Alarm Relay Output

Alarm terminal is output connection for applications
where alarm relay is employed.  This terminal is
powered whenever compressor is locked out due to HPC
or LPC sequences as described.

NOTE: Both high and low pressure switch controls are

inherently automatic reset devices.  The high
pressure switch and low pressure switch cut out
and cut in settings are fixed by specific air
conditioner or heat pump unit model.  The
lockout features, both soft and manual, are a
function of the Compressor Control Module.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break
Timer

The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes.  Delay on Make (DOM)
timing on power-up and after power interruptions is
equal to 2 minutes plus 10% of Delay on Break (DOB)
setting:

0.5 minute (30 seconds) DOB = 123 second DOM
1.0 minute (60 seconds) DOB = 126 second DOM
2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.

Typical Settings for Dual Unit Installation:

Unit 1: DOB set at 2 minutes, and DOM is 132 seconds.

Unit 2: DOB set at 4 minutes, and DOM is 144 seconds.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed.  A pressure table can be found later in the
manual covering all models.  It is imperative to match
the correct pressure table to the unit by model number.

Adjustable Delay On Make And Break Timer

On initial power up or any time power is interrupted to
the unit the 

delay on make

 period begins, which will be

2 minutes plus 10% of the 

delay on break

 setting.

When the delay on make is complete and the high
pressure switch (and low pressure switch if employed)
is closed, the compressor contactor is energized.  Upon
shutdown, the delay or break timer starts and prevents
restart until the delay on break and delay on make
periods have expired.

During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout
timer will go into a 

soft lockout

 and stay in soft lockout

until the high pressure switch closes and the delay on
break time has expired.  If the high pressure switch
opens again in this same operating cycle, the unit will
go into 

manual lockout

 condition and the alarm relay

circuit will energize.  Recycling the wall thermostat
resets the manual lockout.

Low Pressure Switch, Bypass, and Lockout
Sequence

If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout.   Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired.  If the low
pressure switch remains open, or opens again for longer
than 120 seconds the unit will go into manual lockout
condition and the alarm relay circuit will energize.
Recycling the wall thermostat resets the manual
lockout.

Содержание WA4842

Страница 1: ...STRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODELS WA4842 WA4843 WA6022 WA6023 Manual 2100 401A Supersedes 2100 401 File Volume III Tab 16 Date 07 25 06 Bard Manufacturing Company Inc Bryan Ohio...

Страница 2: ...arge 19 Table 8 Rated CFM and Rated ESP 19 Table 9 Maximum ESP of Operation Electric Heat Only 20 Table 10 Pressure Table 20 Table 11 Optional Accessories 21 Getting Other Information and Publications...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning...

Страница 4: ...0 5 0 7 1 1 8 1 0 0 8 2 1 0 9 7 1 2 0 0 6 0 3 7 8 1 0 3 0 3 2 0 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 MODEL NUMBER CONTROL MODULES CAPACITY 60 5 Ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 REVISIONS K...

Страница 5: ...Manual 2100 401A Page 5 of 21 FIGURE 1 UNIT DIMENSIONS WA6023 WA4843 ONLY...

Страница 6: ...Manual 2100 401A Page 6 of 21 FIGURE 2 UNIT DIMENSIONS WA6022 WA4842 ONLY...

Страница 7: ...i c a p m A 1 m u m i x a M e s u F l a n r e t x E r o r e k a e r B t k C 2 r e w o P d l e i F e z i S e r i W 2 d n u o r G e z i S e r i W A T K C B T K C A T K C B T K C A T K C B T K C A T K C...

Страница 8: ...ags and or labels attached to the equipment Design the duct work according to methods given by the Air Conditioning Contractors of America ACCA When duct runs through unheated spaces it should be insu...

Страница 9: ...et of supply air duct require a minimum of 1 4 inch clearance to combustible material If a combustible wall use a minimum of 30 x 10 dimensions for sizing However it is generally recommended that a 1...

Страница 10: ...Manual 2100 401A Page 10 of 21 FIGURE 3 MOUNTING INSTRUCTIONS WA6023 WA4843 ONLY...

Страница 11: ...Manual 2100 401A Page 11 of 21 FIGURE 4 MOUNTING INSTRUCTIONS WA6022 WA4842 ONLY...

Страница 12: ...This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible...

Страница 13: ...Manual 2100 401A Page 13 of 21 FIGURE 6 WALL MOUNTING INSTRUCTIONS FIGURE 7 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 14: ...Manual 2100 401A Page 14 of 21 FIGURE 8 COMMON WALL MOUNTING INSTALLATIONS...

Страница 15: ...ening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing entry See Start Up sec...

Страница 16: ...Manual 2100 401A Page 16 of 21 FIGURE 9 UNIT 24V TERMINAL BOARD...

Страница 17: ...etermined for a specific system or installation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation of the compressor...

Страница 18: ...ual covering all models It is imperative to match the correct pressure table to the unit by model number Adjustable Delay On Make And Break Timer On initial power up or any time power is interrupted t...

Страница 19: ...e e p S h g i H d e e p S h g i H d e e p S h g i H y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C 0 1 2 5 7 7 1 5 7 6 1 5 7 5 1 0 0 6...

Страница 20: ...1 0 1 1 5 1 1 2 0 6 A W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 1 7 3 3 2 2 7 7 4 2 4 7 2 6 2 5 7 8 7 2 6 7 5 9 2 7 7 3 1 3 8 7 1 3 3 8 7 1 5 3 9 7 1 7 3 B D g e d 0 8 B W g e d 7 6...

Страница 21: ...A WA4842A WA4843B WA4842B t r a P r e b m u N n o i t p i r c s e D 5 1 C M C t i K t r a t S X X A 9 0 B C M W B 7 0 B C M W A 8 0 B C M W B 5 0 B C M W t i K r e k a e r B t i u c r i C t i K r e k...

Отзывы: