background image

Manual   2100-200
Page   6

FRESH AIR INTAKE

All units are built with fresh air inlet slots punched in the
service panel.

If the unit is equipped with the fresh air damper
assembly, the assembly is shipped already attached to the
unit.  The damper blade is locked in the closed position.
To allow the damper to operate, the maximum and
minimum blade position stops must be installed.  See
Figure 2.

All capacity, efficiency and cost of operation information
as required for Department of Energy “Energyguide” Fact
Sheets is based upon the fresh air blank-off plate in place
and is recommended for maximum energy efficiency.

The blank-off plate is available upon request from the
factory and is installed in place of the fresh air damper
shipped with each unit.

CONDENSATE DRAIN

A plastic drain hose extends from the drain pan at the top
of the unit down to the unit base. There are openings in
the unit base for the drain hose to pass through. In the
event the drain hose is connected to a drain system of
some type, it must be an open or vented type system to
assure proper drainage.

FIGURE  2

FRESH AIR DAMPER ASSEMBLY

BLADE IS LOCKED
CLOSED FOR
SHIPPING

MIS-938

Содержание WA181

Страница 1: ...0 200J File Volume III Tab 16 Date 04 19 99 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planned Copyright 1999 MIS 656 Models WA181 WA241 Wall Mounted Packaged Air Cond...

Страница 2: ...Blade Setting 14 Tables Table 1 Electric Heat Table 2 Table 2 Electrica Specifications 4 Table 3 Thermostat Wire Size 7 Table 4 Wall Thermostat and Subbase Combinations 7 Table 5 Fan Blade Dimensions...

Страница 3: ...al D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washington DC 20...

Страница 4: ...ROL MODULES COIL OPTIONS X Standard 1 Phenolic Coated Evaporator 2 Phenolic Coated Condenser 3 Phenolic Coated Evaporator and Condenser OUTLET OPTIONS X Front Standard T Top on WA30 and WA36 Models NO...

Страница 5: ...F G I J K L M N O P Q R S T A B C B 8 1 A W 4 2 A W 0 0 3 3 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 9 1 8 8 1 1 8 8 9 1 0 0 5 3 0 5 8 1 5 7 5 2 6 5 0 2 5 7 6 2 6 0 8 2 5 2 9 2 0 0 7 2 3 6 2 3 1 4 3 6 0 2 2 5...

Страница 6: ...0 6 2 1 0 1 0 1 8 6 2 1 0 1 0 1 0 1 0 1 Z 0 B 0 0 B 1 4 2 A W 6 0 B 3 8 0 2 0 3 2 1 1 3 1 2 2 5 1 5 2 4 1 0 1 2 1 0 1 S Q R Maximum size of the time delay fuse or HACR type circuit breaker for protec...

Страница 7: ...is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moistur...

Страница 8: ...of Energy Energyguide Fact Sheets is based upon the fresh air blank off plate in place and is recommended for maximum energy efficiency The blank off plate is available upon request from the factory a...

Страница 9: ...b b u S s e r u t a e F e t a n i m o d e r P 2 0 0 3 0 4 8 1 1 1 3 F 7 8 T 3 0 0 4 0 4 8 0 2 2 1 A 9 3 5 Q l o o c e g a t s 1 t a e h e g a t s 1 n o o t u a n a F l o o c f f o t a e h m e t s y S...

Страница 10: ...100 200 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS MIS 353 NOTE It is recommended that a bead of silicone caulking be placed behind the side mounting flanges and under the top flashing at the time of insta...

Страница 11: ...Page 9 FIGURE 4 WALL MOUNTING INSTRUCTIONS MIS 549 FIGURE 5 WALL MOUNTING INSTRUCTIONS MIS 548 SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR D...

Страница 12: ...Manual 2100 200 Page 10 MIS 550 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Страница 13: ...Manual 2100 200 Page 11 FIGURE 7 LOW VOLTAGE WIRING MIS 1373...

Страница 14: ...delay On a call for heating circuit R W1 make at the thermostat pulling in heat contact for the strip heat and blower operation On a call for second stage heat R W2 makes bringing on second heat cont...

Страница 15: ...tables can be found later in the manual covering all models It is imperative to match the correct pressure table to the unit by model number ADJUSTMENTS Adjustable Delay on Make and Delay on Break Ti...

Страница 16: ...eps to reinstall REFRIGERANT CHARGE The correct system R 22 charge is shown on the unit rating plate Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperatu...

Страница 17: ...u t e R e r u t a r e p m e T e r u s s e r P 5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1 1 8 1 A W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 1 7 4 9 1 3 7 8 0 2 5 7 3 2 2 7 7 8 3 2 9...

Страница 18: ...F c i r t e m o r a B X X X 2 D A F M r e p m a D r i A h s e r F d e z i r o t o M X X X 2 V R C t s u a h x E h t i w r o t a l i t n e V l a i c r e m m o C X X X 2 M F I E t s u a h x E h t i w r...

Отзывы: