Self-Test/Self-Diagnostics (G2)

Operation

The purpose of this option is to provide Self-testing and Self-diagnostic capabilities to the EXIT sign. At predetermined 

intervals, the EXIT sign will automatically switch into battery mode. Refer to the 

Self-Test Features

 section of this page 

for timing details. The EXIT sign will also perform various Self-diagnostic tests of the unit. Visual signaling will alert 

maintenance personnel to a fault of the EXIT sign electronics, battery and/or battery charger. The circuitry continuously 

monitors the operating condition of the EXIT sign and battery charging circuit/battery supply voltage. Refer to the 

LED 

Indicator 

section below for fault reporting details.

Self-Test Features

• The EXIT sign will automatically switch to battery mode every 28 days for a period of 5 minutes.

• The EXIT sign will automatically switch to battery mode every 6 months for a period of 90 minutes.

LED Indicator

• The red “UNIT ALERT” LED indicates whenever the Self-diagnostics system has detected a fault condition. 

   Refer to the chart below when the red “UNIT ALERT” LED is blinking:

• The yellow “STEADY STATE” LED indicates that the charger is turned off.

• The red “CHRG ON” LED indicates that the battery is under full charge.

   

Note: 

The “STEADY STATE” and “CHRG ON” LEDs will toggle faster with a discharged battery. A fully charged battery 

   will cause the yellow “STEADY STATE” LED to be illuminated longer than the red “CHRG ON” LED.

• The green “AC ON” LED indicates that normal AC power is being supplied to the EXIT sign.

Test Button Features

MANUAL TEST – Pressing the test button will switch the unit into battery mode for a set amount of time. The desired 

length of the test is determined by the number of times the test button is pressed.

• Pressing the test button once will switch the unit into battery mode for a period of 2 seconds.

• Pressing the test button twice within 2 seconds will switch the unit into battery mode for a period of 15 minutes.

Pressing the test button once while the unit is MANUAL TEST mode will cancel the manual test and return the unit to 

normal AC power.

RESET – Pressing the test button 3 times will reset the red “UNIT ALERT” LED. If multiple faults are present, it may be 

necessary to repeat this procedure for each remaining fault indicated by the “UNIT ALERT” LED.

Use in accordance with local building codes.

Number of Blinks

1

2

3

4

5

Unit Fault

Battery is Disconnected

Battery Failure

Not Applicable

Charge

Transfer (AC to DC)

Corrective Action

Check Battery Connections

Replace Battery

Not Applicable

Check Battery then Consult Factory
Check Battery then Consult Factory

Содержание Exitronix 900E Series

Страница 1: ...rvice personnel only Ensure that the electrical wiring conforms to the National Electrical Code NEC and local regulations if applicable For use with metal enclosed wiring systems Do not mount near gas or electrical heaters Do not use outdoors Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel The use of accessory eq...

Страница 2: ...he Self test Self diagnostics option do not require DIP switch adjustment 6 Connect the battery to the PCB Red goes to positive and black goes to negative Fig 2 7 Route the wires out through the canopy 8 Slide the homeplate assembly back into the housing 9 Slide the panel assembly into the housing 10 Install the test button and LED indicator in the end cap Fig 3 11 Secure the end cap assembly usin...

Страница 3: ...lies flat Incorrect placement of the lock nut may result in failure 4 Guide the pendant canopy onto the extension rod in the orientation shown Once in place at the top of the extension rod tighten the set screw of the pendant canopy to secure 5 Thread a lock nut on the bottom end of the extension rod Tighten the lock nut so it is not able to spin freely 6 Punch out the center knockout of the J box...

Страница 4: ...sing by inserting the tab of the J box into the bridge lance and securing with a 6 32 x 1 4 screw provided Attach the hanger bars to the sides of the recessed housing using 6 32 screws and wing nuts 6 Install the recessed assembly a If ceiling mounting position the recessed assembly between joists making sure the hanger bars are positioned correctly Use the adjusting slots to guide the hanger bars...

Страница 5: ...te 10 Secure the trimplate panel assembly to recessed housing with 2 6 32 X 3 4 screws Electrical Connections All electrical connections should be made inside the junction box Make electrical connection as follows 120VAC 220 230VAC 277VAC White Common White Common White Common Black 120VAC Yellow 220 230VAC Orange 277VAC Note Cap unused leads to prevent shorting Panel Assembly Test Button and LED ...

Страница 6: ...is turned off The red CHRG ON LED indicates that the battery is under full charge Note The STEADY STATE and CHRG ON LEDs will toggle faster with a discharged battery A fully charged battery will cause the yellow STEADY STATE LED to be illuminated longer than the red CHRG ON LED The green AC ON LED indicates that normal AC power is being supplied to the EXIT sign Test Button Features MANUAL TEST Pr...

Отзывы: