High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout
timer will go into a 

soft lockout

 and stay in soft lockout

until the high pressure switch closes and the delay on
break time has expired.   If the high pressure switch opens
again in this same operating cycle the unit will go into

manual lockout

 condition and the alarm relay circuit will

energize.   Recycling the wall thermostat resets the
manual lockout.

Low Pressure Switch, Bypass, and Lockout
Sequence

If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout.   Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired.  If the low pressure
switch remains open, or opens again for longer than 120
seconds the unit will go into manual lockout condition
and the alarm relay circuit will energize.  Recycling the
wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications
where alarm relay is employed.  This terminal is powered
whenever compressor is locked out due to HPC or LPC
sequences as described.

NOTE: Both high and low pressure switch controls are

inherently automatic reset devices.  The high
pressure switch and low pressure switch cut out
and cut in settings are fixed by specific air
conditioner or heat pump unit model.  The
lockout features, both soft and manual, are a
function of the Compressor Control Module.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break
Timer

The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes.  Delay on Make (DOM)
timing on power-up and after power interruptions is equal
to 2 minutes plus 10% of Delay on Break (DOB) setting:

0.5 minute (30 seconds)

DOB =123 second DOM

1.0 minute (60 seconds)

DOB =126 second DOM

2.0 minute (120 seconds) DOB =132 second DOM
3.0 minute (180 seconds) DOB =138 second DOM
4.0 minute (240 seconds) DOB =144 second DOM
5.0 minute (300 seconds) DOB =150 second DOM

During routine operation of the unit with now power
interruptions the compressor will operate on demand with
no delay.

Typical Settings for Dual Unit Installation:

Unit No. 1:  DOB set at 2 minutes, and DOM is 132 sec.

Unit No. 2:  DOB set at 4 minutes, and DOM is 144 sec.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed.  Pressure tables can be found later in the
manual covering all models.  It is imperative to match the
correct pressure table to the unit by model number.

Содержание WA182

Страница 1: ...2 WALL MOUNTED PACKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS Manual No 2100 369E Supersedes 2100 369D File Volume III Tab 16 Date 08 01 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 19...

Страница 2: ...t Up Label 14 Figure 9 Fan Blade Setting 16 Tables Table 1 Electric Heat Table 4 Table 2 Electrical Specifications 6 Table 3 Thermostat Wire Size 9 Table 4 Wall Thermostat 9 Table 5 Fan Blade Dimensio...

Страница 3: ...ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washin...

Страница 4: ...ic Coated Evaporator 2 Phenolic Coated Condenser 3 Phenolic Coated Evaporator and Condenser OUTLET OPTIONS X Front Standard T Top on WA30 WA36 Models NOTE For 0KW circuit breakers 230 208 Volt or pull...

Страница 5: ...F G I J K L M N O P Q R S T A B C B 8 1 A W 4 2 A W 0 0 3 3 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 9 1 8 8 1 1 8 8 9 1 0 0 5 3 0 5 8 1 5 7 5 2 6 5 0 2 5 7 6 2 6 0 8 2 5 2 9 2 0 0 7 2 3 6 2 3 1 4 3 6 0 2 2 5...

Страница 6: ...ent Factors when more than three conductors are in a raceway TABLE 2 ELECTRICAL SPECIFICATIONS T I U C R I C E L G N I S l e d o M d e t a R s t l o V e s a h P o N d l e i F r e w o P s t i u c r i C...

Страница 7: ...CCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or mois...

Страница 8: ...unit CONDENSATE DRAIN A plastic drain hose extends from the drain pan at the top of the unit down to the unit base There are openings in the unit base for the drain hose to pass through In the event...

Страница 9: ...e g u a g 8 1 e g u a g 6 1 e g u a g 4 1 e g u a g 2 1 5 4 0 6 0 0 1 0 6 1 0 5 2 TABLE 4 WALL THERMOSTAT t a t s o m r e h T s e r u t a e F e t a n i m o d e r P 7 5 0 3 0 4 8 3 5 1 1 D 0 2 2 5 H T...

Страница 10: ...Manual 2100 369E Page 10 of 18 FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 11: ...369E Page 11 of 18 FIGURE 4 WALL MOUNTING INSTRUCTIONS FIGURE 5 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR DUCT...

Страница 12: ...Manual 2100 369E Page 12 of 18 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Страница 13: ...Manual 2100 369E Page 13 of 18 FIGURE 7 LOW VOLTAGE WIRING...

Страница 14: ...f delay On a call for heating circuit R W1 make at the thermostat pulling in heat contact for the strip heat and blower operation On a call for second stage heat R W2 makes bringing on second heat con...

Страница 15: ...or LPC sequences as described NOTE Both high and low pressure switch controls are inherently automatic reset devices The high pressure switch and low pressure switch cut out and cut in settings are f...

Страница 16: ...steps to reinstall REFRIGERANT CHARGE The correct system R 22 charge is shown on the unit rating plate Optimum unit performance will occur with a refrigerant charge resulting in a suction line temper...

Страница 17: ...3 7 8 0 2 5 7 3 2 2 7 7 8 3 2 9 7 3 5 2 1 8 8 6 2 2 8 4 8 2 4 8 9 9 2 5 8 5 1 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 6 7 9 9 1 8 7 4 1 2 0 8 9 2 2 3 8 4 4 2 4 8 9 5 2 6 8 5 7 2 8...

Страница 18: ...M 2 D A F M X X X X t s u a h x E h t i w r o t a l i t n e V l a i c r e m m o C 2 V R C X X X X t s u a h x E h t i w r e z i m o n o c E 2 M F I E X X X X r o t a l i t n e V y r e v o c e R y g r...

Отзывы: