background image

Manual 2100-342

I

Page

14 of 24

WIRING  –  MAIN POWER

Refer to the unit rating plate for wire sizing
information and maximum fuse or “HACR” type
circuit breaker size.  Each outdoor unit is marked
with a “Minimum Circuit Ampacity”.  This means
that the field wiring used must be sized to carry that
amount of current.  Depending on the installed KW
of electric heat, there may be two field power
circuits required.  If this is the case, the unit serial
plate will so indicate.  All models are suitable only
for connection with copper wire. Each unit and/or
wiring diagram will be marked “Use Copper
Conductors Only”.  These instructions 

must be

adhered to.  Refer to the National Electrical Code
(NEC) for complete current carrying capacity data
on the various insulation grades of wiring material.
All wiring must conform to NEC and all local
codes.

The electrical data lists fuse and wire sizes (75° C
copper) for all models including the most commonly
used heater sizes.  Also shown are the number of
field power circuits required for the various models
with heaters.

The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or “HACR” type circuit breaker that is
to be used with the equipment.  The correct size
must be used for proper circuit protection and also
to assure that there will be no nuisance tripping due
to the momentary high starting current of the
compressor motor.

The disconnect access door on this unit may be
locked to prevent unauthorized access to the
disconnect.  To convert for the locking capability,
bend the tab locate in the bottom left hand corner of
the disconnect opening under the disconnect access
panel straight out.  This tab will now line up with
the slot in the door.  When shut, a padlock may be
placed through the hole in the tab preventing entry.

See “Start Up” section for important information on
three phase scroll compressor start ups.

NOTE: The voltage should be measured at the field

power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).

Ten (10) wires should be run from thermostat subbase to
the 24V terminal board in the unit.  A nine conductor,
18 gauge copper color-coded thermostat cable is
recommended.  The connection points are shown in
Figure 8.

WIRING  –  LOW VOLTAGE WIRING

230 / 208V, 1 phase and 3 phase equipment dual
primary voltage transformers.  All equipment leaves the
factory wired on 240V tap.  For 208V operation,
reconnect from 240V to 208V tap.  The acceptable
operating voltage range for the 240 and 208V taps are:

TAP

RANGE

240

253 – 216

208

220 – 187

IMPORTANT

Only the thermostats shown in this Manual
have been tested with this equipment for
proper operation.  Proper unit operation with
thermostats not listed in this Manual, cannot
be assured.

You assume responsibility for proper
operation of the unit when using thermostats
other than those listed above.

FIGURE  8

UNIT 24V TERMINAL BOARD

Содержание WH381

Страница 1: ...ED PACKAGE HEAT PUMPS Models WH381 WH431 WH491 INSTALLATION INSTRUCTIONS Manual 2100 342I Supersedes 2100 342H File Tab 17 Date 08 01 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Movi...

Страница 2: ...ns 22 Removal of Fan Shroud 22 Refrigerant Charge 22 Pressure Tables 24 Figures Figure 1 Unit Dimensions 5 Figure 2 Fresh Air Damper Assembly 8 Figure 3 Condensate Drains 8 Figure 4 Mounting Instructi...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning...

Страница 4: ...URE MODEL NUMBER CONTROL MODULES CAPACITY 38 3 Ton 43 3 Ton 49 4 ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 C 460 60 3 REVISIONS KW VENTILATION OPTIONS X Barometric Fresh Air Damper Standard B Blan...

Страница 5: ...p p u S n r u t e R W D H A B C B E F G I J K L M N O P Q R S T 1 8 3 H W 1 3 4 H W 1 9 4 H W 5 7 0 2 4 2 3 4 2 2 5 7 8 4 8 8 8 9 8 8 9 2 8 8 5 1 8 8 9 2 8 8 3 4 0 1 9 1 6 6 1 3 0 0 0 3 8 6 2 3 4 9 6...

Страница 6: ...S e r i W 2 d n u o r G e z i S e r i W T K C A T K C B T K C A T K C B T K C A T K C B T K C A T K C B Z 0 A 0 0 A 1 8 3 H W 5 0 A 8 0 A 0 1 A 1 8 0 2 0 3 2 1 2 r o 1 2 r o 1 2 r o 1 1 3 7 5 3 7 3 8...

Страница 7: ...ach unit The filter slides into position making it easy to service This filter can be serviced from the outside by removing the service door A 1 inch washable filter and a 2 inch pleated filter are al...

Страница 8: ...n open or vented type system to assure proper drainage FRESH AIR INTAKE All units are built with fresh air inlet slots punched in the service panel If the unit is equipped with a fresh air damper asse...

Страница 9: ...h clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 See Figures 4 and 4A for details WARNING Failur...

Страница 10: ...Manual 2100 342I Page 10 of 24 FIGURE 4 MOUNTING INSTRUCTIONS...

Страница 11: ...s is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mat...

Страница 12: ...Manual 2100 342I Page 12 of 24 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 4 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 13: ...Manual 2100 342I Page 13 of 24 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Страница 14: ...the compressor motor The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect To convert for the locking capability bend the tab locate in the bottom left...

Страница 15: ...zation of the heating Application Data and the heat loss calculation of the building are useful in determining the correct set points NOTE The additional LAB low ambient bypass relay is required to pr...

Страница 16: ...eration of the electric heat until outdoor temperatures have reached a certain design point This won t allow the electric heat to come on as second stage heating unless the outdoor temperature is belo...

Страница 17: ...ing See the Phase Monitor section later in this manual Verification of proper rotation must be made any time a compressor is changed or rewired If improper rotation is corrected at this time there wil...

Страница 18: ...ergizes the reversing valve solenoid constantly whenever the system switch on subbase is placed in Heat position the B terminal being constantly energized from R A thermostat demand for heat completes...

Страница 19: ...he defrost region By placing a jumper across the SEN JMP terminals a 1 4 inch QC terminal works best the defrost sensor mounted on the outdoor coil is shunted out and will activate the timing circuit...

Страница 20: ...g i h e h t f I t i u c r i c d e s o l c a s i o t n o d n a f f o r e w o p e l c y C t n e n o p m o c e v i t c e f e d e c a l p e R r o s s e r p m o c e h t t u o k c o l l l i w l o r t n o c...

Страница 21: ...0 6 4 0 7 4 0 8 4 0 9 4 0 0 5 5 8 9 6 5 4 8 2 5 5 0 4 6 3 5 1 5 0 2 5 4 1 5 0 5 8 2 0 9 4 0 9 5 7 4 0 0 2 6 4 5 5 8 4 4 4 5 5 3 4 5 9 2 2 4 7 7 0 1 4 8 9 8 9 3 7 5 7 8 3 2 5 6 7 3 3 8 5 6 3 8 4 5 5 3...

Страница 22: ...e d o M n o i s n e m i D A 1 8 3 H W 1 3 4 H W 1 9 4 H W 0 0 1 l e d o M 1 8 3 H W 1 3 4 H W 1 9 4 H W W K h g i H d e e p S d e M d e e p S w o L d e e p S h g i H d e e p S d e M d e e p S 5 0 A 3...

Страница 23: ...n I 2 O 1 8 3 H W 1 9 4 H W 1 3 4 H W d e e p S h g i H d e e p S m u i d e M d e e p S w o L d e e p S h g i H d e e p S m u i d e M y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i...

Страница 24: ...h g i H 7 7 3 0 2 7 7 8 1 2 7 7 4 3 2 8 7 0 5 2 9 7 7 6 2 0 8 5 8 2 2 8 4 0 3 4 8 4 2 3 6 8 4 4 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 0 8 0 1 2 0 8 6 2 2 0 8 2 4 2 1 8 9 5 2 2 8...

Отзывы: