Manual   2100-359
Page    5

CONDENSATE DRAIN

A plastic drain hose extends from the drain pan at the top
of the unit down to the unit base.  There are openings in
the unit base for the drain hose to pass through.  In the
event the drain hose is connected to a drain system of
some type, it must be an open or vented type system to
assure proper drainage.

A 1/4 inch clearance to combustible material for the first
three feet of duct attached to the outlet air frame is
required.  See Wall Mounting Instructions and Figures 3
and 3A for further details.

Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wall cavity.

Some installations may not require any return air duct.  A
metallic return air grille is required with installations not
requiring a return air duct.  The spacing between louvers
on the grille shall not be larger than 5/8 inch.

NOTE:  If no return air duct is used, applicable

installation codes may limit this cabinet to
installation only in a single story structure.

Any grille that meets with 5/8 inch louver criteria may be
used.  It is recommended that Bard Return Air Grille Kit
RG2 through RG5 or RFG2 through RFG5 be installed
when no return duct is used.  Contact distributor or
factory for ordering information.  If using a return air
filter grille, filters must be of sufficient size to allow a
maximum velocity of 400 fpm.

Design the duct work according to methods given by the
Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one inch of insulation.  Use
insulation with a vapor barrier on the outside of the
insulation.  Flexible joints should be used to connect the
duct work to the equipment in order to keep the noise
transmission to a minimum.

These instructions and any instructions packaged with
any separate equipment, required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly any tags and/
or labels attached to the equipment.

Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA).  The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association for
the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No. 90A,
and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B.  Where local
regulations are at a variance with instructions, installer
should adhere to local codes.

DUCT WORK

All duct work, supply and return, must be properly sized
for the design air flow requirement of the equipment.  Air
Conditioning Contractors of America (ACCA) is an
excellent guide to proper sizing.  All duct work or
portions thereof not in the conditioned space should be
properly insulated in order to both conserve energy and
prevent condensation or moisture damage.

While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way.  Authorities having
jurisdiction should be consulted before the installation is
made.  See Page 1 for information on codes and
standards.

SHIPPING DAMAGE

Upon receipt of equipment, the carton should be checked
for external signs of shipping damage.  If damage is
found, the receiving party must contact the last carrier
immediately, preferably in writing, requesting inspection
by the carrier’s agent.

GENERAL

The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.

The refrigerant system is completely assembled and
charged.  All internal wiring is complete.

The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.

These instructions explain the recommended method to
install the air cooled self-contained unit and the electrical
wiring connections to the unit.

Содержание WA7013

Страница 1: ...WALL MOUNTED PACKAGE AIR CONDITIONERS Model WA7013 Manual 2100 359B Supersedes 2100 359A File Volume III Tab 16 Date 05 13 02 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just...

Страница 2: ...ESP of Operation Electric Heat Only 15 Table 10 Pressure Table 16 Table 11 Optional Accessories 16 Getting Other Information and Publications 1 Wall Mount General Information 2 Air Conditioning Wall...

Страница 3: ...ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washingto...

Страница 4: ...7 1 1 8 1 0 0 8 2 1 0 9 7 1 2 0 0 6 0 3 7 8 1 0 3 0 3 2 0 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 MODEL NUMBER CONTROL MODULES CAPACITY 60 5 Ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 REVISIONS KW VEN...

Страница 5: ...Manual 2100 359 Page 3 FIGURE 1 UNITDIMENSIONS MIS 1456...

Страница 6: ...d o M T I U C R I C E L G N I S T I U C R I C L A U D d e t a R s t l o V e s a h P o N d l e i F r e w o P s t i u c r i C 3 m u m i n i M t i u c r i C y t i c a p m A 1 m u m i x a M l a n r e t x...

Страница 7: ...entire air conditioning system should be carefully read before beginning the installation Note particularly any tags and or labels attached to the equipment Size of unit for a proposed installation sh...

Страница 8: ...that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 See Figures 2 and 3 for details WAR...

Страница 9: ...Manual 2100 359 Page 7 FIGURE 2 MOUNTINGINSTRUCTIONS MIS 1445...

Страница 10: ...NING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 in...

Страница 11: ...2 X 6 S AND OR STRUCTURAL STEEL THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL A SECOND MEMBER MAY BE REQUIRED FOR SOME WALLS RETURN DUCT OPENING SUPPLY DUCT OPENING FIGURE 4 W...

Страница 12: ...Manual 2100 359 Page 10 FIGURE 6 COMMONWALLMOUNTINGINSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSETINSTALLATION MIS 550...

Страница 13: ...reventing entry Five 5 wires should be run from thermostat subbase to the 24V terminal board in the unit A five conductor 18 gauge copper color coded thermostat cable is recommended The connection poi...

Страница 14: ...Manual 2100 359 Page 12 FIGURE 7 UNIT 24V TERMINAL BOARD MIS 1373B...

Страница 15: ...nstallation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation of the compressor may be changed by reversing any two...

Страница 16: ...e due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light If phases are reversed...

Страница 17: ...INDOORBLOWERPERFORMANCE CFM 230V P S E H n I 2 O 3 1 0 7 A W d e e p S h g i H l i o C y r D l i o C t e W 0 1 2 5 7 7 1 5 7 6 1 5 7 5 1 0 0 6 1 5 2 5 1 5 2 4 1 TABLE 7 REFRIGERANTCHARGE l e d o M w...

Страница 18: ...7 A W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 8 6 5 1 2 8 6 8 2 2 9 6 2 4 2 0 7 6 5 2 1 7 2 7 2 2 7 9 8 2 3 7 5 0 3 4 7 4 2 3 5 7 3 4 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d...

Отзывы: