Bard WPV48D Скачать руководство пользователя страница 19

Manual   2100-250
Page   17

LAKE AND POND INSTALLATIONS

Lakes and ponds can provide a low cost source of water for heating and cooling with a ground water heat
pump.  Direct usage of the water without some filtration is not recommended as algae and turbid water can
foul the water to freon heat exchanger.  Instead, there have been very good results using a dry well dug next to
the water line or edge.  Normal procedure in installing a dry well is to backhoe a 15 to 20 foot hole adjacent to
the body of water (set backhoe as close to the water's edge as possible).  Once excavated, a perforated
plastic casing should be installed with gravel backfill placed around the casing.  The gravel bed should provide
adequate filtration of the water to allow good performance of the ground water heat pump.  Refer to Figure 16.

The following is a list of recommendations to following when installing this type of system:

A. A lake or pond should be at least 1 acre (40,000 square feet) in surface area for each 50,000 BTUs of

ground water heat pump capacity or have 2 times the cubic feet size of the dwelling that you are trying
to heat (includes basement if heated).

B. The average water depth should be at least 5 feet and there should be an area where the water depth

is at least 12 to 15 feet deep.

C. If  possible, use a submersible pump suspended in the dry well casing.  Jet pumps and other types of

suction pumps normally consume more electrical energy than similarly sized submersible pumps.  Pipe
the unit the same as a water well system.

D. Size the pump to provide necessary GPM for the ground water heat pump.  A 12 GPM or greater water

flow rate is required on all modes when used on this type system.

E. A pressure tank should be installed in dwelling to be heated adjacent to the ground water heat pump.

A pressure switch should be installed at the tank for pump control.

F. All plumbing should be carefully sized to compensate for friction losses, etc., particularly if the pond or

lake is over 200 feet from the dwelling to be heated or cooled.

G. Keep all water lines below low water level and below the frost line.

H. Most installers use 4 inch field tile (rigid plastic or corrugated) for water return to the lake or pond.

I. The drain line discharge should be located at least 100 feet from the dry well location.

J. The drain line should be installed with a slope of 2 inches per 10 feet of run to provide complete

drainage of the line when the ground water heat pump is not operating.  This gradient should also help
prevent freezing of the discharge where the pipe terminates above the frost line.

K. Locate the discharge high enough above high water level so the water will not back up and freeze

inside the drain pipe.

L. Where the local conditions prevent the use of a gravity drainage system to a lake or pond, you can

instead run standard plastic piping out into the pond below the frost and low water level.

For complete information on water well systems and lake and pond applications, refer to Manual 2100-078
available from your distributor.

          WARNING

Thin ice may result in the vicinity of the discharge line.

Содержание WPV48D

Страница 1: ...48D WPV60D BARD MANUFACTURING COMPANY Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 250G Supersedes 2100 250F File Volume I Tab 8 Date 09 25 01 Copyright 2001 Earth Loop Fluid T...

Страница 2: ...t Pump Performance Report 31 32 Figures Figure 1 Filter Removal 3 Figure 2 Piping Access to the Unit 3 Figure 3 Optional Terminal Board Cover 4 Figure 4 Duct Heater 5 Figure 5 Connection of Water Line...

Страница 3: ...h c n I r e P s n i F 3 1 3 6 4 3 1 3 6 4 S B L T H G I E W G N I P P I H S 0 7 3 5 7 3 TABLE 3 INDOOR BLOWER PERFORMANCE CFM DRY COIL WITH FILTER j For wet coil CFM multiply by 96 ESP External Stati...

Страница 4: ...ems NFPA No 90B LOCATION The unit may be installed in a basement closet or utility room provided adequate service access is insured Ideally three sides of the unit should have a minimum access clearan...

Страница 5: ...local plumbing codes It is not recommended that any condensate drain line be connected to a sewer main The drain line enters the unit through the water access panel see Figure 2 and connects to the FP...

Страница 6: ...he momentary high starting current of the compressor motor THERMOSTAT LOW VOLTAGE WIRING A 24 volt terminal strip is mounted on top of the unit with an optional terminal board cover included with the...

Страница 7: ...hite wire from the heater to W2 on 24 volt terminal block A For the 15 and 20 KW duct heaters connect the white and white with black tracer wires to W2 TABLE 4 ACCESSORY ITEMS DUCT HEATER SEE FIGURE 4...

Страница 8: ...nected to a home water heater The amount of annual hot water supplied and thus additional energy cost savings will depend on the amount of hot water usage and the number of hours the heat pump operate...

Страница 9: ...solution through the earth coupling heat pump and equipment room components The small circulator keeps the operating costs of the system to a minimum However the performance of the circulator MUST be...

Страница 10: ...s test plugs in order to start up and troubleshoot a closed loop system properly water in and water out temperatures at the heat pump must be monitored A test plug is installed on one leg of each conn...

Страница 11: ...e exterior of the heat pump if 3 4 inch piping is used in small heat pump models Be sure to use a backup wrench when installing the adapters to the heat pump PIPING CONNECTIONS Up to 12 feet of reinfo...

Страница 12: ...OUT PRESSURE TEMPERATURE TEST PLUG WATER IN PRESSURE TEMPERATURE TEST PLUG PIPING ACCESS PANEL MAY BE INSTALLED AS SHOWN OR ON LEFT OR RIGHT SIDE OF UNIT INSTALL 1 750 SNAP BUSHING wpv8 tif MIS 1219 T...

Страница 13: ...Manual 2100 250 Page 11 HEAD FEET FIGURE 12 PUMP MODULE HOOKUP FLOW GPM HEAD FEET FIGURE 13 PRESSURE AND TEMPERATURE SENSING ADAPTER AND COMPONENTS FLOW GPM wpv20 tif...

Страница 14: ...flow rate If the flow rate is too low recheck the selection of the loop pump module model for sufficient capacity If the module selection is correct there is probably trapped air or a restriction in...

Страница 15: ...o the unit regardless of variations in water pressure Observe the water flow direction indicated by the arrow on the side of the valve body Following is a table showing which valve is to be installed...

Страница 16: ...ents are met 1 Adequate flow rate in GPM 2 Adequate pressure at the fixture 3 Able to meet the above from the depth of the well feet of lift The pressure requirements put on the pump are directly affe...

Страница 17: ...air flow problems and then refrigeration system problems NOTE If a charge problem is determined high or low A Check for possible refrigerant loss B Discharge all remaining refrigerant from unit C Evac...

Страница 18: ...bonate of calcium and magnesium carbonate is very soluble in water It will remain dissolved in the water until some outside factor upsets the balance This outside influence may be a large change in wa...

Страница 19: ...y sized submersible pumps Pipe the unit the same as a water well system D Size the pump to provide necessary GPM for the ground water heat pump A 12 GPM or greater water flow rate is required on all m...

Страница 20: ...IGURE 16 WATER WELL SYSTEM WATER SUPPLY LINE ELECTRICAL LINE 12 to 15 LAKE or POND GRAVEL FILL WATER LEVEL 15 TO 20 DEEP DROP PIPE PERFORATED PLASTIC CASING SUBMERSIBLE PUMP TO PRESSURE TANK WELL CAP...

Страница 21: ...at the thermostat In the meantime since the compressor is operating refrigerant pressure will equalize and the high pressure switch will automatically reset However the circuit to the compressor conta...

Страница 22: ...Manual 2100 250 Page 20 FIGURE 18 FIGURE 17 MIS 096 wpv13 tif...

Страница 23: ...Manual 2100 250 Page 21 FIGURE 19 WATER SOURCE HEAT PUMP COOLING CYCLE MIS 1229...

Страница 24: ...Manual 2100 250 Page 22 FIGURE 20 WATER SOURCE HEAT PUMP HEATING CYCLE MIS 1228...

Страница 25: ...3 4 9 7 3 0 0 0 0 6 0 0 1 8 4 1 0 4 0 0 0 5 6 3 3 9 2 5 1 2 4 TABLE 6B MODEL WPV48D 1 550 CFM 9 GPM y r D b l u B b l u B t e W y t i c a p a C g n i l o o C F s e e r g e D l i o C r e t a W g n i r...

Страница 26: ...G s u l P g n i t a e H g n i l o o C h u t B s t t a W h u t B s t t a W 2 0 0 1 8 9 1 0 1 0 0 1 4 1 0 1 7 9 3 0 1 1 0 1 6 2 0 1 6 9 5 0 1 2 0 1 8 2 0 1 5 9 6 0 1 2 0 1 TABLE 9 FLOW RATES FOR VARIOUS...

Страница 27: ...7 1 5 1 7 7 2 6 1 6 7 3 7 1 6 7 4 8 1 5 7 5 9 1 5 7 6 0 2 4 7 7 1 2 3 7 9 2 2 3 7 0 4 2 3 7 0 5 2 2 7 2 6 2 2 7 3 7 2 1 7 4 8 2 1 7 5 9 2 D 0 6 V P W B D 5 7 B W 2 6 e d i S w o L e d i S h g i H 9 5...

Страница 28: ...ctive Air Volume Low Air Filters Dirty Undersized or Restricted Ductwork Auxillary Heat Upstream of Coil Compressor Will Not Run No Power at Contactor Compressor Will Not Run Power at Contactor Compre...

Страница 29: ...Manual 2100 250 Page 27 THERMOSTATDIAGRAMS...

Страница 30: ...Manual 2100 250 Page 28...

Страница 31: ...Manual 2100 250 Page 29...

Страница 32: ...Manual 2100 250 Page 30...

Страница 33: ...Date Installed 5 User s Owner s Name Address 6 Unit Location WATER SYSTEM INFORMATION 7 Open Loop System Water Well Closed Loop System A If Open Loop where is water discharged 8 The following questio...

Страница 34: ...ine temperature 6 from compressor F 21 Superheat at compressor F 22 Liquid line temperature at metering device F 23 Coil Subcooling F INDOOR SIDE DATA Cooling Heating 24 Dry bulb temperature at air en...

Отзывы: