CHECKING TEMPERATURE SENSOR OUTSIDE
UNIT CIRCUIT

1. Disconnect temperature sensor from board and

from outdoor coil.

2. Use an ohmmeter and measure the resistance of the

sensor.  Also use ohmmeter to check for short or
open.

3. Check resistance reading to chart of resistance use

sensor ambient temperature.  (Tolerance of part is
± 10%)

4. If sensor resistance reads very low, then sensor is

shorted and will not allow proper operation of the
heat pump control.

5. If sensor is out of tolerance, shorted, open, or reads

very low ohms then it should be replaced.

     F

        R

     F

        R

     F

             R

-25.0

-24.0

-23.0

-22.0

-21.0

-20.0

-19.0

-18.0

-17.0

-16.0

-15.0

-14.0

-13.0

-12.0

-11.0

-10.0

-9.0

-8.0

-7.0

-6.0

-5.0

-4.0

-3.0

-2.0

-1.0

0.0

1.0

2.0

3.0

4.0

5.0

6.0

7.0

8.0

9.0

10.0

11.0

12.0

13.0

14.0

15.0

16.0

17.0

18.0

19.0

20.0

21.0

22.0

23.0

24.0

196871

190099

183585

177318

171289

165487

159904

154529

149355

144374

139576

134956

130506

126219

122089

118108

114272

110575

107010

103574

100260

97064

93981

91008

88139

85371

82699

80121

77632

75230

72910

70670

68507

66418

64399

62449

60565

58745

56985

55284

53640

52051

50514

49028

47590

46200

44855

43554

42295

41077

25.0

26.0

27.0

28.0

29.0

30.0

31.0

32.0

33.0

34.0

35.0

36.0

37.0

38.0

39.0

40.0

41.0

42.0

43.0

44.0

45.0

46.0

47.0

48.0

49.0

50.0

51.0

52.0

53.0

54.0

55.0

56.0

57.0

58.0

59.0

60.0

61.0

62.0

63.0

64.0

65.0

66.0

67.0

68.0

69.0

70.0

71.0

72.0

73.0

74.0

39898

38757

37652

36583

35548

34545

33574

32634

31723

30840

29986

29157

28355

27577

26823

26092

25383

24696

24030

23384

22758

22150

21561

20989

20435

19896

19374

18867

18375

17898

17434

16984

16547

16122

15710

15310

14921

14544

14177

13820

13474

13137

12810

12492

12183

11883

11591

11307

11031

10762

75.0

76.0

77.0

78.0

79.0

80.0

81.0

82.0

83.0

84.0

85.0

86.0

87.0

88.0

89.0

90.0

91.0

92.0

93.0

94.0

95.0

96.0

97.0

98.0

99.0

100.0

101.0

102.0

103.0

104.0

105.0

106.0

107.0

108.0

109.0

110.0

111.0

112.0

113.0

114.0

115.0

116.0

117.0

118.0

119.0

120.0

121.0

122.0

123.0

124.0

10501

10247

10000

9760

9526

9299

9077

8862

8653

8449

8250

8057

7869

7686

7507

7334

7165

7000

6840

6683

6531

6383

6239

6098

5961

5827

5697

5570

5446

5326

5208

5094

4982

4873

4767

4663

4562

4464

4367

4274

4182

4093

4006

3921

3838

3757

3678

3601

3526

3452

TEMPERATURE F VS RESISTANCE R OF TEMPERATURE

Содержание WH262

Страница 1: ...LLATION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMPS Models WH262 WH311 Manual 2100 350D Supersedes 2100 350C File Volume III Tab 17 Date 09 26 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since...

Страница 2: ...an Blade Setting Dimensions 22 Removal of Fan Shroud 22 Refrigerant Charge 22 Pressure Tables 23 Optional Accessories 24 Figures Figure 1 Unit Dimensions 5 Figure 2 Fresh Air Damper Assembly 8 Figure...

Страница 3: ...r Air Conditioning Manual N Low Pressure Low Velocity ACCA Manual D or Duct System Design for Winter Manual Q and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditi...

Страница 4: ...al Room Ventilator Motorized with Exhaust E Economizer Internal Fully Modulating with Exhaust R Energy Recovery Ventilator Motorized with Exhaust COIL OPTIONS X Standard 1 Phenolic Coated Evaporator 2...

Страница 5: ...Manual 2100 350D Page 5 of 24 FIGURE 1 UNIT DIMENSIONS...

Страница 6: ...A N A N Z 0 C 2 6 2 H W 3 0 6 4 1 0 1 5 1 4 1 4 1 A N A N A N A N A N A N A N A N Z 0 A 1 1 3 H W 1 8 0 2 0 3 2 1 6 2 0 4 0 1 0 1 A N A N A N A N A N A N A N A N Z 0 B 1 1 3 H W 3 8 0 2 0 3 2 1 0 2 5...

Страница 7: ...irflow requirement of the equipment Air Conditioning Contractors of America ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properl...

Страница 8: ...s required for Department of Energy Energyguide Fact Sheets is based upon the fresh air blank off plate in place and is recommended for maximum energy efficiency FIGURE 2 BLOWER DAMPER ASSEMBLY The bl...

Страница 9: ...ustible material The supply air opening would then be 30 x 12 See Figures 3 and 4 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location See Figure 4 4 Mount bottom moun...

Страница 10: ...Manual 2100 350D Page 10 of 24 FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 11: ...tween the supply air duct and combustible materials This is required for the first three 3 feet of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to...

Страница 12: ...Manual 2100 350D Page 12 of 24 FIGURE 5 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 13: ...Manual 2100 350D Page 13 of 24 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Страница 14: ...locked to prevent unauthorized access to the disconnect To convert for the locking capability bend the tab located in the bottom left hand corner of the disconnect opening under the disconnect access...

Страница 15: ...eat loss calculation of the building are useful in determining the correct set points OPTIONAL COMPRESSOR CUTOFF THERMOSTAT See Figures 9 and 10 Heat pump compressor operation at outdoor temperatures...

Страница 16: ...night set back condition or someone increasing the thermostat set point NOTE Some programmable thermostats do have a built in time delay for pulling in second stage heat when coming off set back condi...

Страница 17: ...iminating pressure equalization noise except during defrost are to be used IMPORTANT INSTALLER NOTE For improved start up performance wash the indoor coil with a dishwashing detergent HIGH PRESSURE SW...

Страница 18: ...st control board has an option of 30 60 or 90 minute setting All models are shipped from the factory on the 60 minute pin If special circumstances require a change to another time remove the wire from...

Страница 19: ...Manual 2100 350D Page 19 of 24 FIGURE 13 DEFROST CONTROL BOARD...

Страница 20: ...g i h e h t f I t i u c r i c d e s o l c a s i o t n o d n a f f o r e w o p e l c y C t n e n o p m o c e v i t c e f e d e c a l p e R r o s s e r p m o c e h t t u o k c o l l l i w l o r t n o c...

Страница 21: ...507 66418 64399 62449 60565 58745 56985 55284 53640 52051 50514 49028 47590 46200 44855 43554 42295 41077 25 0 26 0 27 0 28 0 29 0 30 0 31 0 32 0 33 0 34 0 35 0 36 0 37 0 38 0 39 0 40 0 41 0 42 0 43 0...

Страница 22: ...able 7 for proper subcooling levels for evaluation of proper charge G N I L O O C G N I T A E H l e d o M d e t a R w o l f r i A D O 5 9 e r u t a r e p m e T D O 2 8 e r u t a r e p m e T D O 7 4 e...

Страница 23: ...9 8 8 3 2 0 9 4 5 2 1 9 1 7 2 2 9 0 9 2 4 9 9 0 3 5 9 1 3 3 1 1 3 H W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 3 7 0 9 1 4 7 5 0 2 5 7 0 2 2 6 7 7 3 2 7 7 4 5 2 8 7 2 7 2 8 7 1 9 2 9...

Страница 24: ...X X 3 D A F M r e p m a D r i A h s e r F d e z i r o t o M X X X X X X A 3 A V R E W A 3 C V R E W r o t a l i t n e V y r e v o c e R y g r e n E r o t a l i t n e V y r e v o c e R y g r e n E X X...

Отзывы: