background image

Manual 2100-350D
Page

18 of 24

On “Auto” option a circuit is completed from R-W1 and
R-Y on each heating “on” cycle, energizing reversing
valve solenoid and pulling in compressor contactor
starting compressor and outdoor motor.  R-G also make
starting indoor blower motor.  Heat pump heating cycle
now in operation.  The second option has no “Auto”
changeover position, but instead energizes the reversing
valve solenoid constantly whenever the system switch
on subbase is placed in “Heat” position, the “B”
terminal being constantly energized from R.  A
thermostat demand for heat completes R-Y circuit,
pulling in compressor contactor starting compressor and
outdoor motor.  R-G also make starting indoor blower
motor.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed.  Pressure tables can be found later in the
manual covering all models on both cooling and heating
cycles.  It is imperative to match the correct pressure
table to the unit by model number.

DEFROST CYCLE

The defrost cycle is controlled by temperature and time
on the solid state heat pump control.  See Figure 13.

When the outdoor temperature is in the lower 40°F
temperature range or colder, the outdoor coil
temperature is 32°F or below.  This coil temperature is
sensed by the coil temperature sensor mounted near the
bottom of the outdoor coil.  Once coil temperature
reaches 30°F or below, the coil temperature sensor
sends a signal to the control logic of the heat pump
control and the defrost timer will start.

After 60 minutes at 30°F or below, the heat pump
control will place the system in the defrost mode.

During the defrost mode, the refrigerant cycle switches
back to the cooling cycle, the outdoor motor stops,
electric heaters are energized, and hot gas passing
through the outdoor coil melts any accumulated frost.
When the temperature rises to approximately 57°F, the
coil temperature sensor will send a signal to the heat
pump control which will return the system to heating
operations automatically.

If some abnormal or temporary condition such as a high
wind causes the heat pump to have a prolonged defrost
cycle, the heat pump control will restore the system to
heating operation automatically after 10 minutes.

The heat pump defrost control board has an option of
30, 60 or 90-minute setting.  All models are shipped
from the factory on the 60-minute pin.  If special
circumstances require a change to another time, remove
the wire from the 60-minute terminal and reconnect to
the desired terminal.  The manufacturer's
recommendation is for 60-minute defrost cycles.  Refer
to Figure 13.

There is a cycle speed up jumper on the control.  This
can be used to reduce the time between defrost cycle
operation without waiting for time to elapse.

Use a small screwdriver or other metallic object, or
another 1/4 inch QC, to short between the 

SPEEDUP

terminals to accelerate the HPC timer and initiate
defrost.

Be careful not to touch any other terminals with the
instrument used to short the 

SPEEDUP

 terminals.  It

may take up to 10 seconds with the 

SPEEDUP

terminals shorted for the speedup to be completed and
the defrost cycle to start.

As soon as the defrost cycle kicks in remove the
shorting instrument from the SPEEDUP terminals.

Otherwise the timing will remain accelerated and run
through the 1-minute minimum defrost length sequence
in a matter of seconds and will automatically terminate
the defrost sequence.

There is an initiate defrost jumper (sen jump) on the
control that can be used at any outdoor ambient during
the heating cycle to simulate a 0° coil temperature.
This can be used to check defrost operation of the unit
without waiting for the outdoor ambient to fall into the
defrost region.

By placing a jumper across the 

SEN JMP

 terminals (a

1/4 inch QC terminal works best) the defrost sensor
mounted on the outdoor coil is shunted out and will
activate the timing circuit.  This permits the defrost
cycle to be checked out in warmer weather conditions
without the outdoor temperature having to fall into the
defrost region.

In order to terminate the defrost test the 

SEN JMP

jumper must be removed.  If left in place too long the
compressor could stop due to the high pressure control
opening because of  high pressure condition created by
operating in the cooling mode with outdoor fan off.
Pressure will rise fairly fast as there is likely no actual
frost on the outdoor coil in this artificial test condition.

There is also a 5-minute compressor time delay function
built into the HPC.  This is to protect the compressor from
short cycling conditions.  In some instances it is helpful to
the service technician to override or speed up this timing
period, and shorting out the 

SPEEDUP

 terminals for a few

seconds can do this.

Содержание WH262

Страница 1: ...LLATION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMPS Models WH262 WH311 Manual 2100 350D Supersedes 2100 350C File Volume III Tab 17 Date 09 26 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since...

Страница 2: ...an Blade Setting Dimensions 22 Removal of Fan Shroud 22 Refrigerant Charge 22 Pressure Tables 23 Optional Accessories 24 Figures Figure 1 Unit Dimensions 5 Figure 2 Fresh Air Damper Assembly 8 Figure...

Страница 3: ...r Air Conditioning Manual N Low Pressure Low Velocity ACCA Manual D or Duct System Design for Winter Manual Q and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditi...

Страница 4: ...al Room Ventilator Motorized with Exhaust E Economizer Internal Fully Modulating with Exhaust R Energy Recovery Ventilator Motorized with Exhaust COIL OPTIONS X Standard 1 Phenolic Coated Evaporator 2...

Страница 5: ...Manual 2100 350D Page 5 of 24 FIGURE 1 UNIT DIMENSIONS...

Страница 6: ...A N A N Z 0 C 2 6 2 H W 3 0 6 4 1 0 1 5 1 4 1 4 1 A N A N A N A N A N A N A N A N Z 0 A 1 1 3 H W 1 8 0 2 0 3 2 1 6 2 0 4 0 1 0 1 A N A N A N A N A N A N A N A N Z 0 B 1 1 3 H W 3 8 0 2 0 3 2 1 0 2 5...

Страница 7: ...irflow requirement of the equipment Air Conditioning Contractors of America ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properl...

Страница 8: ...s required for Department of Energy Energyguide Fact Sheets is based upon the fresh air blank off plate in place and is recommended for maximum energy efficiency FIGURE 2 BLOWER DAMPER ASSEMBLY The bl...

Страница 9: ...ustible material The supply air opening would then be 30 x 12 See Figures 3 and 4 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location See Figure 4 4 Mount bottom moun...

Страница 10: ...Manual 2100 350D Page 10 of 24 FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 11: ...tween the supply air duct and combustible materials This is required for the first three 3 feet of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to...

Страница 12: ...Manual 2100 350D Page 12 of 24 FIGURE 5 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 13: ...Manual 2100 350D Page 13 of 24 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Страница 14: ...locked to prevent unauthorized access to the disconnect To convert for the locking capability bend the tab located in the bottom left hand corner of the disconnect opening under the disconnect access...

Страница 15: ...eat loss calculation of the building are useful in determining the correct set points OPTIONAL COMPRESSOR CUTOFF THERMOSTAT See Figures 9 and 10 Heat pump compressor operation at outdoor temperatures...

Страница 16: ...night set back condition or someone increasing the thermostat set point NOTE Some programmable thermostats do have a built in time delay for pulling in second stage heat when coming off set back condi...

Страница 17: ...iminating pressure equalization noise except during defrost are to be used IMPORTANT INSTALLER NOTE For improved start up performance wash the indoor coil with a dishwashing detergent HIGH PRESSURE SW...

Страница 18: ...st control board has an option of 30 60 or 90 minute setting All models are shipped from the factory on the 60 minute pin If special circumstances require a change to another time remove the wire from...

Страница 19: ...Manual 2100 350D Page 19 of 24 FIGURE 13 DEFROST CONTROL BOARD...

Страница 20: ...g i h e h t f I t i u c r i c d e s o l c a s i o t n o d n a f f o r e w o p e l c y C t n e n o p m o c e v i t c e f e d e c a l p e R r o s s e r p m o c e h t t u o k c o l l l i w l o r t n o c...

Страница 21: ...507 66418 64399 62449 60565 58745 56985 55284 53640 52051 50514 49028 47590 46200 44855 43554 42295 41077 25 0 26 0 27 0 28 0 29 0 30 0 31 0 32 0 33 0 34 0 35 0 36 0 37 0 38 0 39 0 40 0 41 0 42 0 43 0...

Страница 22: ...able 7 for proper subcooling levels for evaluation of proper charge G N I L O O C G N I T A E H l e d o M d e t a R w o l f r i A D O 5 9 e r u t a r e p m e T D O 2 8 e r u t a r e p m e T D O 7 4 e...

Страница 23: ...9 8 8 3 2 0 9 4 5 2 1 9 1 7 2 2 9 0 9 2 4 9 9 0 3 5 9 1 3 3 1 1 3 H W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 3 7 0 9 1 4 7 5 0 2 5 7 0 2 2 6 7 7 3 2 7 7 4 5 2 8 7 2 7 2 8 7 1 9 2 9...

Страница 24: ...X X 3 D A F M r e p m a D r i A h s e r F d e z i r o t o M X X X X X X A 3 A V R E W A 3 C V R E W r o t a l i t n e V y r e v o c e R y g r e n E r o t a l i t n e V y r e v o c e R y g r e n E X X...

Отзывы: