background image

Manual 2100-495A
Page

3 of 21

MODEL NOMENCLATURE LEGEND

NOTE: Never set intake blower at a lower speed than

the exhaust blower, as it will create a
negative pressure in the room.

During operation below 5 degrees F outdoor
temperature, freezing of moisture in the heat
transfer wheel can occur.  Consult the factory
if this possibility exists.

GENERAL INFORMATION

The ventilator should only be installed by a trained
heating and air conditioning technician.  These
instructions serve as a guide to the technician installing
the ventilator package.  They are not intended as a step-
by-step procedure with which the mechanically-inclined
owner can install the package.

The ventilator housing is shipped in one carton, which
contains the following:

1.

Energy Recovery Ventilator

2.

Service Door

3.

Rain Hood and Mist Eliminator

4.

Installation Instructions

UNPACKING

Upon receipt of the equipment, be sure to compare the
model number found on the shipping label with the
accessory identification information on the ordering and
shipping document to verify that the correct accessory
has been shipped.

Inspect the carton housing of each ventilator as it is
received, and before signing the freight bill, verify that
all items have been received and that there is no visible
damage.  Note any shortages or damage on all copies of
the freight bill.  The receiving party must contact the last
carrier immediately, preferably in writing, requesting
inspection by the carrier’s agent.  Concealed damage not
discovered until after loading must be reported to the
carrier within 15 days of its receipt.

GENERAL DESCRIPTION

The Energy Recovery Ventilator was designed to
provide energy efficient, cost effective ventilation to
meet I.A.Q. (Indoor Air Quality) requirements while still
maintaining good indoor comfort and humidity control
for a variety of applications such as schools, classrooms,
lounges, conference rooms, beauty salons and others.  It
provides a constant supply of fresh air for control of
airborne pollutants including CO

2

, smoke, radon,

formaldehyde, excess moisture, virus and bacteria.

The ventilator incorporates patented rotary heat
exchanger technology to remove both heat and moisture.

It is designed as a single package, which can be easily
factory or field installed for new installations or retrofit to
Bard WF wall mounted units.  The package consists of a
unique rotary Energy Recovery Cassette that can be easily
removed for cleaning or maintenance.  The cassette has a
21-inch diameter heat transfer wheel for efficient heat
transfer.  The heat transfer wheel uses a permanently
bonded dry desiccant coating for total heat recovery.

Ventilation is accomplished with two (2) blower/motor
assemblies each consisting of a drive motor and dual
blowers for maximum ventilation at low sound levels.
On non-independent motor control models, the air is
exhausted at the same rate that fresh air is brought into
the structure, thus not impacting building pressure.  On
independent motor control models, the air can be
exhausted at a different rate than the intake or fresh air.
Never operate the fresh air at a lower speed than the
exhaust air.  Operating the fresh air at a higher speed
than the exhaust air will help maintain a slight positive
pressure in the building.  The rotating energy wheel
provides the heat transfer effectively during both
summer and winter conditions.  Provides required
ventilation to meet the requirements of ASHRAE 62.1-
2007 standard.

WF

= Wall Mount Gas Furnace

Energy Recovery Ventilator

Color
-X = Beige
-4 = Buckeye Gray

WF     ERV  –  X

ELECTRICAL SPECIFICATIONS

l

e

d

o

M

e

g

a

t

l

o

V

s

p

m

A

l

o

r

t

n

o

C

e

g

a

t

l

o

V

V

R

E

F

W

8

0

2

/

0

3

2

1

.

2

V

4

2

Содержание WFERV-A-X

Страница 1: ...A X WFERV A 4 ENERGY RECOVERY VENTILATOR WITH EXHAUST Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 495A Supersedes 2100 495 File Volume III Tab...

Страница 2: ...gure 9 Operation of Unit with WFERV 14 Figure 10 Thermostat Wiring 18 Figure 11 Terminal Block Location Diagram 19 Figure 12 Hub Assembly with Ball Bearings 20 Tables Table 1 Ventilation Air CFM 16 Mo...

Страница 3: ...lity requirements while still maintaining good indoor comfort and humidity control for a variety of applications such as schools classrooms lounges conference rooms beauty salons and others It provide...

Страница 4: ...5 0 0 4 8 0 0 6 3 0 0 0 5 9 0 8 5 7 0 7 5 6 0 6 0 0 8 6 2 0 0 7 7 1 0 0 6 9 0 0 6 8 0 0 6 8 0 0 6 8 0 0 6 8 0 0 6 8 0 0 6 8 0 0 6 8 0 0 2 8 1 0 0 1 9 0 0 0 1 0 0 0 0 3 9 1 0 0 7 2 1 0 0 9 6 0 0 2 6 0...

Страница 5: ...l panel 9 Remove female plug of low voltage wiring harness from the heat recovery assembly and snap into filter rack Route electrical harness leads through the 7 8 bushing into the low voltage box See...

Страница 6: ...See Figure 9 Be sure to insert the top flange of the air intake hood into and through the slot in the service door and between the door and insulation to prevent bowing of the door 18 Close front doo...

Страница 7: ...MOVE VENT OPTION DOOR MIS 2350 FRONT DOOR VENT OPTION DOOR EXHAUST COVER PLATES FIGURE 2A ASSEMBLY OF EXHAUST BLOWER ENCLOSURE PART NUMBERS COLOR A B C BEIGE 134 248 X 134 244 X 134 243 X GRAY 134 248...

Страница 8: ...Manual 2100 495A Page 8 of 21 FIGURE 3 FILTER AND EXHAUST PLATE LOCATION FRONT EXHAUST FILL PLATE FILL PLATE FILTER FRONT DOOR REAR EXHAUST SCREW MIS 2345...

Страница 9: ...INSTALLATION OF EXHAUST BLOWER ASSEMBLY MIS 2353 ASSEMBLY RIGHT SIDE LOWER WFERV FRONT PLATE REMOVE FASTEN ASSEMBLY TO CONDENSER PARTITION WITH 4 SCREWS DO NOT LOCATING HOLES ATTATCH EXHAUST BLOWER E...

Страница 10: ...Manual 2100 495A Page 10 of 21 FIGURE 5 INSTALLATION OF WFERV...

Страница 11: ...Manual 2100 495A Page 11 of 21 FIGURE 6 WFERV ASSEMBLY...

Страница 12: ...21 FIGURE 7 WIRING 230 VOLT MIS 2356 ON WIRING DIAGRAM 230 VOLT CONTROL BOARD AS SHOWN WIRES TO L1 AND L2 ON BLOWER WIRES CONNECT WIRES INSERTED WITH CONNECT LOW VOLTAGE WIRES TO C W1 AND G AS SHOWN O...

Страница 13: ...Manual 2100 495A Page 13 of 21 FIGURE 8 INSTALLATION OF FRESH AIR INTAKE HOOD ASSEMBLY...

Страница 14: ...ITH WFERV INSTALLED SUPPLY AIR AIR EXHAUST RETURN AIR TOP FILTER BURNER BOX EXHAUST BLOWER HOOD INTAKE AIR GAS MANIFOLD GAS VALVE INDUCER DRAFT AIR BLOWER BLOWER EXHAUST WERV CASSETTE HOOD INDOOR COMF...

Страница 15: ...cupied periods wastes energy decreases the expected life of the WFERV and can result in a large moisture buildup in the structure The WFERV removes 60 to 70 of the moisture in the incoming air not 100...

Страница 16: ...ing the efficiency with which the desiccant can absorb and desorb moisture FREQUENCY In a reasonably clean indoor environment such as a school office building or home experience shows that reductions...

Страница 17: ...sette out of ventilator 6 Use a shop vacuum with brush attachment to clean both sides of the energy recovery wheels 7 Reverse shop vacuum to use as a blower and blow out any residual dry debris from t...

Страница 18: ...Manual 2100 495A Page 18 of 21 FIGURE 10 THERMOSTAT WIRING DIAGRAM...

Страница 19: ...Manual 2100 495A Page 19 of 21 FIGURE 11 TERMINAL BLOCK LOCATION...

Страница 20: ...Manual 2100 495A Page 20 of 21 FIGURE 12 HUB ASSEMBLY WITH BALL BEARING...

Страница 21: ...Manual 2100 495A Page 21 of 21...

Отзывы: