background image

Manual 2100-342

I

Page

6 of 24

1

Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.

2

Based on 75° C copper wire.  All Wiring must conform to NEC and all local codes.

3

These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors.  Refer to the National Electric
Code (latest revision), article 310 for power conductor sizing.

CAUTION:

When more than one field power conductor circuit is run through one conduit, the conductors must be derated.
Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than 3 conductors
are in a raceway.

TABLE  2

ELECTRICAL SPECIFICATIONS

l

e

d

o

M

T

I

U

C

R

I

C

E

L

G

N

I

S

T

I

U

C

R

I

C

L

A

U

D

d

e

t

a

R

&

s

t

l

o

V

e

s

a

h

P

.

o

N

d

l

e

i

F

r

e

w

o

P

s

t

i

u

c

r

i

C

3

m

u

m

i

n

i

M

t

i

u

c

r

i

C

y

t

i

c

a

p

m

A

1

m

u

m

i

x

a

M

l

l

a

n

r

e

t

x

E

r

o

e

s

u

F

.

t

i

u

c

r

i

C

r

e

k

a

e

r

B

2

d

l

e

i

F

r

e

w

o

P

e

r

i

W

e

z

i

S

2

d

n

u

o

r

G

e

r

i

W

e

z

i

S

3

m

u

m

i

n

i

M

t

i

u

c

r

i

C

y

t

i

c

a

p

m

A

1

m

u

m

i

x

a

M

l

a

n

r

e

t

x

E

r

o

e

s

u

F

.

t

k

C

r

e

k

a

e

r

B

2

r

e

w

o

P

d

l

e

i

F

e

z

i

S

e

r

i

W

2

d

n

u

o

r

G

e

z

i

S

e

r

i

W

T

K

C

A

T

K

C

B

T

K

C

A

T

K

C

B

T

K

C

A

T

K

C

B

T

K

C

A

T

K

C

B

Z

0

A

,

0

0

A

-

1

8

3

H

W

5

0

A

8

0

A

0

1

A

1

-

8

0

2

/

0

3

2

1

2

r

o

1

2

r

o

1

2

r

o

1

1

3

7

5

3

7

3

8

5

4

0

7

0

8

0

9

8

6

4

4

0

1

8

8

8

-

-

-

1

3

1

3

1

3

-

-

-

6

2

2

4

2

5

-

-

-

0

5

0

5

0

5

-

-

-

0

3

5

4

0

6

-

-

-

8

8

8

-

-

-

0

1

8

6

-

-

-

0

1

0

1

0

1

-

-

-

0

1

0

1

0

1

Z

0

B

,

0

0

B

-

1

8

3

H

W

6

0

B

9

0

B

3

-

8

0

2

/

0

3

2

1

1

1

3

2

1

4

0

5

5

3

5

4

0

5

8

8

6

0

1

0

1

0

1

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

,

0

0

C

-

1

8

3

H

W

Z

0

C

6

0

C

9

0

C

3

-

0

6

4

1

1

1

3

1

1

2

5

2

5

1

5

2

0

3

4

1

0

1

0

1

4

1

0

1

0

1

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Z

0

A

,

0

0

A

-

1

3

4

H

W

5

0

A

8

0

A

0

1

A

1

-

8

0

2

/

0

3

2

1

2

r

o

1

2

r

o

1

2

r

o

1

4

3

0

6

6

7

6

8

0

5

0

7

0

8

0

9

8

6

4

3

0

1

8

8

8

-

-

-

4

3

4

3

4

3

-

-

-

6

2

2

4

2

5

-

-

-

0

5

0

5

0

5

-

-

-

0

3

5

4

0

6

-

-

-

8

8

8

-

-

-

0

1

8

6

-

-

-

0

1

0

1

0

1

-

-

-

0

1

0

1

0

1

Z

0

B

,

0

0

B

-

1

3

4

H

W

6

0

B

9

0

B

3

-

8

0

2

/

0

3

2

1

1

1

5

2

3

4

2

5

5

3

0

5

0

6

8

8

6

0

1

0

1

0

1

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

,

0

0

C

-

1

3

4

H

W

Z

0

C

6

0

C

9

0

C

3

-

0

6

4

1

1

1

4

1

2

2

6

2

0

2

5

2

0

3

2

1

0

1

0

1

2

1

0

1

0

1

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Z

0

A

,

0

0

A

-

1

9

4

H

W

5

0

A

8

0

A

0

1

A

1

-

8

0

2

/

0

3

2

1

2

r

o

1

2

r

o

1

2

r

o

1

0

4

6

6

2

8

2

9

0

6

0

7

0

9

0

0

1

8

4

4

3

0

1

8

8

8

-

-

-

0

4

0

4

0

4

-

-

-

6

2

2

4

2

5

-

-

-

0

5

0

5

0

5

-

-

-

0

3

5

4

0

6

-

-

-

8

8

8

-

-

-

0

1

8

6

-

-

-

0

1

0

1

0

1

-

-

-

0

1

0

1

0

1

Z

0

B

,

0

0

B

-

1

9

4

H

W

6

0

B

9

0

B

3

-

8

0

2

/

0

3

2

1

1

1

9

2

7

4

7

5

5

4

0

6

0

6

0

1

8

6

0

1

0

1

0

1

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

,

0

0

C

-

1

9

4

H

W

Z

0

C

6

0

C

9

0

C

3

-

0

6

4

1

1

1

6

1

4

2

9

2

0

2

0

3

0

3

2

1

0

1

0

1

2

1

0

1

0

1

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Содержание WH381

Страница 1: ...ED PACKAGE HEAT PUMPS Models WH381 WH431 WH491 INSTALLATION INSTRUCTIONS Manual 2100 342I Supersedes 2100 342H File Tab 17 Date 08 01 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Movi...

Страница 2: ...ns 22 Removal of Fan Shroud 22 Refrigerant Charge 22 Pressure Tables 24 Figures Figure 1 Unit Dimensions 5 Figure 2 Fresh Air Damper Assembly 8 Figure 3 Condensate Drains 8 Figure 4 Mounting Instructi...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning...

Страница 4: ...URE MODEL NUMBER CONTROL MODULES CAPACITY 38 3 Ton 43 3 Ton 49 4 ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 C 460 60 3 REVISIONS KW VENTILATION OPTIONS X Barometric Fresh Air Damper Standard B Blan...

Страница 5: ...p p u S n r u t e R W D H A B C B E F G I J K L M N O P Q R S T 1 8 3 H W 1 3 4 H W 1 9 4 H W 5 7 0 2 4 2 3 4 2 2 5 7 8 4 8 8 8 9 8 8 9 2 8 8 5 1 8 8 9 2 8 8 3 4 0 1 9 1 6 6 1 3 0 0 0 3 8 6 2 3 4 9 6...

Страница 6: ...S e r i W 2 d n u o r G e z i S e r i W T K C A T K C B T K C A T K C B T K C A T K C B T K C A T K C B Z 0 A 0 0 A 1 8 3 H W 5 0 A 8 0 A 0 1 A 1 8 0 2 0 3 2 1 2 r o 1 2 r o 1 2 r o 1 1 3 7 5 3 7 3 8...

Страница 7: ...ach unit The filter slides into position making it easy to service This filter can be serviced from the outside by removing the service door A 1 inch washable filter and a 2 inch pleated filter are al...

Страница 8: ...n open or vented type system to assure proper drainage FRESH AIR INTAKE All units are built with fresh air inlet slots punched in the service panel If the unit is equipped with a fresh air damper asse...

Страница 9: ...h clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 See Figures 4 and 4A for details WARNING Failur...

Страница 10: ...Manual 2100 342I Page 10 of 24 FIGURE 4 MOUNTING INSTRUCTIONS...

Страница 11: ...s is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mat...

Страница 12: ...Manual 2100 342I Page 12 of 24 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 4 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 13: ...Manual 2100 342I Page 13 of 24 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Страница 14: ...the compressor motor The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect To convert for the locking capability bend the tab locate in the bottom left...

Страница 15: ...zation of the heating Application Data and the heat loss calculation of the building are useful in determining the correct set points NOTE The additional LAB low ambient bypass relay is required to pr...

Страница 16: ...eration of the electric heat until outdoor temperatures have reached a certain design point This won t allow the electric heat to come on as second stage heating unless the outdoor temperature is belo...

Страница 17: ...ing See the Phase Monitor section later in this manual Verification of proper rotation must be made any time a compressor is changed or rewired If improper rotation is corrected at this time there wil...

Страница 18: ...ergizes the reversing valve solenoid constantly whenever the system switch on subbase is placed in Heat position the B terminal being constantly energized from R A thermostat demand for heat completes...

Страница 19: ...he defrost region By placing a jumper across the SEN JMP terminals a 1 4 inch QC terminal works best the defrost sensor mounted on the outdoor coil is shunted out and will activate the timing circuit...

Страница 20: ...g i h e h t f I t i u c r i c d e s o l c a s i o t n o d n a f f o r e w o p e l c y C t n e n o p m o c e v i t c e f e d e c a l p e R r o s s e r p m o c e h t t u o k c o l l l i w l o r t n o c...

Страница 21: ...0 6 4 0 7 4 0 8 4 0 9 4 0 0 5 5 8 9 6 5 4 8 2 5 5 0 4 6 3 5 1 5 0 2 5 4 1 5 0 5 8 2 0 9 4 0 9 5 7 4 0 0 2 6 4 5 5 8 4 4 4 5 5 3 4 5 9 2 2 4 7 7 0 1 4 8 9 8 9 3 7 5 7 8 3 2 5 6 7 3 3 8 5 6 3 8 4 5 5 3...

Страница 22: ...e d o M n o i s n e m i D A 1 8 3 H W 1 3 4 H W 1 9 4 H W 0 0 1 l e d o M 1 8 3 H W 1 3 4 H W 1 9 4 H W W K h g i H d e e p S d e M d e e p S w o L d e e p S h g i H d e e p S d e M d e e p S 5 0 A 3...

Страница 23: ...n I 2 O 1 8 3 H W 1 9 4 H W 1 3 4 H W d e e p S h g i H d e e p S m u i d e M d e e p S w o L d e e p S h g i H d e e p S m u i d e M y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i...

Страница 24: ...h g i H 7 7 3 0 2 7 7 8 1 2 7 7 4 3 2 8 7 0 5 2 9 7 7 6 2 0 8 5 8 2 2 8 4 0 3 4 8 4 2 3 6 8 4 4 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 0 8 0 1 2 0 8 6 2 2 0 8 2 4 2 1 8 9 5 2 2 8...

Отзывы: