Bard WPV48D Скачать руководство пользователя страница 21

Manual   2100-250
Page   19

1.   COOLING WITH OR WITHOUT DUCT HEATERS

Whenever the system lever is moved to COOL, thermostat system switch completes a circuit R to O,
energizing the reversing valve solenoid.  On a call for cooling, the cooling bulb completes a circuit from
R to G, energizing the blower relay coil.  The blower relay contacts complete a 230 volt circuit to the
blower motor and the blower operates.  R to Y circuit is completed at the same time as the fan circuit
and current flows from Y to terminal 4 at the lockout relay.  Terminal 4 of the lockout relay provides two
paths for current flow.

A. Through the lockout relay coil which offers the resistance of the lockout relay coil.

B. Through the normally closed contacts of the lockout relay to terminal 5 of the lockout relay and then

through the high and low pressure switches to the compressor contactor coil.

If the high pressure and low temperature switches remain closed (refrigerant pressure and temperature
remains normal), the path of least resistance is through these safety controls to the compressor
contactor coil.  The contacts of the compressor contactor complete a 230 volt circuit to the compressor
and the compressor runs.  If discharge pressure reaches the set point of the high pressure control, the
normally closed contacts of the high pressure control open and current no longer flows to the
compressor contact coil--the coil drops out.  Current now can take the path of least resistance through
the lockout relay coil, energizing the lockout relay coil and opening terminals 4 and 5 of the lockout
relay.  The lockout relay will remain energized as long as a circuit is completed between R and Y at the
thermostat.  In the meantime, since the compressor is operating, refrigerant pressure will equalize and
the high pressure switch will automatically reset.  However, the circuit to the compressor contact will not
be complete until the lockout relay is de-energized by moving the thermostat system switch to OFF,
breaking the circuit from R to Y dropping out the lockout relay coil and permitting terminals 4 and 5 to
make.  When the high pressure switch closes, a circuit is complete to L at the thermostat, energizing
the signal light to indicate a malfunction.  When the system switch is moved from OFF to COOL, the
cycle is repeated.

2.   SINGLE STAGE HEAT WITHOUT DUCT HEATERS

Compressor circuit R to Y including lockout relay and pressure controls is the same as cooling.  Blower
circuit R to G is the same as cooling.  With system switch set to HEAT, no circuit is completed between
R and O and reversing valve solenoid is not energized.

3.   TWO STAGE HEAT WITH DUCT HEATERS

First stage heat is the same as single heating without duct heater.  When the second stage thermostat
bulb makes, a circuit is completed from C to W2, energizing the duct heater heat contactor, through the
heating element and manual reset limit.  C to W2 also simultaneously energizes the 24 volt coil on the
interlock relay, closing the contacts, which in turn energize the low voltage coil on the blower relay to
close the high voltage contacts and power the blower motor.  The elements and blower remain energized
as long as C to W2 are made.

4.   EMERGENCY HEAT

When the system switch is moved to EMER, the compressor circuit R to Y is disconnected.  Control of
the electric heaters is from C to W2 and W3 through the thermostat second stage heating bulb.  Blower
operation is controlled by the second stage heating bulb.  Operation is the same as above, "Two Stage
Heat with Duct Heaters."

SEQUENCE OF OPERATION

Содержание WPV48D

Страница 1: ...48D WPV60D BARD MANUFACTURING COMPANY Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 250G Supersedes 2100 250F File Volume I Tab 8 Date 09 25 01 Copyright 2001 Earth Loop Fluid T...

Страница 2: ...t Pump Performance Report 31 32 Figures Figure 1 Filter Removal 3 Figure 2 Piping Access to the Unit 3 Figure 3 Optional Terminal Board Cover 4 Figure 4 Duct Heater 5 Figure 5 Connection of Water Line...

Страница 3: ...h c n I r e P s n i F 3 1 3 6 4 3 1 3 6 4 S B L T H G I E W G N I P P I H S 0 7 3 5 7 3 TABLE 3 INDOOR BLOWER PERFORMANCE CFM DRY COIL WITH FILTER j For wet coil CFM multiply by 96 ESP External Stati...

Страница 4: ...ems NFPA No 90B LOCATION The unit may be installed in a basement closet or utility room provided adequate service access is insured Ideally three sides of the unit should have a minimum access clearan...

Страница 5: ...local plumbing codes It is not recommended that any condensate drain line be connected to a sewer main The drain line enters the unit through the water access panel see Figure 2 and connects to the FP...

Страница 6: ...he momentary high starting current of the compressor motor THERMOSTAT LOW VOLTAGE WIRING A 24 volt terminal strip is mounted on top of the unit with an optional terminal board cover included with the...

Страница 7: ...hite wire from the heater to W2 on 24 volt terminal block A For the 15 and 20 KW duct heaters connect the white and white with black tracer wires to W2 TABLE 4 ACCESSORY ITEMS DUCT HEATER SEE FIGURE 4...

Страница 8: ...nected to a home water heater The amount of annual hot water supplied and thus additional energy cost savings will depend on the amount of hot water usage and the number of hours the heat pump operate...

Страница 9: ...solution through the earth coupling heat pump and equipment room components The small circulator keeps the operating costs of the system to a minimum However the performance of the circulator MUST be...

Страница 10: ...s test plugs in order to start up and troubleshoot a closed loop system properly water in and water out temperatures at the heat pump must be monitored A test plug is installed on one leg of each conn...

Страница 11: ...e exterior of the heat pump if 3 4 inch piping is used in small heat pump models Be sure to use a backup wrench when installing the adapters to the heat pump PIPING CONNECTIONS Up to 12 feet of reinfo...

Страница 12: ...OUT PRESSURE TEMPERATURE TEST PLUG WATER IN PRESSURE TEMPERATURE TEST PLUG PIPING ACCESS PANEL MAY BE INSTALLED AS SHOWN OR ON LEFT OR RIGHT SIDE OF UNIT INSTALL 1 750 SNAP BUSHING wpv8 tif MIS 1219 T...

Страница 13: ...Manual 2100 250 Page 11 HEAD FEET FIGURE 12 PUMP MODULE HOOKUP FLOW GPM HEAD FEET FIGURE 13 PRESSURE AND TEMPERATURE SENSING ADAPTER AND COMPONENTS FLOW GPM wpv20 tif...

Страница 14: ...flow rate If the flow rate is too low recheck the selection of the loop pump module model for sufficient capacity If the module selection is correct there is probably trapped air or a restriction in...

Страница 15: ...o the unit regardless of variations in water pressure Observe the water flow direction indicated by the arrow on the side of the valve body Following is a table showing which valve is to be installed...

Страница 16: ...ents are met 1 Adequate flow rate in GPM 2 Adequate pressure at the fixture 3 Able to meet the above from the depth of the well feet of lift The pressure requirements put on the pump are directly affe...

Страница 17: ...air flow problems and then refrigeration system problems NOTE If a charge problem is determined high or low A Check for possible refrigerant loss B Discharge all remaining refrigerant from unit C Evac...

Страница 18: ...bonate of calcium and magnesium carbonate is very soluble in water It will remain dissolved in the water until some outside factor upsets the balance This outside influence may be a large change in wa...

Страница 19: ...y sized submersible pumps Pipe the unit the same as a water well system D Size the pump to provide necessary GPM for the ground water heat pump A 12 GPM or greater water flow rate is required on all m...

Страница 20: ...IGURE 16 WATER WELL SYSTEM WATER SUPPLY LINE ELECTRICAL LINE 12 to 15 LAKE or POND GRAVEL FILL WATER LEVEL 15 TO 20 DEEP DROP PIPE PERFORATED PLASTIC CASING SUBMERSIBLE PUMP TO PRESSURE TANK WELL CAP...

Страница 21: ...at the thermostat In the meantime since the compressor is operating refrigerant pressure will equalize and the high pressure switch will automatically reset However the circuit to the compressor conta...

Страница 22: ...Manual 2100 250 Page 20 FIGURE 18 FIGURE 17 MIS 096 wpv13 tif...

Страница 23: ...Manual 2100 250 Page 21 FIGURE 19 WATER SOURCE HEAT PUMP COOLING CYCLE MIS 1229...

Страница 24: ...Manual 2100 250 Page 22 FIGURE 20 WATER SOURCE HEAT PUMP HEATING CYCLE MIS 1228...

Страница 25: ...3 4 9 7 3 0 0 0 0 6 0 0 1 8 4 1 0 4 0 0 0 5 6 3 3 9 2 5 1 2 4 TABLE 6B MODEL WPV48D 1 550 CFM 9 GPM y r D b l u B b l u B t e W y t i c a p a C g n i l o o C F s e e r g e D l i o C r e t a W g n i r...

Страница 26: ...G s u l P g n i t a e H g n i l o o C h u t B s t t a W h u t B s t t a W 2 0 0 1 8 9 1 0 1 0 0 1 4 1 0 1 7 9 3 0 1 1 0 1 6 2 0 1 6 9 5 0 1 2 0 1 8 2 0 1 5 9 6 0 1 2 0 1 TABLE 9 FLOW RATES FOR VARIOUS...

Страница 27: ...7 1 5 1 7 7 2 6 1 6 7 3 7 1 6 7 4 8 1 5 7 5 9 1 5 7 6 0 2 4 7 7 1 2 3 7 9 2 2 3 7 0 4 2 3 7 0 5 2 2 7 2 6 2 2 7 3 7 2 1 7 4 8 2 1 7 5 9 2 D 0 6 V P W B D 5 7 B W 2 6 e d i S w o L e d i S h g i H 9 5...

Страница 28: ...ctive Air Volume Low Air Filters Dirty Undersized or Restricted Ductwork Auxillary Heat Upstream of Coil Compressor Will Not Run No Power at Contactor Compressor Will Not Run Power at Contactor Compre...

Страница 29: ...Manual 2100 250 Page 27 THERMOSTATDIAGRAMS...

Страница 30: ...Manual 2100 250 Page 28...

Страница 31: ...Manual 2100 250 Page 29...

Страница 32: ...Manual 2100 250 Page 30...

Страница 33: ...Date Installed 5 User s Owner s Name Address 6 Unit Location WATER SYSTEM INFORMATION 7 Open Loop System Water Well Closed Loop System A If Open Loop where is water discharged 8 The following questio...

Страница 34: ...ine temperature 6 from compressor F 21 Superheat at compressor F 22 Liquid line temperature at metering device F 23 Coil Subcooling F INDOOR SIDE DATA Cooling Heating 24 Dry bulb temperature at air en...

Отзывы: