Bard WH183 Скачать руководство пользователя страница 8

Manual    2100-373
Page        6

INSTALLATION  INSTRUCTIONS

WALL MOUNTING INFORMATION

1. These units are secured by wall mounting brackets

which secure the unit to the outside wall surface at
both sides.  A bottom mounting bracket is provided
for ease of installation, but is not required.

2. On wood frame walls, the wall construction must be

strong and rigid enough to carry the weight of the
unit without transmitting any unit vibration.

3. Concrete block walls must be thoroughly inspected

to insure that they are capable of carrying the weight
of the unit being installed.

4. The unit is suitable for 0 inch clearance from the

unit, and from the supply and return air ducts.

MOUNTING THE UNIT

1. Two holes for the supply and return air openings

must be cut through the wall as shown in Figure 3.

2. Locate and mark lag bolt locations and bottom

mounting bracket location, if desired.  See Figure 3.

3. Mount bottom mounting bracket, if used.

4. Hook top rain flashing under back bend of top.  Top

rain flashing is shipped secured to the right side of
the back.

5. Position unit in opening and secure with 5/16 lag

bolts.  Use 5/16” diameter flat washers on the lag
bolts.

6. Secure rain flashing to wall and caulk across entire

length of top.  See Figure 3.

7. For additional mounting rigidity, the return air and

supply air frames or collars can be drilled and
screwed or welded to the structural wall itself
(depending upon wall construction).  Be sure to
observe required clearance if combustible wall.

8. On side by side installations, maintain a minimum

of 20 inches clearance on right side of unit to allow
access to control panel and heaters, and to allow
proper airflow to the outdoor coil.  Additional
clearance may be required to meet local or national
codes.

Содержание WH183

Страница 1: ...T PUMP Models WH183 WH242 INSTALLATION INSTRUCTIONS Manual 2100 373A Supersedes 2100 373 File Volume III Tab 17 Date 05 13 02 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just a...

Страница 2: ...11 Figure 9 Start Up Procedure Decal 13 Figure 10 Defrost Control Board 14 Figure 11 Fan Blade Setting 17 Figure 12 Compressor Burnout Cleanup Procedure 13 Start Up 13 Important Installer Note 13 Cra...

Страница 3: ...and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Co...

Страница 4: ...ng inspection by the carrier s agent GENERAL The equipment covered in this manual is to be installed by trained experienced service and installation technicians The refrigerant system is completely as...

Страница 5: ...Manual 2100 373 Page 3 FIGURE 1 UNIT DIMENSIONS MIS 992...

Страница 6: ...ntion to note 89 of table 310 regarding Ampacity Adjustment Factors when more than 3 are in a raceway T I U C R I C E L G N I S l e d o M d e t a R s t l o V d n a e s a h P d l e i F o N r e w o P s...

Страница 7: ...wn to the unit base There are openings in the unit base for the drain hose to pass through In the event the drain hose is connected to a drain system of some type it must be an open or vented type sys...

Страница 8: ...shown in Figure 3 2 Locate and mark lag bolt locations and bottom mounting bracket location if desired See Figure 3 3 Mount bottom mounting bracket if used 4 Hook top rain flashing under back bend of...

Страница 9: ...Manual 2100 373 Page 7 FIGURE 3 MOUNTINGINSTRUCTIONS MIS 353...

Страница 10: ...Manual 2100 373 Page 8 FIGURE 5 WALLMOUNTINGINSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS MIS 548 MIS 549 FIGURE 4 WALLMOUNTINGINSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 11: ...Manual 2100 373 Page 9 FIGURE 6 COMMONWALLMOUNTINGINSTALLATIONS MIS 550...

Страница 12: ...ly used heater sizes Also shown are the number of field power circuits required for the various models with heaters IMPORTANT NOTE Only the thermostat and subbase combinations as shown in Figure 7 wil...

Страница 13: ...e Figure 8 for compressor cutoff and outdoor thermostat wiring MIS 409 FIGURE 8 COMPRESSOR CUTOFF AND OUTDOOR THERMOSTAT WIRING 4 8 KW 1 Phase 6 KW 3 Phase TABLE 3 THERMOSTATWIRESIZE r e m r o f s n a...

Страница 14: ...d pressure etc that will prevent compressor from operating will cause green lamp to activate This is a signal to the operator of the equipment to place system in emergency heat position TABLE 4 WALLTH...

Страница 15: ...r The G indoor motor circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation IMPORTANT THESE PROCEDURES MU...

Страница 16: ...umper on the control This can be used to reduce the time between defrost cycle operation without waiting for time to elapse Use a small screwdr4iver or other metallic object or another 1 4 inch QC to...

Страница 17: ...g n i t a r r o t i c a p a c k c e h C d e t r o h s r o n e p o r o f k c e h C r o t i c a p a c r o t i c a p a c e c a l p e R l o r t n o c p m u p t a e H e v i t c e f e d n o y a l e r n a f...

Страница 18: ...17434 16984 16547 16122 15710 15310 14921 14544 14177 13820 13474 13137 12810 12492 12183 11883 11591 11307 11031 10762 75 0 76 0 77 0 78 0 79 0 80 0 81 0 82 0 83 0 84 0 85 0 86 0 87 0 88 0 89 0 90 0...

Страница 19: ...6 from compressor as shown in Table 7 The suction line temperatures in Table 7 are based upon 80 F dry bulb 67 F wet bulb 50 R H temperature and rated airflow across the evaporator during cooling cycl...

Страница 20: ...0 1 1 2 3 2 0 1 7 3 3 2 4 2 H W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 5 7 6 1 2 6 7 9 2 2 7 7 2 4 2 9 7 6 5 2 0 8 1 7 2 1 8 6 8 2 3 8 2 0 3 4 8 8 1 3 6 8 6 3 3 B D g e d 0 8 B W g...

Страница 21: ...t o M t s u a h x E h t i w r o t a l i t n e V m o o r s s a l C t s u a h x E h t i w r e z i m o n o c E r o t a l i t n e V y r e v o c e R y g r e n E X X X X X X X X X X X X X X X X X X X X X X...

Отзывы: