indicator The EXIT sign is equipped with a bi color LED which displays green and or red A steady green LED indicates that normal AC power is being supplied to the EXIT sign and the battery is fully charged A flashing green LED indicates that the EXIT sign is undergoing a test A flashing red and green LED indicates that the battery is being charged A re...

Отзывы: