Bard WH183 Скачать руководство пользователя страница 6

Manual    2100-373
Page        4

Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA).  The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association
for the Installation of Air Conditioning and Ventilating
systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B. Where local
regulations are at a variance with instructions, installer
should adhere to local codes.

DUCT WORK

Any heat pump is more critical of proper operating
charge and an adequate duct system that a straight air
conditioning unit.  All duct work, supply and return,
must be properly sized for the design air flow
requirement of the equipment.  Air Conditioning
Contractors of America (ACCA) is an excellent guide

Q

R

S

T

Maximum size of the time delay fuse or HACR type circuit breaker for protection
of field wiring conductors.

Based on 75° C copper wire.  All wiring must conform to NEC and all local
codes.

Maximum KW that can operate with heat pump on.

These “Minimum Circuit Ampacity” values are to be used for sizing the field
power conductors.  Refer to the National Electric Code (latest revision), article
310, for power conductor sizing.    CAUTION:  When more than one field
power conductor circuit is run through one conduit the conductors must be
derated.  Pay special attention to note 89 of table 310 regarding Ampacity
Adjustment Factors when more than 3 are in a raceway.

T

I

U

C

R

I

C

E

L

G

N

I

S

l

e

d

o

M

d

e

t

a

R

s

t

l

o

V

d

n

a

e

s

a

h

P

d

l

e

i

F

.

o

N

r

e

w

o

P

s

t

i

u

c

r

i

C

m

m

u

m

i

n

i

M

t

i

u

c

r

i

C

y

t

i

c

a

p

m

A

j

m

u

m

i

x

a

M

l

a

n

r

e

t

x

E

r

o

e

s

u

F

t

i

u

c

r

i

C

r

e

k

a

e

r

B

k

d

l

e

i

F

r

e

w

o

P

e

z

i

S

e

r

i

W

k

d

n

u

o

r

G

e

z

i

S

e

r

i

W

Z

0

A

,

0

0

A

-

3

8

1

H

W

4

0

A

l

8

0

A

1

-

8

0

2

/

0

3

2

1
1
1

7

1

8

3

9

5

5

2

0

4

0

6

2

1

0

1

6

2

1

0

1

0

1

Z

0

A

,

0

0

A

-

2

4

2

H

W

4

0

A

l

8

0

A

1

-

8

0

2

/

0

3

2

1
1
1

8

1

9

3

0

6

5

2

0

4

0

6

2

1

0

1

6

2

1

0

1

0

1

Z

0

B

,

0

0

B

-

2

4

2

H

W

6

0

B

1

-

8

0

2

/

0

3

2

1
1

5

1

3

3

0

2

5

3

2

1

8

2

1

0

1

Z

0

C

,

0

0

C

-

2

4

2

H

W

6

0

C

3

-

0

6

4

1
1

8

7

1

5

1

0

2

4

1

2

1

4

1

2

1

TABLE  2

ELECTRICAL SPECIFICATIONS

to proper sizing.  All duct work or portions thereof not
in the conditioned space should be properly insulated in
order to both conserve energy and prevent condensation
or moisture damage.

Refer to Table 10 for maximum static pressure
available for duct design.

Design the duct work according to methods given by the
Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one inch of insulation.
Use insulation with a vapor barrier on the outside of the
insulation.  Flexible joints should be used to connect the
duct work to the equipment in order to keep the noise
transmission to a minimum.

A 1/4 inch clearance to combustible material for the
first three feet of duct attached to the outlet air frame is
required.  See Pages Wall Mounting Instructions and
Figure 3 for further details.

Содержание WH183

Страница 1: ...T PUMP Models WH183 WH242 INSTALLATION INSTRUCTIONS Manual 2100 373A Supersedes 2100 373 File Volume III Tab 17 Date 05 13 02 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just a...

Страница 2: ...11 Figure 9 Start Up Procedure Decal 13 Figure 10 Defrost Control Board 14 Figure 11 Fan Blade Setting 17 Figure 12 Compressor Burnout Cleanup Procedure 13 Start Up 13 Important Installer Note 13 Cra...

Страница 3: ...and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Co...

Страница 4: ...ng inspection by the carrier s agent GENERAL The equipment covered in this manual is to be installed by trained experienced service and installation technicians The refrigerant system is completely as...

Страница 5: ...Manual 2100 373 Page 3 FIGURE 1 UNIT DIMENSIONS MIS 992...

Страница 6: ...ntion to note 89 of table 310 regarding Ampacity Adjustment Factors when more than 3 are in a raceway T I U C R I C E L G N I S l e d o M d e t a R s t l o V d n a e s a h P d l e i F o N r e w o P s...

Страница 7: ...wn to the unit base There are openings in the unit base for the drain hose to pass through In the event the drain hose is connected to a drain system of some type it must be an open or vented type sys...

Страница 8: ...shown in Figure 3 2 Locate and mark lag bolt locations and bottom mounting bracket location if desired See Figure 3 3 Mount bottom mounting bracket if used 4 Hook top rain flashing under back bend of...

Страница 9: ...Manual 2100 373 Page 7 FIGURE 3 MOUNTINGINSTRUCTIONS MIS 353...

Страница 10: ...Manual 2100 373 Page 8 FIGURE 5 WALLMOUNTINGINSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS MIS 548 MIS 549 FIGURE 4 WALLMOUNTINGINSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 11: ...Manual 2100 373 Page 9 FIGURE 6 COMMONWALLMOUNTINGINSTALLATIONS MIS 550...

Страница 12: ...ly used heater sizes Also shown are the number of field power circuits required for the various models with heaters IMPORTANT NOTE Only the thermostat and subbase combinations as shown in Figure 7 wil...

Страница 13: ...e Figure 8 for compressor cutoff and outdoor thermostat wiring MIS 409 FIGURE 8 COMPRESSOR CUTOFF AND OUTDOOR THERMOSTAT WIRING 4 8 KW 1 Phase 6 KW 3 Phase TABLE 3 THERMOSTATWIRESIZE r e m r o f s n a...

Страница 14: ...d pressure etc that will prevent compressor from operating will cause green lamp to activate This is a signal to the operator of the equipment to place system in emergency heat position TABLE 4 WALLTH...

Страница 15: ...r The G indoor motor circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation IMPORTANT THESE PROCEDURES MU...

Страница 16: ...umper on the control This can be used to reduce the time between defrost cycle operation without waiting for time to elapse Use a small screwdr4iver or other metallic object or another 1 4 inch QC to...

Страница 17: ...g n i t a r r o t i c a p a c k c e h C d e t r o h s r o n e p o r o f k c e h C r o t i c a p a c r o t i c a p a c e c a l p e R l o r t n o c p m u p t a e H e v i t c e f e d n o y a l e r n a f...

Страница 18: ...17434 16984 16547 16122 15710 15310 14921 14544 14177 13820 13474 13137 12810 12492 12183 11883 11591 11307 11031 10762 75 0 76 0 77 0 78 0 79 0 80 0 81 0 82 0 83 0 84 0 85 0 86 0 87 0 88 0 89 0 90 0...

Страница 19: ...6 from compressor as shown in Table 7 The suction line temperatures in Table 7 are based upon 80 F dry bulb 67 F wet bulb 50 R H temperature and rated airflow across the evaporator during cooling cycl...

Страница 20: ...0 1 1 2 3 2 0 1 7 3 3 2 4 2 H W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 5 7 6 1 2 6 7 9 2 2 7 7 2 4 2 9 7 6 5 2 0 8 1 7 2 1 8 6 8 2 3 8 2 0 3 4 8 8 1 3 6 8 6 3 3 B D g e d 0 8 B W g...

Страница 21: ...t o M t s u a h x E h t i w r o t a l i t n e V m o o r s s a l C t s u a h x E h t i w r e z i m o n o c E r o t a l i t n e V y r e v o c e R y g r e n E X X X X X X X X X X X X X X X X X X X X X X...

Отзывы: