
Manual 2100-250
Page 17
LAKE AND POND INSTALLATIONS
Lakes and ponds can provide a low cost source of water for heating and cooling with a ground water heat
pump. Direct usage of the water without some filtration is not recommended as algae and turbid water can
foul the water to freon heat exchanger. Instead, there have been very good results using a dry well dug next to
the water line or edge. Normal procedure in installing a dry well is to backhoe a 15 to 20 foot hole adjacent to
the body of water (set backhoe as close to the water's edge as possible). Once excavated, a perforated
plastic casing should be installed with gravel backfill placed around the casing. The gravel bed should provide
adequate filtration of the water to allow good performance of the ground water heat pump. Refer to Figure 16.
The following is a list of recommendations to following when installing this type of system:
A. A lake or pond should be at least 1 acre (40,000 square feet) in surface area for each 50,000 BTUs of
ground water heat pump capacity or have 2 times the cubic feet size of the dwelling that you are trying
to heat (includes basement if heated).
B. The average water depth should be at least 5 feet and there should be an area where the water depth
is at least 12 to 15 feet deep.
C. If possible, use a submersible pump suspended in the dry well casing. Jet pumps and other types of
suction pumps normally consume more electrical energy than similarly sized submersible pumps. Pipe
the unit the same as a water well system.
D. Size the pump to provide necessary GPM for the ground water heat pump. A 12 GPM or greater water
flow rate is required on all modes when used on this type system.
E. A pressure tank should be installed in dwelling to be heated adjacent to the ground water heat pump.
A pressure switch should be installed at the tank for pump control.
F. All plumbing should be carefully sized to compensate for friction losses, etc., particularly if the pond or
lake is over 200 feet from the dwelling to be heated or cooled.
G. Keep all water lines below low water level and below the frost line.
H. Most installers use 4 inch field tile (rigid plastic or corrugated) for water return to the lake or pond.
I. The drain line discharge should be located at least 100 feet from the dry well location.
J. The drain line should be installed with a slope of 2 inches per 10 feet of run to provide complete
drainage of the line when the ground water heat pump is not operating. This gradient should also help
prevent freezing of the discharge where the pipe terminates above the frost line.
K. Locate the discharge high enough above high water level so the water will not back up and freeze
inside the drain pipe.
L. Where the local conditions prevent the use of a gravity drainage system to a lake or pond, you can
instead run standard plastic piping out into the pond below the frost and low water level.
For complete information on water well systems and lake and pond applications, refer to Manual 2100-078
available from your distributor.
WARNING
Thin ice may result in the vicinity of the discharge line.
Содержание WPV48D
Страница 22: ...Manual 2100 250 Page 20 FIGURE 18 FIGURE 17 MIS 096 wpv13 tif...
Страница 23: ...Manual 2100 250 Page 21 FIGURE 19 WATER SOURCE HEAT PUMP COOLING CYCLE MIS 1229...
Страница 24: ...Manual 2100 250 Page 22 FIGURE 20 WATER SOURCE HEAT PUMP HEATING CYCLE MIS 1228...
Страница 29: ...Manual 2100 250 Page 27 THERMOSTATDIAGRAMS...
Страница 30: ...Manual 2100 250 Page 28...
Страница 31: ...Manual 2100 250 Page 29...
Страница 32: ...Manual 2100 250 Page 30...