background image

Manual 2100-234

I

Page

12 of 17

WIRING – MAIN POWER

Refer to the unit rating plate for wire sizing information
and maximum fuse or “HACR” type circuit breaker size.
Each outdoor unit is marked with a “Minimum Circuit
Ampacity”.  This means that the field wiring used must
be sized to carry that amount of current.  Depending on
the installed  KW of electric heat, there may be two field
power circuits required.  If this is the case, the unit serial
plate will so indicate.  All models are suitable only for
connection with copper wire.  Each unit and/or wiring
diagram will be marked “Use Copper Conductors Only”.
These instructions 

must be

 adhered to.  Refer to the

National Electrical Code (NEC) for complete current
carrying capacity data on the various insulation grades of
wiring material.  All wiring must conform to NEC and all
local codes.

The electrical data lists fuse and wire sizes (75°C copper)
for all models, including the most commonly used heater
sizes.  Also shown are the number of field power circuits
required for the various models with heaters.

The unit rating plate lists a “Maximum Time Delay Relay
Fuse” of “HACR” type circuit breaker that is to be used
with the equipment.  The correct size must be used for
proper circuit protection and also to assure that there will
be no nuisance tripping due to the momentary high
starting current of the compressor motor.

P

A

T

E

G

N

A

R

0

4

2

-

3

5

2

6

1

2

8

0

2

-

0

2

2

7

8

1

NOTE: The voltage should be measured at the field power

connection point in the unit and while the unit is
operating at full load (maximum amperage
operating condition).

Five (5) wires should be run from thermostat subbase to
the 24V terminal board in the unit.  A five conductor, 18
gauge copper, color-coded thermostat cable is
recommended.  The connection points are shown in
Figure 7.

WIRING – LOW VOLTAGE WIRING

230/208, 1 phase equipment use dual primary voltage
transformers.  All equipment leaves the factory wired on
240V tap.  For 208V operation, reconnect from 240V to
208V tap.  The acceptable operating voltage range for the
240 and 208V taps are:

r

e

m

r

o

f

s

n

a

r

T

A

V

A

L

F

e

g

u

a

G

e

r

i

W

e

c

n

a

t

s

i

D

m

u

m

i

x

a

M

t

e

e

F

n

i

0

4

3

.

2

e

g

u

a

G

0

2

e

g

u

a

G

8

1

e

g

u

a

G

6

1

e

g

u

a

G

4

1

e

g

u

a

G

2

1

5

4

0

6

0

0

1

0

6

1

0

5

2

TABLE  3

THERMOSTAT WIRE SIZE

TABLE  4

WALL THERMOSTAT

t

a

t

s

o

m

r

e

h

T

s

e

r

u

t

a

e

F

e

t

a

n

i

m

o

d

e

r

P

7

5

0

-

3

0

4

8

3

5

1

1

D

0

2

2

5

H

T

t

a

e

H

e

g

a

t

s

1

,

l

o

o

C

e

g

a

t

s

1

e

l

b

a

m

m

a

r

g

o

r

P

-

n

o

N

c

i

n

o

r

t

c

e

l

E

r

e

v

o

e

g

n

a

h

c

l

a

u

n

a

M

r

o

o

t

u

A

8

5

0

-

3

0

4

8

1

5

1

1

D

0

2

2

5

H

T

t

a

e

H

e

g

a

t

s

2

,

l

o

o

C

e

g

a

t

s

2

e

l

b

a

m

m

a

r

g

o

r

P

-

n

o

N

c

i

n

o

r

t

c

e

l

E

r

e

v

o

e

g

n

a

h

c

l

a

u

n

a

M

r

o

o

t

u

A

0

6

0

-

3

0

4

8

)

5

4

4

-

0

2

1

1

(

t

a

e

H

e

g

a

t

s

3

;

l

o

o

C

e

g

a

t

s

3

c

i

n

o

r

t

c

e

l

E

e

l

b

a

m

m

a

r

g

o

r

P

-

n

o

N

/

e

l

b

a

m

m

a

r

g

o

r

P

l

a

n

o

i

t

n

e

v

n

o

C

r

o

P

H

r

e

v

o

e

g

n

a

h

c

l

a

u

n

a

M

r

o

o

t

u

A

Содержание WA121

Страница 1: ...PACKAGE AIR CONDITIONERS Model WA121 INSTALLATION INSTRUCTIONS Manual 2100 234I Supersedes 2100 234H File Volume III Tab 16 Date 08 01 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Mo...

Страница 2: ...nsion 16 Refrigerant Charge 16 Pressure Tables 17 Option Field Installed Accessories 17 Figures Figure 1 Unit Dimensions 5 Figure 2 Blower Damper Assembly 7 Figure 3 Mounting Instructions 9 Figure 4 W...

Страница 3: ...esign for ACCA Manual D Residential Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hamps...

Страница 4: ...0 8 0 1 5 0 8 0 2 0 4 5 7 1 1 8 1 5 7 2 3 1 1 d e d u l c n i s t t a w r e w o l b h t i W WA 12 1 A 00 X X X X X J MODEL NUMBER REVISIONS CONTROL MODULES E Low Ambient Control J Telecommunication VO...

Страница 5: ...Manual 2100 234I Page 5 of 17 FIGURE 1 UNIT DIMENSIONS FACTORY BUILT AT 5 INCHES...

Страница 6: ...Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Vent...

Страница 7: ...service door A 2 inch pleated filter is also available as an optional accessory The internal filter brackets are adjustable to accommodate the 2 inch filter by bending the metal tabs holding the 1 in...

Страница 8: ...unit a different size wall opening is required 2 Locate and mark lag bolt locations if desired See Figure 3 3 Hook top rain flashing under back bend of top Top rain flashing is shipped attached to the...

Страница 9: ...Manual 2100 234I Page 9 of 17 FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 10: ...Manual 2100 234I Page 10 of 17 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 4 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 11: ...Manual 2100 234I Page 11 of 17 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Страница 12: ...T E G N A R 0 4 2 3 5 2 6 1 2 8 0 2 0 2 2 7 8 1 NOTE The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load maximum amperage operat...

Страница 13: ...Manual 2100 234I Page 13 of 17 FIGURE 7 LOW VOLTAGE WIRING...

Страница 14: ...ke is complete and the high pressure switch and low pressure switch if employed is closed the compressor contactor is energized Upon shutdown the delay on break time starts and prevents restart until...

Страница 15: ...38 second DOM 4 0 minute 240 seconds DOB 144 second DOM 5 0 minute 300 seconds DOB 150 second DOM During routine operation of the unit with no power interruptions the compressor will operate on demand...

Страница 16: ...9 o D O e r u t a r e p m e T 2 8 o D O e r u t a r e p m e T 1 2 1 A W 0 0 4 6 5 4 5 7 6 5 6 TABLE 6 SUCTION LINE TEMPERATURE The suction line temperatures in Table 6 are based upon 80 F dry bulb 67...

Страница 17: ...7 2 9 1 9 7 7 0 2 2 8 2 2 2 4 8 8 3 2 7 8 5 5 2 0 9 2 7 2 2 9 0 9 2 5 9 9 0 3 7 9 8 2 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 1 8 8 9 1 5 8 4 1 2 8 8 0 3 2 1 9 7 4 2 4 9 4 6 2 7 9...

Отзывы: