manualshive.com logo in svg
background image

Manual

2100-369E

Page

14 of 18

IMPORTANT INSTALLER NOTE

For improved start-up performance, wash the indoor coil
with a dishwasher detergent.

CRANKCASE HEATERS

All units are provided with some form of compressor
crankcase heat.

All single and three phase models have an insertion well-
type heater located in the lower section of the compressor
housing.  This is a self-regulating type heater that draws
only enough power to maintain the compressor at a safe
temperature.

Some form of crankcase heat is essential to prevent liquid
refrigerant from migrating to the compressor, causing oil
pump out on compressor start up and possible valve
failure due to compressing a liquid.

The decal in Figure 8 is affixed to all outdoor units
detailing start up procedure.  This is very important.
Please read carefully.

SERVICE HINTS

1. Caution homeowner to maintain clean air filters at all

times.  Also, not to needlessly close off supply and
return air registers.  This reduces airflow through the
system, which shortens equipment service life as well
as increasing operating costs.

2. Check all power fuses or circuit breakers to be sure

they are the correct rating.

3. Periodic cleaning of the outdoor coil to permit full and

unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

Cooling—Circuit R-Y makes at thermostat pulling in
compressor contactor, starting the compressor and
outdoor motor.  The G (indoor motor) circuit is
automatically completed on any call for cooling operation
or can be energized by manual fan switch on subbase for
constant air circulation.  On all 230 volt units there is a
one-minute off delay on the blower motor.  460 volt
models do not have an off delay.  On a call for heating,
circuit R-W1 make at the thermostat pulling in heat
contact for the strip heat and blower operation.  On a call
for second stage heat, R-W2 makes bringing on second
heat contactor, if so equipped.

START UP

COMPRESSOR CONTROL MODULE

The compressor control module is optional on the models
covered by this manual.  The compressor control is an
anti-short cycle/lockout timer with high and low pressure
switch monitoring and alarm relay output.

Adjustable Delay On Make And Break Timer

On initial power up or anytime power is interrupted to the
unit, the 

delay on make

 period begins, which will be 2

minutes plus 10% of the 

delay on break

 setting.  When

the delay on make is complete and the high pressure
switch (and low pressure switch if employed) is closed,
the compressor contactor is energized.  Upon shutdown
the delay or break timer starts and prevents restart until
the delay on break and delay on make periods have
expired.  During routine operation of the unit with no
power interruptions the compressor will operate on
demand with no delay.

FIGURE 8

START UP LABEL

IMPORTANT

These procedures must be
followed at initial start up and at
any time power has been removed
for 12 hours or longer.

To prevent compressor damage which may
result from the presence of liquid refrigerant
in the compressor crankcase:

1. Make certain the room thermostat is in the

"off" position (the compressor is not to
operate).

2. Apply power by closing the system

disconnect switch.  This energizes the
compressor heater which evaporates the
liquid refrigerant in the crankcase.

3. Allow 4 hours or 60 minutes per pound of

refrigerant in the system as noted on the
unit rating plate, whichever is greater.

4. After properly elapsed time, the thermostat

may be set to operate the compressor.

5. Except as required for safety while

servicing, 

do not open system

disconnect  switch

.

           

 7961-061

Содержание WA182

Страница 1: ...2 WALL MOUNTED PACKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS Manual No 2100 369E Supersedes 2100 369D File Volume III Tab 16 Date 08 01 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 19...

Страница 2: ...t Up Label 14 Figure 9 Fan Blade Setting 16 Tables Table 1 Electric Heat Table 4 Table 2 Electrical Specifications 6 Table 3 Thermostat Wire Size 9 Table 4 Wall Thermostat 9 Table 5 Fan Blade Dimensio...

Страница 3: ...ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washin...

Страница 4: ...ic Coated Evaporator 2 Phenolic Coated Condenser 3 Phenolic Coated Evaporator and Condenser OUTLET OPTIONS X Front Standard T Top on WA30 WA36 Models NOTE For 0KW circuit breakers 230 208 Volt or pull...

Страница 5: ...F G I J K L M N O P Q R S T A B C B 8 1 A W 4 2 A W 0 0 3 3 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 9 1 8 8 1 1 8 8 9 1 0 0 5 3 0 5 8 1 5 7 5 2 6 5 0 2 5 7 6 2 6 0 8 2 5 2 9 2 0 0 7 2 3 6 2 3 1 4 3 6 0 2 2 5...

Страница 6: ...ent Factors when more than three conductors are in a raceway TABLE 2 ELECTRICAL SPECIFICATIONS T I U C R I C E L G N I S l e d o M d e t a R s t l o V e s a h P o N d l e i F r e w o P s t i u c r i C...

Страница 7: ...CCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or mois...

Страница 8: ...unit CONDENSATE DRAIN A plastic drain hose extends from the drain pan at the top of the unit down to the unit base There are openings in the unit base for the drain hose to pass through In the event...

Страница 9: ...e g u a g 8 1 e g u a g 6 1 e g u a g 4 1 e g u a g 2 1 5 4 0 6 0 0 1 0 6 1 0 5 2 TABLE 4 WALL THERMOSTAT t a t s o m r e h T s e r u t a e F e t a n i m o d e r P 7 5 0 3 0 4 8 3 5 1 1 D 0 2 2 5 H T...

Страница 10: ...Manual 2100 369E Page 10 of 18 FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 11: ...369E Page 11 of 18 FIGURE 4 WALL MOUNTING INSTRUCTIONS FIGURE 5 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR DUCT...

Страница 12: ...Manual 2100 369E Page 12 of 18 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Страница 13: ...Manual 2100 369E Page 13 of 18 FIGURE 7 LOW VOLTAGE WIRING...

Страница 14: ...f delay On a call for heating circuit R W1 make at the thermostat pulling in heat contact for the strip heat and blower operation On a call for second stage heat R W2 makes bringing on second heat con...

Страница 15: ...or LPC sequences as described NOTE Both high and low pressure switch controls are inherently automatic reset devices The high pressure switch and low pressure switch cut out and cut in settings are f...

Страница 16: ...steps to reinstall REFRIGERANT CHARGE The correct system R 22 charge is shown on the unit rating plate Optimum unit performance will occur with a refrigerant charge resulting in a suction line temper...

Страница 17: ...3 7 8 0 2 5 7 3 2 2 7 7 8 3 2 9 7 3 5 2 1 8 8 6 2 2 8 4 8 2 4 8 9 9 2 5 8 5 1 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 6 7 9 9 1 8 7 4 1 2 0 8 9 2 2 3 8 4 4 2 4 8 9 5 2 6 8 5 7 2 8...

Страница 18: ...M 2 D A F M X X X X t s u a h x E h t i w r o t a l i t n e V l a i c r e m m o C 2 V R C X X X X t s u a h x E h t i w r e z i m o n o c E 2 M F I E X X X X r o t a l i t n e V y r e v o c e R y g r...

Отзывы: