SYSTEM START UP PROCEDURE

1. Be sure main power to the unit is OFF at disconnect.

2. Set thermostat system switch to OFF, fan switch to AUTO.

3. Move main power disconnect to ON.  Except as required for safety while servicing, DO NOT

OPEN THE UNIT DISCONNECT SWITCH.

4. Check system air flow for obstructions.

A. Move thermostat fan switch to ON.  Blower runs.

B. Be sure all registers and grilles are open.

C. Move thermostat fan switch to AUTO.  Blower should stop.

5. Flush, fill and pressurize the closed loop system as outlined in manual 2100-099.

6. Fully open the manual inlet and outlet valves.  Start the loop pump module circulator(s) and check for

proper operation.  If circulator(s) are not operating, turn off power and diagnose the problem.

7. Check fluid flow using a direct reading flow meter or a single water pressure gauge, measure the

pressure drop at the pressure-temperature plugs across the water coil.  Compare the measurement
with flow versus pressure drop table to determine the actual flow rate.  If the flow rate is too low,
recheck the selection of the loop pump module model for sufficient capacity.  If the module selection is
correct, there is probably trapped air or a restriction in the piping circuit.

8. Start the unit in cooling mode.  By moving the thermostat switch to cool, fan should be set for AUTO.

9. Check the system refrigerant pressures against the cooling refrigerant pressure table in the installation

manual for rated water flow and entering water temperatures.  If the refrigerant pressures do not
match, check for air flow problem then refrigeration system problem.

10. Switch the unit to the heating mode.  By moving the thermostat switch to heat, fan should be set for

AUTO.

11. Check the refrigerant system pressures against the heating refrigerant pressure table in installation

manual.  Once again, if they do not match, check for air flow problems and then refrigeration system
problems.

NOTE:  If a charge problem is determined (high or low):

A. Check for possible refrigerant leaks.

B. Recover all remaining refrigerant from unit and repair leak.

C. Evacuate unit down to 29 inches of vacuum.

D. Recharge the unit with refrigerant by weight.  This is the only way to insure a proper charge.

Содержание WPV48D

Страница 1: ...48D WPV60D BARD MANUFACTURING COMPANY Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 250G Supersedes 2100 250F File Volume I Tab 8 Date 09 25 01 Copyright 2001 Earth Loop Fluid T...

Страница 2: ...t Pump Performance Report 31 32 Figures Figure 1 Filter Removal 3 Figure 2 Piping Access to the Unit 3 Figure 3 Optional Terminal Board Cover 4 Figure 4 Duct Heater 5 Figure 5 Connection of Water Line...

Страница 3: ...h c n I r e P s n i F 3 1 3 6 4 3 1 3 6 4 S B L T H G I E W G N I P P I H S 0 7 3 5 7 3 TABLE 3 INDOOR BLOWER PERFORMANCE CFM DRY COIL WITH FILTER j For wet coil CFM multiply by 96 ESP External Stati...

Страница 4: ...ems NFPA No 90B LOCATION The unit may be installed in a basement closet or utility room provided adequate service access is insured Ideally three sides of the unit should have a minimum access clearan...

Страница 5: ...local plumbing codes It is not recommended that any condensate drain line be connected to a sewer main The drain line enters the unit through the water access panel see Figure 2 and connects to the FP...

Страница 6: ...he momentary high starting current of the compressor motor THERMOSTAT LOW VOLTAGE WIRING A 24 volt terminal strip is mounted on top of the unit with an optional terminal board cover included with the...

Страница 7: ...hite wire from the heater to W2 on 24 volt terminal block A For the 15 and 20 KW duct heaters connect the white and white with black tracer wires to W2 TABLE 4 ACCESSORY ITEMS DUCT HEATER SEE FIGURE 4...

Страница 8: ...nected to a home water heater The amount of annual hot water supplied and thus additional energy cost savings will depend on the amount of hot water usage and the number of hours the heat pump operate...

Страница 9: ...solution through the earth coupling heat pump and equipment room components The small circulator keeps the operating costs of the system to a minimum However the performance of the circulator MUST be...

Страница 10: ...s test plugs in order to start up and troubleshoot a closed loop system properly water in and water out temperatures at the heat pump must be monitored A test plug is installed on one leg of each conn...

Страница 11: ...e exterior of the heat pump if 3 4 inch piping is used in small heat pump models Be sure to use a backup wrench when installing the adapters to the heat pump PIPING CONNECTIONS Up to 12 feet of reinfo...

Страница 12: ...OUT PRESSURE TEMPERATURE TEST PLUG WATER IN PRESSURE TEMPERATURE TEST PLUG PIPING ACCESS PANEL MAY BE INSTALLED AS SHOWN OR ON LEFT OR RIGHT SIDE OF UNIT INSTALL 1 750 SNAP BUSHING wpv8 tif MIS 1219 T...

Страница 13: ...Manual 2100 250 Page 11 HEAD FEET FIGURE 12 PUMP MODULE HOOKUP FLOW GPM HEAD FEET FIGURE 13 PRESSURE AND TEMPERATURE SENSING ADAPTER AND COMPONENTS FLOW GPM wpv20 tif...

Страница 14: ...flow rate If the flow rate is too low recheck the selection of the loop pump module model for sufficient capacity If the module selection is correct there is probably trapped air or a restriction in...

Страница 15: ...o the unit regardless of variations in water pressure Observe the water flow direction indicated by the arrow on the side of the valve body Following is a table showing which valve is to be installed...

Страница 16: ...ents are met 1 Adequate flow rate in GPM 2 Adequate pressure at the fixture 3 Able to meet the above from the depth of the well feet of lift The pressure requirements put on the pump are directly affe...

Страница 17: ...air flow problems and then refrigeration system problems NOTE If a charge problem is determined high or low A Check for possible refrigerant loss B Discharge all remaining refrigerant from unit C Evac...

Страница 18: ...bonate of calcium and magnesium carbonate is very soluble in water It will remain dissolved in the water until some outside factor upsets the balance This outside influence may be a large change in wa...

Страница 19: ...y sized submersible pumps Pipe the unit the same as a water well system D Size the pump to provide necessary GPM for the ground water heat pump A 12 GPM or greater water flow rate is required on all m...

Страница 20: ...IGURE 16 WATER WELL SYSTEM WATER SUPPLY LINE ELECTRICAL LINE 12 to 15 LAKE or POND GRAVEL FILL WATER LEVEL 15 TO 20 DEEP DROP PIPE PERFORATED PLASTIC CASING SUBMERSIBLE PUMP TO PRESSURE TANK WELL CAP...

Страница 21: ...at the thermostat In the meantime since the compressor is operating refrigerant pressure will equalize and the high pressure switch will automatically reset However the circuit to the compressor conta...

Страница 22: ...Manual 2100 250 Page 20 FIGURE 18 FIGURE 17 MIS 096 wpv13 tif...

Страница 23: ...Manual 2100 250 Page 21 FIGURE 19 WATER SOURCE HEAT PUMP COOLING CYCLE MIS 1229...

Страница 24: ...Manual 2100 250 Page 22 FIGURE 20 WATER SOURCE HEAT PUMP HEATING CYCLE MIS 1228...

Страница 25: ...3 4 9 7 3 0 0 0 0 6 0 0 1 8 4 1 0 4 0 0 0 5 6 3 3 9 2 5 1 2 4 TABLE 6B MODEL WPV48D 1 550 CFM 9 GPM y r D b l u B b l u B t e W y t i c a p a C g n i l o o C F s e e r g e D l i o C r e t a W g n i r...

Страница 26: ...G s u l P g n i t a e H g n i l o o C h u t B s t t a W h u t B s t t a W 2 0 0 1 8 9 1 0 1 0 0 1 4 1 0 1 7 9 3 0 1 1 0 1 6 2 0 1 6 9 5 0 1 2 0 1 8 2 0 1 5 9 6 0 1 2 0 1 TABLE 9 FLOW RATES FOR VARIOUS...

Страница 27: ...7 1 5 1 7 7 2 6 1 6 7 3 7 1 6 7 4 8 1 5 7 5 9 1 5 7 6 0 2 4 7 7 1 2 3 7 9 2 2 3 7 0 4 2 3 7 0 5 2 2 7 2 6 2 2 7 3 7 2 1 7 4 8 2 1 7 5 9 2 D 0 6 V P W B D 5 7 B W 2 6 e d i S w o L e d i S h g i H 9 5...

Страница 28: ...ctive Air Volume Low Air Filters Dirty Undersized or Restricted Ductwork Auxillary Heat Upstream of Coil Compressor Will Not Run No Power at Contactor Compressor Will Not Run Power at Contactor Compre...

Страница 29: ...Manual 2100 250 Page 27 THERMOSTATDIAGRAMS...

Страница 30: ...Manual 2100 250 Page 28...

Страница 31: ...Manual 2100 250 Page 29...

Страница 32: ...Manual 2100 250 Page 30...

Страница 33: ...Date Installed 5 User s Owner s Name Address 6 Unit Location WATER SYSTEM INFORMATION 7 Open Loop System Water Well Closed Loop System A If Open Loop where is water discharged 8 The following questio...

Страница 34: ...ine temperature 6 from compressor F 21 Superheat at compressor F 22 Liquid line temperature at metering device F 23 Coil Subcooling F INDOOR SIDE DATA Cooling Heating 24 Dry bulb temperature at air en...

Отзывы: