background image

Risk of electric shock. Always disconnect the pump from the power source before handling inspections or repairs.

Symptom

Possible Cause(s)

Corrective Action

Pump will not run

1.   Poor electrical connection, blown fuse, tripped 

  breaker or other interruption of power; 

  improper power supply
2.   Motor or switch inoperative (go to manual 
  operation)
2a. Float movement restricted
2b. Switch will not activate pump or is defective
2c. Defective motor
3.   Insuffi cient liquid level

1.  Check all electrical connections for security. 
  Have electrician measure current in motor leads, 
  if current is within ± 20% of locked rotor Amps, 
  impeller is probably locked. If current is 0, 
  overload may be tripped. Remove power, allow 
  pump to cool, then re-check current.
2a. Reposition pump or clean basin as required to 
  provide adaquate clearance for float
2b. Disconnect level control. Set ohmmeter for a 
  low rang, such as 100 ohms full scale and 
  connect to level control leads. Actuate level 
  control manually and check to see that 
  ohmmeter shows zero ohms for closed switch 
  and full scale for open switch. (Float Switch)
2c. Check winding insulation (Megger Test) and 
  winding resistance. If check is outside of range, 
  dry and re-check. If still defective, replace per 
  service instructions.
3.  Make sure liquid level is above the pump
4.  Re-check all sizing calculations to determine 
  proper pump size.
5.  Check discharge line for restrictions, including 
  ice if line passes through or into cold areas.
6.  Remove and examine check valve for proper 
  installation and freedom of operation
7.  Open valve
8.  Check impeller for freedom of operation, 
  security and condition. Clean impeller cavity 
  and inlet of any obstruction
9.  Loosen union slightly to allow trapped air to 

 escape. Verify that turn-off level of switch is set 

  so that the suction is always flooded. Clean vent
  hole
10. Check rotation. If power supply is three phase, 
  reverse any two of three power supply leads to 
  ensure proper impeller rotation
11. Repair fixtures as required to eliminate leakage
12. Check pump temperature limits and fluid
  temperature
13. Replace portion of discharge pipe with flexible
  connector or tighten existing piping.
14. Turn to automatic position
15. Check for leaks around basin inlet and outlets

Pump will not turn off 

2a. Float movement restricted
2b. Switch will not activate pump or is defective
4.   Excessive inflow or pump not properly sized for 

application

9.   Pump may be air locked causing pump not to flow
14. H-O-A switch on panel is in "HAND" position

Pump hums but doesn’t run

1.  Incorrect low voltage
8.  Impeller jammed or loose on shaft, or inlet 
  plugged

Pump delivers insufficient capacity

1.  Incorrect low voltage
4.   Excessive inflow or pump not properly sized for
  application
5.  Discharge restricted
6.  Check valve partially closed or installed backwards
7.   Shut-off valve closed
8.  Impeller jammed or loose on shaft, or inlet 
  plugged
9.  Pump may be air locked causing pump not to flow
10. Piping fixtures leaking or discharge before the 
  nozzle

Pump cycles too frequently or runs periodically 

when f ixtures are not in use

6.  Check valve partially closed or installed backwards
11. Fixtures are leaking
15. Ground water entering basin

Pump shuts of f and turns on independent of

switch, (trips thermal overload protector). 

CAUTION!

Pump may start unexpectedly. 

Disconnect power supply.

1.  Incorrect low voltage
4.   Excessive inflow or pump not properly sized for
  application
8.  Impeller jammed or loose on shaft, or inlet 
  plugged
12. Excessive water temperature (internal 
  protection only)

Pump operates noisily or vibrates excessively

2c. Worn bearings, motor shaft bent
5.  Debris in impeller cavity or broken impeller
10. Pump running backwards
13. Piping attachments to building structure too 
  loose or rigid

NOTE: 

Barmesa Pumps assumes no responsibility for damage or injury due to disassembly in the field. Disassembly of the pumps or supplied accessories other 

than at Barmesa Pumps or its authorized service centers, automatically voids warranty.

14

Troubleshooting Chart

barmesapumps.com

Содержание 2BSE102SS

Страница 1: ...rsible Solids Handling Pumps IMPORTANT Read all instructions in this manual before operating or servicing a pump 2BSE SS 0 5 0 75 1 HP 1750 RPM 2BSE51SS 0 5 HP 2BSE72SS 2BSE73SS 2BSE74SS 0 75 HP 2BSE1...

Страница 2: ...associatedwithornearthepump T h i s p u m p i s n o t i n t e n d e d f o r u s e i n swimming pools or water installations where there is DANGER humancontactwithpumpedfluid Riskofelectric shock To re...

Страница 3: ...ctioninmotor Three phase NEMA B oil filled Requires overload protection to be included in controlpanel 18 661 6 687 2 165 2 FLANGE 9 763 12 637 6 5 4 875 12 937 11 8 3 FLANGE MODEL PART No HP VOLTS PH...

Страница 4: ...top of the motor housing or a minimum level of 10 inches above the basin floor Electrical Connections Power cable The power cable mounted to the pump must not be modified in any way except for shorten...

Страница 5: ...ll with new oil Insulation Test An insulation megger test should be performed on the motor Before the pump is put into service The resistance values ohms as well as the voltage volts and current amps...

Страница 6: ...ocks or 4 piece of pvc pipe to avoid resting unit on shaft 05 Service Pressure builds up extremely fast increase pressure by TAPPING air nozzle Too much pressure will damage seal DO NOT exceed 10 PSI...

Страница 7: ...r equivalent to shaft threads Screw impeller onto shaft hand tight while using a screwdriver in the slot at the end of the shaft to hold it stationary Rotate impeller to check for binding 12 Place gas...

Страница 8: ...POWER CORD 4x12 G T1 T7 T2 T8 T3 T9 T4 T5 T6 G L1 L2 L3 GREEN BLACK RED WHITE MOTOR LEADS Cable Motor Lead Number Green Green Black 1 and 7 Red 2 and 8 White 3 and 9 4 5 and 6 together Figure 4 T2 T3...

Страница 9: ...08 Repair Parts Figure 5 For Repair Part Please supply Model Number and Serial as shown on Name Plate and Part Description and Part Number as shown on Parts List barmesapumps com...

Страница 10: ...R 3 DISHARGE 1 HT200 22 HEX SOCKET CAP SCREWS 1 4 20UNC x 28 2 SS 304 23 V SHAPE RING 1 NBR 40 24 MECHANICAL SEAL 31 8 x 15 9 x 32 5 1 SiC SiC 25 ELLASTIC COLLAR 40 1 65Mn 26 ELLASTIC COLLAR 17 1 65Mn...

Страница 11: ...supply leads to ensure proper impeller rotation 11 Repair fixturesasrequiredtoeliminateleakage 12 Check pump temperature limits and fluid temperature 13 Replace portion of discharge pipe with flexible...

Страница 12: ......

Отзывы: