background image

Manual 2100-384B
Page

14 of 19

START UP

IMPORTANT INSTALLER NOTE

For improved start up performance, wash the indoor coil
with a dishwasher detergent.

SERVICE HINTS

1. Caution owner to maintain clean air filters at all

times and also not to needlessly close off supply
and return air registers.  This reduces airflow
through the system, which shortens equipment
service life as well as increasing operation costs.

2. The unit is equipped with a high pressure cut out

switch.

3. Check all power fuses or circuit breakers to be sue

they are the correct rating.

4. Periodic cleaning of the outdoor coil to permit full

and unrestricted airflow circulation is essential.

HIGH PRESSURE SWITCH

The WE121 models are supplied with a remote reset
high pressure switch.  If tripped, this pressure switch
may be reset by turning the thermostat off then back on
again.

SEQUENCE OF OPERATION

COOLING

 – Circuit R-Y makes at thermostat pulling

in compressor contactor, starting the compressor and
outdoor motor.  The G (indoor motor) circuit is
automatically completed on any call for cooling
operation or can be energized by manual fan switch on
subbase for constant air circulation.  On a call for
heating, circuit R-W1 make at the thermostat pulling in
heat contact for the strip heat and blower operation.

COMPRESSOR CONTROL MODULE

The compressor control module is optional on the
models covered by this manual.  The compressor
control is an anti-short cycle/lockout timer with high
and low pressure switch monitoring and alarm relay
output.

Adjustable Delay on Make and Break Timer

On initial power up or any time power is interrupted to
the unit the 

delay on make

 period begins, which will be

2 minutes plus 10% of the 

delay on break

 setting.

When the delay on make is complete and the high
pressure switch (and low pressure switch if employed) is
closed, the compressor contactor is energized.  Upon
shutdown, the delay on break time starts and prevents
restart until the delay on break and delay on make
periods have expired.

During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout
timer will go into a 

soft lockout

 and stay in soft lockout

until the high pressure switch closes 

and

 the delay on

break time has expired.  If the high pressure switch
opens again in this same operating cycle the unit will go
into manual lockout condition and the alarm relay
circuit will energize.  Recycling the wall thermostat
resets the manual lockout.

Low Pressure Switch, Bypass  and Lockout
Sequence (Optional)

If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout.  Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired.  If the low
pressure switch remains open, or opens again for longer
that 120 seconds the unit will go into manual lockout
condition and the alarm relay circuit will energize.
Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications
where alarm relay is employed.  This terminal is
powered whenever compressor is locked out due to HPC
or LPC sequences as described.

NOTE: Both high and low pressure switch controls are

inherently automatic reset devices.  The high
pressure switch and low pressure switch cut out
and cut in settings are fixed by specific air
conditioner or heat pump unit model.  The
lockout features, both soft and manual, are a
function of the Compressor Control Module.

Содержание WE121

Страница 1: ...RS Model WE121 INSTALLATION INSTRUCTIONS Manual 2100 384B Supersedes 2100 384A File Volume III Tab 16 Date 09 17 10 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as plan...

Страница 2: ...harge 16 Pressure Table 17 Optional Field Installed Accessories 17 R 407C Refrigerant Service Procedure Considerations 18 Charging 18 Leaks 18 Figures Figure 1 Unit Dimensions 5 Figure 2 Blower Damper...

Страница 3: ...ter and Summer Air Conditioning Duct Design for ACCA Manual D Residential Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...field power conductors Refer to the National Electrical Code latest revision article 310 for power conductor sizing CAUTION When more than one field power conductor circuit is run through one conduit...

Страница 5: ...Manual 2100 384B Page 5 of 19 FIGURE 1 UNIT DIMENSIONS FACTORY BUILT AT 5 INCHES WE121...

Страница 6: ...r Heating and Air Conditioning Systems NFPA No 90B Where local regulations are at a variance with instructions installer should adhere to local codes DUCT WORK All duct work supply and return must be...

Страница 7: ...f the fresh air damper shipped with each unit FIGURE 2 FRESH AIR DAMPER CONDENSATE DRAIN This unit employs an automatic condensate disposal system consisting of a base drain pan drain valve and fan bl...

Страница 8: ...must be cut through the wall as shown in Figure 4 NOTE If the combination SUPPLY RETURN Grille Assembly model CSRG 1 is to be used in conjunction with this unit a different size wall opening is requir...

Страница 9: ...Manual 2100 384B Page 9 of 19 FIGURE 3 MOUNTING INSTRUCTIONS WHEN USING THE COMBINATION SUPPLY RETURN GRILLE ASSEMBLY CSRG 1...

Страница 10: ...Manual 2100 384B Page 10 of 19 FIGURE 4 MOUNTING INSTRUCTIONS THIS INFORMATION DOES NOT APPLY IF CSRG 1 COMBINATION SUPPLY RETURN GRILLE ASSEMBLY IS TO BE USED SEE FIGURE 3...

Страница 11: ...UCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL DIMENSIONS 2 x 4 S 2 x 6 S OR STRUCTURAL STEEL ATTACH TO TOP 1 000 CLEARANCE 1 000 CLEARA...

Страница 12: ...ATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE WALL INSTALLATION DUCTED SUPPLY GRILLE OUT...

Страница 13: ...fuse and wire sizes 75 C copper for all models including the most commonly used heater sizes Also shown are the number of field power circuits required for the various models with heaters The unit rat...

Страница 14: ...is complete and the high pressure switch and low pressure switch if employed is closed the compressor contactor is energized Upon shutdown the delay on break time starts and prevents restart until the...

Страница 15: ...38 second DOM 4 0 minute 240 seconds DOB 144 second DOM 5 0 minute 300 seconds DOB 150 second DOM During routine operation of the unit with no power interruptions the compressor will operate on demand...

Страница 16: ...ry bulb 67 F wet bulb 50 R H temperature and rated airflow across the evaporator during cooling cycle TABLE 3 FAN BLADE DIMENSION l e d o M A n o i s n e m i D 1 2 1 E W 2 1 TABLE 7 MAXIMUM ESP OF OPE...

Страница 17: ...Air Temperature Entering Outdoor Coil o F l e d o M r i A n r u t e R e r u t a r e p m e T e r u s s e r P 5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1 1 2 1 E W B D 5 7 B W 2 6 e d i S w o L e d i S...

Страница 18: ...nt cylinder must be in liquid phase it is suggested that a sight glass be connected between the charging hose and the suction service port This will permit you to adjust the cylinder hand valve so tha...

Страница 19: ...5 8 5 6 9 5 7 0 6 7 1 6 7 2 6 2 5 6 7 7 6 0 0 7 3 2 7 8 4 7 7 6 7 8 8 7 9 0 8 9 2 8 0 5 1 5 5 1 0 6 1 5 6 1 0 7 1 5 7 1 0 8 1 5 8 1 0 9 1 5 9 1 0 0 2 5 0 2 0 1 2 5 1 2 0 2 2 5 2 2 0 3 2 5 3 2 0 4 2 5...

Отзывы: