background image

Manual 2100-405A
Page

16 of 18

Alarm Relay Output

Alarm terminal is output connection for applications
where alarm relay is employed.  This terminal is
powered whenever compressor is locked out due to HPC
or LPC sequences as described.

NOTE: Both high and low pressure switch controls

are inherently automatic reset devices.  The
high pressure switch and low pressure switch
cut out and cut in settings are fixed by specific
air conditioner or heat pump unit model.  The
lockout features, both soft and manual, are a
function of the Compressor Control Module.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break
Timer

The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes.  Delay on Make (DOM)
timing on power-up and after power interruptions is
equal to 2 minutes plus 10% of Delay on Break (DOB)
setting:

0.5 minute

(30 seconds) DOB = 123 second DOM

1.0 minute

(60 seconds) DOB = 126 second DOM

2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power
interruptions, the compressor will operate on demand
with no delay.

Typical Settings for Dual Unit Installation:

Unit 1:  DOB set at 2 minutes, and DOM is 132 seconds

Unit 2:  DOB set at 4 minutes, and DOM is 144 seconds

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed.  Pressure tables can be found later in the
manual covering all models.  It is imperative to match
the correct pressure table to the unit by model number.

COMPRESSOR CONTROL MODULE

The compressor control module is optional on the
models covered by this manual.  The compressor control
is an anti-short cycle/lockout timer with high and low
pressure switch monitoring and alarm relay output.

Adjustable Delay on Make and Break Timer

On initial power up or any time power is interrupted to
the unit the 

delay on make

 period begins, which will be

2 minutes plus 10% of the 

delay on break

 setting.  When

the delay on make is complete and the high pressure
switch (and low pressure switch if employed) is closed,
the compressor contactor is energized.  Upon shutdown,
the delay or break timer starts and prevents restart until
the delay on break and delay on make periods have
expired.

During routine operation of the unit with no power
interruptions, the compressor will operate on demand
with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout
timer will go into a 

soft lockout

 and stay in soft lockout

until the high pressure switch closes and the delay on
make time has expired.  If the high pressure switch
opens again in this same operating cycle the unit will go
into 

manual lockout

 condition and the alarm relay

circuit will energize.  Recycling the wall thermostat
resets the manual lockout.

Low Pressure Switch, Bypass, and Lockout
Sequence

If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout.  Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired.  If the low
pressure switch remains open, or opens again for longer
than 120 seconds the unit will go into manual lockout
condition and the alarm relay circuit will energize.
Recycling the wall thermostat resets the manual lockout.

Содержание WL302

Страница 1: ...o 2100 405A Supersedes 2100 405 File Volume III Tab 16 Date 07 25 06 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Model WL302 WL372 WALL MOUNTED PACKAGED AIR...

Страница 2: ...SP 17 Table 11 Maximum ESP of Operation Electric Heat Only 17 Table 12 Cooling Pressure 18 Table 13 Optional Accessories 18 Getting Other Information and Publications For more information contact thes...

Страница 3: ...er and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...uctors are in a raceway TABLE 1 ELECTRICAL SPECIFICATIONS s l e d o M d e t a R s t l o V s e s a h P o N d l e i F r e w o P s t i u c r i C 3 m u m i n i M t i u c r i C y t i c a p m A 1 m u m i x...

Страница 5: ...i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C B 2 0 3 L W 1 7 3 L W 0 2 8 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 7 2 8 8 3 1 8 8 7 2 0 0 0 4 0 5 8 1 5 7 5 2 3 9...

Страница 6: ...National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type NFPA No 90A and Residence Type Warm Air Heating and Air Conditioning...

Страница 7: ...tructions and Figures 3 4 and 5 for further details Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Any grille that meets t...

Страница 8: ...bustible wall 9 On side by side installations maintain a minimum of 20 inches clearance on left side to allow access to heat strips and control panel and to allow proper airflow to the outdoor coil Ad...

Страница 9: ...OPERATING VOLTAGE RANGE P A T E G N A R V 0 4 2 6 1 2 3 5 2 V 8 0 2 7 8 1 0 2 2 r e m r o f s n a r T A V A L F e g u a G e r i W m u m i x a M e c n a t s i D t e e F n I 5 5 3 2 e g u a g 0 2 e g u...

Страница 10: ...Manual 2100 405A Page 10 of 18 FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 11: ...ual 2100 405A Page 11 of 18 FIGURE 4 WALL MOUNTING INSTRUCTIONS FIGURE 5 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS FOR OPENING SIZES SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSI...

Страница 12: ...Manual 2100 405A Page 12 of 18 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Страница 13: ...ustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheatin...

Страница 14: ...Manual 2100 405A Page 14 of 18 FIGURE 8 LOW VOLTAGE WIRING...

Страница 15: ...urrent draw compared to tabulated values The direction of rotation of the compressor may be changed by reversing any two line connections to the unit START UP PHASE MONITOR All units with three phase...

Страница 16: ...CONTROL MODULE The compressor control module is optional on the models covered by this manual The compressor control is an anti short cycle lockout timer with high and low pressure switch monitoring a...

Страница 17: ...hes from compressor as shown in the following table A AIRFLOW TABLE 8 SUCTION LINE TEMPERATURES s l e d o M d e t a R w o l f r i A F 5 9 p m e T D O F 2 8 p m e T D O 2 0 3 L W 0 0 0 1 9 5 6 5 6 6 4...

Страница 18: ...3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 3 8 8 2 2 4 8 3 4 2 6 8 9 5 2 8 8 4 7 2 9 8 2 9 2 0 9 9 0 3 2 9 7 2 3 3 9 7 4 3 4 9 6 6 3 2 7 3 L W B D g e d 5 7 B W g e d 2 6 e d i S w o...

Отзывы: